24 en Install the Detector Heads

F220 Series Detectors with F220-B6RS Bases

 

 

4.3Set CleanMe Feature

The Clean Me feature monitors the smoke chamber’s sensitivity and sends a trouble signal to the control panel when the sensitivity degrades to a preset level.

NOTE! When a CleanMe signal is sent to a control panel

i that is not CleanMe compatible, the signal may be misinterprted as an alarm.

To activate the CleanMe feature:

1.Put the detector into sensitivity mode by placing a magnet next to the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 21). Remove the magnet after the first red LED flash and before the third red LED flash.

2.When the magnet is removed, the LED flashes green once and shows the first of two sensitivity displays.

3.When the LED next flashes red, replace the magnet near the T mark (refer to Figure 4.2, Item 8 on page 21).

4.Hold the magnet against the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 21) until the green LED flashes twice and the red LED repeats the sensitivity indication.

5.The detector exits sensitivity mode. If CleanMe has been successfully enabled, the green LED flashes twice in rapid succession every eight seconds indicating that CleanMe is

activated.

To disable CleanMe, repeat this process and verify the double flash returns to a single flash.

4.4Flash Rate and Trouble Indication

These detectors include the Chamber Check Automatic Trouble Indicator that verifies the detector’s calibration is within the factory listed range. NFPA guidelines for sensitivity testing can

F.01U.029.847 -01 2007.02

Installation Manual

Bosch Security Systems, Inc.

Image 24
Contents F220 Series Detectors with F220-B6RS Base Required Maintenance and Testing LegalTrademarks General Information Compatible Control PanelsBase Features F220 Series Detectors About F220 Series Detector Heads2 F220 Series Detector Features 3 F220 Series Heat Detector HeadsTechnical Specifications General Specifications4 F220 Series Smoke Detector Heads Install the Bases Base SpecificationsDetector Specifications Electrical SupervisionPage Wire the Bases Loop Wiring SpecificationsTerminal Connections EOL ResistorsWire Optional Remote Annunciators Wire F220-B6RS Sounder BasesFour-wire Loop Termination NAC Configurations Local Configurations F220-B6RS Local Configuration DIP Switch Settings D275 Wire Power Supervision Modules Wire F220-B6E Power Supervision BaseF220-B6E Wire D275 Power Supervision Module D275Install the Detector Heads Mount the Detector HeadsOptional Locking Bar LED Detector Head Keyed. Do not force them onto the mounting basesTest Mode Sensitivity ModeSet Detector Modes Set CleanMe Feature Flash Rate and Trouble IndicationTest the Installation Inspect the InstallationActivate an Alarm at Each Detector Reset the Control PanelTest Each Detector Test the Alarm Loop Perform Nfpa 72 Required TestingTest any CO Sensors USA