Bosch Power Tools 2000 11.1Digit 1, Point Type, Refer to .3 Digit 3, Point Options, Point Codes

Page 37
11.1Digit 1, Point Type

2000 Series Program Entry Guide 11.0

Point Codes

 

 

EN 37

11.1Digit 1, Point Type

For Digit 1 selections 3, 4, 5, 6, 7, 8, 9, B, C: If an alarm occurs on these points within 2 minutes of a closing (exit time expired, Excursion/Exit included), the system sends a RECENT CLOSING message with the Alarm Report.

For Digit 1 selections 6, 7, 8, 9, B, C: If these points are faulted at the end of exit delay, the system waits a period equal to entry delay before sending an Alarm Report. If the system is not turned off, it sends an EXIT ERROR message with the Alarm Report.

Set Digit 1 to 0 (zero) for points used for RF keypads and arming devices: If you want to use an RF keypad or other arming device, you must assign each device to a point number in order to learn the device into the system. Set Digit 1 to 0 for RF keypad and arming device points.

Table 5: Digit 1 Selections

Display

Selection

 

Description

0

Disabled

Point does not respond to opens or shorts. Set Digit 1 to 0 if you are using

 

 

this point number for an RF Keypad or arming device.

1

Fire

 

Short on sensor loop starts fire alarm response.

 

 

Open on sensor loop causes trouble response.

 

 

Fire points are not bypassable. Single Ring programming option does not

 

 

apply to Fire points.

 

 

Missing Fire points generate a trouble response when the system is on or

 

 

off.

 

 

2

Fire with Alarm

 

Short on sensor loop starts verification process:

 

 

Verification (use Fire

 

1.

Control panel removes power to Point 1 for 4 seconds to reset smoke

 

 

with Alarm Verification

 

 

detectors.

 

 

for Point 1 only)

 

2.

Short on loop within 120 seconds of reset starts alarm response. If the

 

 

 

 

 

 

 

 

 

point remains normal or open for the 120-second verification window

 

 

 

 

 

no alarm response occurs.

 

 

 

 

3.

Verification is not recommended for RF points.

 

 

 

 

4.

Missing Fire points generate a trouble response when the system is on

 

 

 

 

 

or off.

 

 

 

 

5.

RF Tamper for Fire points generates a trouble response when the

 

 

 

 

 

system is on or off.

 

 

 

 

6.

Do not use Fire Alarm Verification points as Cross or Partner points.

 

 

 

 

 

Refer to Section 11.3 Digit 3, Point Options.

 

Bosch Security Systems 7/05 35114F

Image 37
Contents 2000 Series Control PanelsAbout This Manual Using this Guide for Keypad ProgrammingE Version Control Panels Bosch Security Systems 7/05 35114F2000 Series Program Entry Guide Contents ContentsAn Example, Entering Custom Text Bosch Security Systems 7/05 35114FTables Figures2000 Series Program Entry Guide Contents System Configuration 1.0 System Configuration3 Keyswitch 2000 Series Program Entry GuideSystem Configuration 6 Custom Service TextDefault Blank 2000 Series Program Entry Guide2.1Phone Routing Set to No 2.0 PhonePhone Routing Set to Yes Phone6 Non-FireRoute 5 Fire Route7 Pt Trbl Route 8 Restoral Route12 Sys Trbl Route 11 Cancel Route13 Sys Trbl Route 14 Duress RouteDefault: Local 15 Test Route2000 Series Program Entry Guide PhoneReports 3.0 Reports1 O/C Rpts - All On 3 Restricted O/C6 Restoral Rpts 5 Cancel Rpt7 AC Fail Buzz/Rpt 2000 Series Program Entry GuideDefault 8 Point User Flag2000 Series Program Entry Guide ReportsReports 2000 Series Program Entry GuideEN Bosch Security Systems | 7/05 | 35114F4.1Modem Reports 4.0ReceiverReceiver 1 Rcvr FormatReceiver 2000 Series Program Entry GuideEN Table 2 continuedReceiver 2000 Series Program Entry GuideEN Table 2 continued1 - Account number 2 - Report group 4.2Pulse Report Groups3 - Point, user 2 Fire Group3 Non-FireGroup 8 Cancel Group4 Pt Trbl Group 5 Restoral Group11 Duress Group 10 Sys Res Group12 Test Group 2000 Series Program Entry GuideRemote Programming 5.0 Remote Programming1 RAM Passcode 2 RAM PhoneRemote Programming 2000 Series Program Entry GuideEN Open/Close 6.0 Open/Close1 Entry Dly Time 2 Exit Dly Time5 No Delay 6.1Step Outside6 Excursion 2000 Series Program Entry Guide2000 Series Program Entry Guide 6.2ExitOpen/Close Open/Close 2000 Series Program Entry GuideEN Bosch Security Systems 7/05 35114F7.0ABC Keys 2 A-KeyAlarm OutputABC Keys 1 A-KeyReport9 C-KeyAlarm Report 5B-KeyAlarm Report 6 B-KeyOutput 7 B-KeyAck Tone8 B-KeyText 10 C-KeyOutput8.0 Bell 4 Alarm on 2 FailBell 1 Bell TimeBell 2000 Series Program Entry GuideEN Bosch Security Systems 7/05 35114FTest Timer 9.0 Test Timer1 Test Interval 2 Hours to Next2000 Series Program Entry Guide Test TimerThe report defers one interval from the time of the last report. For example, if theTest Intrvl prompt is set to 1 Day, and the system transmits an Opening Report at 9 00 PM, the interval begins at 9 00 PM. If the system transmitted no other reports before 9 00 PM the following day, at 9 00 PM the system transmits the Test Report Address Configuration 10.0 Address Configuration1 Address 2 Address 3 Address 4 Address 5 Address 6 Address 7 Address 8 Address2000 Series Program Entry Guide Address ConfigurationEN Bosch Security Systems 7/05 35114FPoint Codes 11.0 Point Codes1 Point 2 Point5 Point 4 Point6 Point 7 to 24 Points 7 toRefer to Section 11.3 Digit 3, Point Options 11.1Digit 1, Point Type2000 Series Program Entry Guide Point Codes2000 Series Program Entry Guide 11.3 Digit 3, Point OptionsPoint Codes ENPoint Codes 2000 Series Program Entry GuideEN Point Codes 2000 Series Program Entry GuideEN Point Codes 2000 Series | Program Entry Guide |EN 2000 Series Program Entry Guide the Extended Delay featurePoint Codes EN2000 Series Program Entry Guide 11.2Digit 2, Alarm ResponsesPoint Codes 2000 Series Program Entry Guide 11.3Digit 3, Point OptionsPoint Codes EN2000 Series Program Entry Guide 11.4Digit 4, Device AddressPoint Codes EN2000 Series Program Entry Guide 11.5Digit 5, Sensor LoopPoint Codes Point Codes 2000 Series Program Entry GuideEN Table 9 Digit Selection Summary2000 Series Program Entry Guide 11.6 Recommended Point CodesPoint Codes Point Codes 2000 Series Program Entry GuideTable 16 Panic Device swinger bypass Point Codes 2000 Series Program Entry GuideEN Bosch Security Systems 7/05 35114FPoint Text 12.0 Point Text1 to 24 Point Text 2000 Series Program Entry GuidePoint Text 2000 Series Program Entry GuideEN Bosch Security Systems 7/05 35114F13.1Relay Function Logic 13.0 Relays13.2Relay Functions Relays2000 Series Program Entry Guide the Parameter promptRelays ENRelays 2000 Series Program Entry GuideEN 2000 Series Program Entry Guide 13.3Relay Parameters, for Keypad Programming OnlyRelays 14.0 User Test 2 User Tst, BatteryUser Test 1 User Tst, BellUser Test 2000 Series Program Entry GuideEN Bosch Security Systems 7/05 35114FPasscodes 15.0 Passcodes1 Instir Code 2 Passcode LengthPasscode-# 5 Change Passcodethe Passcode Type and to enter a unique passcode for up to eight usersRF Parameters 16.0 RF Parameters1 Supervision Interval 2000 Series Program Entry GuideRF Parameters 2000 Series Program Entry GuideEN Bosch Security Systems 7/05 35114F3 Disable System 1 Return to Default17.0 Program Lock Program LockProgram Lock 2000 Series Program Entry GuideEN Bosch Security Systems 7/05 35114F18.1Getting Started 18.0Keypad Programming18.2View Mode Keypad Programming18.4Scroll Lists 18.3Modify Mode18.5Yes and No Entries 18.4 Scroll Lists2000 Series Program Entry Guide 18.6An Example, Entering Custom TextKeypad Programming 2000 Series Program Entry Guide 18.7Keypad Programming TipsKeypad Programming 2000 Series Program Entry Guide Index Index2000 Series Program Entry Guide Index 2000 Series Program Entry Guide Index Bosch Security Systems 130 Perinton Parkway Fairport, NY Customer ServiceTechnical Support 2005 Bosch Security Systems 35114F