2000 Series Program Entry Guide 3.0 | Reports |
|
|
EN 12
If the system is on with No Delay, alarm output at Terminals 4 and 5 follows the alarm delay programmed here. The alarm sounds at the keypad without delay.
When mixing Delay Alarm points (Digit 2 set for 7 or 8), with No Delay Alarm points (Digit 2 set for 5, 6, or 9), the alarm output follows the programmed alarm delay if Delay Alarm points are faulted first.
255 = Voice Verification: Only set the Delay Alrm Rpt prompt to 255 when using an optional
Duress Reports and A, B, C Key Reports are affected by Alarm Report Delay. These reports are sent immediately in all cases.
The Security Industry Association (SIA) recommends the Delay Alarm Report feature be enabled with the delay set to 15 seconds. Enter 15 at this prompt to comply with the SIA recommendation.
Press the [0] key to disable the Delay Alrm Rpt prompt for all points.
5 Cancel Rpt
Default: | Yes | |
|
|
|
Selection: | Yes, No | |
|
|
|
0 |
| No |
|
|
|
1 |
| Yes |
|
|
|
Set the Cancel Rpt prompt to Yes to enable Cancel Report. If a user turns the system off after an alarm, but before bell time expires, a Cancel Report follows the Alarm Report.
If the user turns the system off before Delay Alrm Rpt prompt time expires, the control panel sends no Alarm, Cancel, or Restoral Report for points programmed with a 2, 3, 7, or 8 in Digit 2 of the point code.
If you set the Cancel Rpt prompt to No, the control panel does not send Cancel Reports.
6 Restoral Rpts
Default: | No | |
Selection: | No, Yes, Delay | |
|
|
|
0 |
| No |
|
|
|
1 |
| Yes |
|
|
|
2 |
| Delay |
|
|
|
Set the Restoral Rpts prompt to Yes to send Restoral Reports to the receiver for all points. The system sends Restoral Reports when points return to normal (not faulted) after an Alarm or Trouble Report.
Set the Restoral Rpts prompt to No to prevent the system from sending Restoral Reports for any point.
Set the Restoral Rpts prompt to Delay to delay sending Restoral Reports until bell time expires.
7 AC Fail Buzz/Rpt
Default: No Buzz, No Report
Selection: No Buzz, No Report
Buzz, No Report
Buzz, Report
Buzz, | |
No Buzz, Report | |
No Buzz, | |
|
|
No Buzz No Report | 0 |
|
|
Buzz, No Report | 1 |
|
|
Buzz, Report | 2 |
|
|
Buzz, | 3 |
|
|
No Buzz Report | 4 |
|
|
No Buzz, | 5 |
|
|
The control panel monitors AC power. When AC power to terminals 1 and 2 is interrupted, the control panel waits 60 seconds. If AC power is not restored within 60 seconds, it provides the response programmed in AC Fail Buzz/Rpt.
When set to No Buzz, No Report the system only flashes the OK light at the keypad to indicate a system trouble. It does not sound the trouble tone or send a report to the receiver.
When set to Buzz, No Report the system flashes the OK light at the keypad to indicate a system trouble and sounds the trouble tone. No report is sent to the receiver.