4.2Pulse Report Groups

2000 Series Program Entry Guide 4.0

Receiver

 

 

EN 18

4.2Pulse Report Groups

If you select the Pulse Format you need to set the report code for each report group. Pulse 4x2 reports consist of a four-digit account number, a one-digit report group code, and a one-digit point or User ID number.

For example, a control panel with the Account Number prompt set to 1213, the Rcvr Format prompt set to pulse, the Fire Group prompt set to 3, and Point 1 programmed as a Fire point would send the report shown in Figure 1 for an alarm on Point 1.

Figure 1: Pulse Report Groups

1213 3 1

1

2 3

1 - Account number

2 - Report group

3 - Point, user

The Pulse Format allows for only one digit in the Point, User position. If you install more than eight points and report in Pulse Format, the control panel combines reports as shown in Table 3.

Table 3: Pulse Format

Point Number reported in Pulse

1

2

3

4

5

6

7

8

Format

 

 

 

 

 

 

 

 

Point Number displayed at keypad

1

2

3

4

5

6

7

8

 

9

10

11

12

13

14

15

16

 

 

 

 

 

 

 

 

 

 

17

18

19

20

21

22

23

24

Use the following Pulse Report Groups to designate Pulse Report Group codes for this installation.

Do not duplicate Pulse Report Group codes. You cannot distinguish reports from groups with duplicated codes.

The expanded reports available in Modem II format are not available in the Pulse Format.

2 Fire Group

Default:

0

 

 

Selection:

0 to 9, B to F

 

 

1 to 8

Fire alarm from Points 1 to 24.

 

 

9 or 0

Fire alarm from key A, B, or C. Refer to Section 7.0 ABC Keys.

 

There is no Pulse Format version of the Modem II Alarm Cross Point Report. The Cross Point

 

feature creates two point alarms. Refer to Section 11.0 Point Codes.

 

 

Bosch Security Systems 7/05 35114F

Image 18
Contents Control Panels 2000 SeriesE Version Control Panels Using this Guide for Keypad ProgrammingAbout This Manual Bosch Security Systems 7/05 35114FAn Example, Entering Custom Text Contents2000 Series Program Entry Guide Contents Bosch Security Systems 7/05 35114FFigures Tables2000 Series Program Entry Guide Contents 3 Keyswitch 1.0 System ConfigurationSystem Configuration 2000 Series Program Entry GuideDefault Blank 6 Custom Service TextSystem Configuration 2000 Series Program Entry GuidePhone Routing Set to Yes 2.0 Phone2.1Phone Routing Set to No Phone7 Pt Trbl Route 5 Fire Route6 Non-FireRoute 8 Restoral Route13 Sys Trbl Route 11 Cancel Route12 Sys Trbl Route 14 Duress Route2000 Series Program Entry Guide 15 Test RouteDefault: Local Phone1 O/C Rpts - All On 3.0 ReportsReports 3 Restricted O/C7 AC Fail Buzz/Rpt 5 Cancel Rpt6 Restoral Rpts 2000 Series Program Entry Guide2000 Series Program Entry Guide 8 Point User FlagDefault ReportsEN 2000 Series Program Entry GuideReports Bosch Security Systems | 7/05 | 35114FReceiver 4.0Receiver4.1Modem Reports 1 Rcvr FormatEN 2000 Series Program Entry GuideReceiver Table 2 continuedEN 2000 Series Program Entry GuideReceiver Table 2 continued3 - Point, user 4.2Pulse Report Groups1 - Account number 2 - Report group 2 Fire Group4 Pt Trbl Group 8 Cancel Group3 Non-FireGroup 5 Restoral Group12 Test Group 10 Sys Res Group11 Duress Group 2000 Series Program Entry Guide1 RAM Passcode 5.0 Remote ProgrammingRemote Programming 2 RAM Phone2000 Series Program Entry Guide Remote ProgrammingEN 1 Entry Dly Time 6.0 Open/CloseOpen/Close 2 Exit Dly Time6 Excursion 6.1Step Outside5 No Delay 2000 Series Program Entry Guide6.2Exit 2000 Series Program Entry GuideOpen/Close EN 2000 Series Program Entry GuideOpen/Close Bosch Security Systems 7/05 35114FABC Keys 2 A-KeyAlarm Output7.0ABC Keys 1 A-KeyReport8 B-KeyText 5B-KeyAlarm Report 6 B-KeyOutput 7 B-KeyAck Tone9 C-KeyAlarm Report 10 C-KeyOutputBell 4 Alarm on 2 Fail8.0 Bell 1 Bell TimeEN 2000 Series Program Entry GuideBell Bosch Security Systems 7/05 35114F1 Test Interval 9.0 Test TimerTest Timer 2 Hours to NextTest Timer 2000 Series Program Entry GuideThe report defers one interval from the time of the last report. For example, if theTest Intrvl prompt is set to 1 Day, and the system transmits an Opening Report at 9 00 PM, the interval begins at 9 00 PM. If the system transmitted no other reports before 9 00 PM the following day, at 9 00 PM the system transmits the Test Report 1 Address 2 Address 3 Address 4 Address 5 Address 10.0 Address ConfigurationAddress Configuration 6 Address 7 Address 8 AddressEN Address Configuration2000 Series Program Entry Guide Bosch Security Systems 7/05 35114F1 Point 11.0 Point CodesPoint Codes 2 Point6 Point 4 Point5 Point 7 to 24 Points 7 to2000 Series Program Entry Guide 11.1Digit 1, Point TypeRefer to Section 11.3 Digit 3, Point Options Point CodesPoint Codes 11.3 Digit 3, Point Options2000 Series Program Entry Guide EN2000 Series Program Entry Guide Point CodesEN 2000 Series Program Entry Guide Point CodesEN 2000 Series | Program Entry Guide | Point CodesEN Point Codes the Extended Delay feature2000 Series Program Entry Guide EN11.2Digit 2, Alarm Responses 2000 Series Program Entry GuidePoint Codes Point Codes 11.3Digit 3, Point Options2000 Series Program Entry Guide ENPoint Codes 11.4Digit 4, Device Address2000 Series Program Entry Guide EN11.5Digit 5, Sensor Loop 2000 Series Program Entry GuidePoint Codes EN 2000 Series Program Entry GuidePoint Codes Table 9 Digit Selection Summary11.6 Recommended Point Codes 2000 Series Program Entry GuidePoint Codes 2000 Series Program Entry Guide Point CodesTable 16 Panic Device swinger bypass EN 2000 Series Program Entry GuidePoint Codes Bosch Security Systems 7/05 35114F1 to 24 Point Text 12.0 Point TextPoint Text 2000 Series Program Entry GuideEN 2000 Series Program Entry GuidePoint Text Bosch Security Systems 7/05 35114F13.2Relay Functions 13.0 Relays13.1Relay Function Logic RelaysRelays the Parameter prompt2000 Series Program Entry Guide EN2000 Series Program Entry Guide RelaysEN 13.3Relay Parameters, for Keypad Programming Only 2000 Series Program Entry GuideRelays User Test 2 User Tst, Battery14.0 User Test 1 User Tst, BellEN 2000 Series Program Entry GuideUser Test Bosch Security Systems 7/05 35114F1 Instir Code 15.0 PasscodesPasscodes 2 Passcode Lengththe Passcode Type and to enter a unique 5 Change PasscodePasscode-# passcode for up to eight users1 Supervision Interval 16.0 RF ParametersRF Parameters 2000 Series Program Entry GuideEN 2000 Series Program Entry GuideRF Parameters Bosch Security Systems 7/05 35114F17.0 Program Lock 1 Return to Default3 Disable System Program LockEN 2000 Series Program Entry GuideProgram Lock Bosch Security Systems 7/05 35114F18.2View Mode 18.0Keypad Programming18.1Getting Started Keypad Programming18.5Yes and No Entries 18.3Modify Mode18.4Scroll Lists 18.4 Scroll Lists18.6An Example, Entering Custom Text 2000 Series Program Entry GuideKeypad Programming 18.7Keypad Programming Tips 2000 Series Program Entry GuideKeypad Programming Index 2000 Series Program Entry Guide Index2000 Series Program Entry Guide Index 2000 Series Program Entry Guide Index Technical Support Fairport, NY Customer ServiceBosch Security Systems 130 Perinton Parkway 2005 Bosch Security Systems 35114F