Bosch Power Tools 2000 manual Series Program Entry Guide, Point Codes

Page 40
Manual background

2000 Series Program Entry Guide 11.0

Point Codes

 

 

EN 40

Table 5: continued

Display

Selection

Description

9

Controlled, Part, No

When control panel is All or Part On (armed), short or open causes alarm

 

Delay

response.

 

 

Part points must be normal (not faulted) or bypassed before control panel

 

 

can be Part armed.

 

 

If an alarm occurs on these points within 2 minutes of a closing (exit time

 

 

expired, Excursion/Exit included), the system sends a RECENT CLOSING

 

 

message with the Alarm Report.

 

 

If these points are faulted at the end of exit delay, the system waits a period

 

 

equal to entry delay before sending an Alarm Report. If the system is not

 

 

turned off, it sends an EXIT ERROR message with the Alarm Report.

 

 

Missing Controlled points generate an alarm response when on, a trouble

 

 

response when off.

 

 

RF Tamper for a Controlled point generates an alarm response when on, a

 

 

trouble response when off.

A

Keyswitch

Shorting then restoring Keyswitch points toggles the control panel from All

 

 

(or Part) On to off, off to All On.

 

 

The trouble option (refer to Section 11.3 Digit 3, Point Options)determines

 

 

how Keyswitch points respond to opens when the system is off. When the

 

 

system is All or Part On, an open produces an alarm response. A keyswitch

 

 

always causes a trouble condition if it is opened in the off state, regardless

 

 

of the value programmed in Digit 3.

 

 

If an alarm occurs on these points within 2 minutes of a closing (exit time

 

 

expired, Excursion/Exit included), the system sends a RECENT CLOSING

 

 

message with the Alarm Report.

 

 

Missing Keyswitch points generate an alarm response when on, a trouble

 

 

response when off.

 

 

RF Tamper for Keyswitch points generates an alarm response when on, a

 

 

trouble response when off.

Bosch Security Systems 7/05 35114F

Image 40
Contents Control Panels 2000 SeriesUsing this Guide for Keypad Programming About This ManualE Version Control Panels Bosch Security Systems 7/05 35114FContents 2000 Series Program Entry Guide ContentsAn Example, Entering Custom Text Bosch Security Systems 7/05 35114FTables Figures2000 Series Program Entry Guide Contents 1.0 System Configuration System Configuration3 Keyswitch 2000 Series Program Entry Guide6 Custom Service Text System ConfigurationDefault Blank 2000 Series Program Entry Guide2.0 Phone 2.1Phone Routing Set to NoPhone Routing Set to Yes Phone5 Fire Route 6 Non-FireRoute7 Pt Trbl Route 8 Restoral Route11 Cancel Route 12 Sys Trbl Route13 Sys Trbl Route 14 Duress Route15 Test Route Default: Local2000 Series Program Entry Guide Phone3.0 Reports Reports1 O/C Rpts - All On 3 Restricted O/C5 Cancel Rpt 6 Restoral Rpts7 AC Fail Buzz/Rpt 2000 Series Program Entry Guide8 Point User Flag Default2000 Series Program Entry Guide Reports2000 Series Program Entry Guide ReportsEN Bosch Security Systems | 7/05 | 35114F4.0Receiver 4.1Modem ReportsReceiver 1 Rcvr Format2000 Series Program Entry Guide ReceiverEN Table 2 continued2000 Series Program Entry Guide ReceiverEN Table 2 continued4.2Pulse Report Groups 1 - Account number 2 - Report group3 - Point, user 2 Fire Group8 Cancel Group 3 Non-FireGroup4 Pt Trbl Group 5 Restoral Group10 Sys Res Group 11 Duress Group12 Test Group 2000 Series Program Entry Guide5.0 Remote Programming Remote Programming1 RAM Passcode 2 RAM PhoneRemote Programming 2000 Series Program Entry GuideEN 6.0 Open/Close Open/Close1 Entry Dly Time 2 Exit Dly Time6.1Step Outside 5 No Delay6 Excursion 2000 Series Program Entry Guide2000 Series Program Entry Guide 6.2ExitOpen/Close 2000 Series Program Entry Guide Open/CloseEN Bosch Security Systems 7/05 35114F2 A-KeyAlarm Output 7.0ABC KeysABC Keys 1 A-KeyReport5B-KeyAlarm Report 6 B-KeyOutput 7 B-KeyAck Tone 9 C-KeyAlarm Report8 B-KeyText 10 C-KeyOutput4 Alarm on 2 Fail 8.0 BellBell 1 Bell Time2000 Series Program Entry Guide BellEN Bosch Security Systems 7/05 35114F9.0 Test Timer Test Timer1 Test Interval 2 Hours to Next2000 Series Program Entry Guide Test TimerThe report defers one interval from the time of the last report. For example, if theTest Intrvl prompt is set to 1 Day, and the system transmits an Opening Report at 9 00 PM, the interval begins at 9 00 PM. If the system transmitted no other reports before 9 00 PM the following day, at 9 00 PM the system transmits the Test Report 10.0 Address Configuration Address Configuration1 Address 2 Address 3 Address 4 Address 5 Address 6 Address 7 Address 8 AddressAddress Configuration 2000 Series Program Entry GuideEN Bosch Security Systems 7/05 35114F11.0 Point Codes Point Codes1 Point 2 Point4 Point 5 Point6 Point 7 to 24 Points 7 to11.1Digit 1, Point Type Refer to Section 11.3 Digit 3, Point Options2000 Series Program Entry Guide Point Codes11.3 Digit 3, Point Options 2000 Series Program Entry GuidePoint Codes ENPoint Codes 2000 Series Program Entry GuideEN Point Codes 2000 Series Program Entry GuideEN Point Codes 2000 Series | Program Entry Guide |EN the Extended Delay feature 2000 Series Program Entry GuidePoint Codes EN2000 Series Program Entry Guide 11.2Digit 2, Alarm ResponsesPoint Codes 11.3Digit 3, Point Options 2000 Series Program Entry GuidePoint Codes EN11.4Digit 4, Device Address 2000 Series Program Entry GuidePoint Codes EN2000 Series Program Entry Guide 11.5Digit 5, Sensor LoopPoint Codes 2000 Series Program Entry Guide Point CodesEN Table 9 Digit Selection Summary2000 Series Program Entry Guide 11.6 Recommended Point CodesPoint Codes Point Codes 2000 Series Program Entry GuideTable 16 Panic Device swinger bypass 2000 Series Program Entry Guide Point CodesEN Bosch Security Systems 7/05 35114F12.0 Point Text Point Text1 to 24 Point Text 2000 Series Program Entry Guide2000 Series Program Entry Guide Point TextEN Bosch Security Systems 7/05 35114F13.0 Relays 13.1Relay Function Logic13.2Relay Functions Relaysthe Parameter prompt 2000 Series Program Entry GuideRelays ENRelays 2000 Series Program Entry GuideEN 2000 Series Program Entry Guide 13.3Relay Parameters, for Keypad Programming OnlyRelays 2 User Tst, Battery 14.0 User TestUser Test 1 User Tst, Bell2000 Series Program Entry Guide User TestEN Bosch Security Systems 7/05 35114F15.0 Passcodes Passcodes1 Instir Code 2 Passcode Length5 Change Passcode Passcode-#the Passcode Type and to enter a unique passcode for up to eight users16.0 RF Parameters RF Parameters1 Supervision Interval 2000 Series Program Entry Guide2000 Series Program Entry Guide RF ParametersEN Bosch Security Systems 7/05 35114F1 Return to Default 3 Disable System17.0 Program Lock Program Lock2000 Series Program Entry Guide Program LockEN Bosch Security Systems 7/05 35114F18.0Keypad Programming 18.1Getting Started18.2View Mode Keypad Programming18.3Modify Mode 18.4Scroll Lists18.5Yes and No Entries 18.4 Scroll Lists2000 Series Program Entry Guide 18.6An Example, Entering Custom TextKeypad Programming 2000 Series Program Entry Guide 18.7Keypad Programming TipsKeypad Programming Index 2000 Series Program Entry Guide Index2000 Series Program Entry Guide Index 2000 Series Program Entry Guide Index Fairport, NY Customer Service Bosch Security Systems 130 Perinton ParkwayTechnical Support 2005 Bosch Security Systems 35114F