Kenmore 153.33114 Draft Hood Installation, Vent Pipe Size, Vent Pipe System, Vent Connectors

Page 19

2000 BTUH

CONFINED

SPACE

1 SQ. INCH PER

2000 BTUH

ALL AIR FROM OUTDOORS USING HORIZONTAL DUCTS

FIGURE 16.

ALTERNATIVE

OPENING

LOCATION

1SQ. INCH

CONFINED

PER3OOOBTUH

SPACE

using the manufacturer's instructions and local codes, rules, or regulations.

IMPORTANT: If you tack the necessary skills required to properly install this venting system, you should not proceed, but get help from a qualified technician.

Draft Hood Installation

L SCREWS (FOUR PROVIDED)

_tP'--'DRAFT HOOD

SLOTJ_ _JACKETTOP p" LSLOT

INSTALL THE DRAFT HOOD WITH

THE FOUR SCREWS PROVIDED.

FIGURE 18.

Align the legs of the draft hood with the slots provided. Insert the legs and secure the draft hood to the water heater's top with the four screws provided as shown in Figure 18. Do not alter the draft hood in any way. If you are replacing an existing water heater, be sure to use the draft hood supplied with this water heater.

Vent Pipe Size

It is important that you follow the guidelines in these instructions for sizing a vent pipe system. If a transition to a larger vent size

is required, the vent transition connection must be made at the draft hood outlet.

ALL AIR FROM OUTDOORS - USING A SINGLE PERMANENT OPENING

FIGURE 17.

Vent Pipe System

This water heater uses a non-direct, single-pipe vent system to remove exhaust gases created by the burning of fossil fuels. Air for combustion is taken from the immediate water heater location or is ducted in from the outside (see "Combustion Air Supply and Ventilation").

This water heater must be properly vented for the removal of exhaust gases to the outside atmosphere. Correct installation of the vent pipe system is mandatory for the proper and efficient operation of this water heater and is an important factor in the life of the unit.

The vent pipe must be installed according to all local and state codes or, in the absence of local and state codes, the "National Fuel Gas Code", ANSI Z223.1(NFPA 54)-current edition. The vent pipe installation must not be obstructed so as to prevent the removal of exhaust gases to the outside atmosphere.

IMPORTANT: The use of vent dampers is not recommended by the manufacturer of this water heater. Although some vent dampers are certified by CSA International, this certification applies to the vent damper device only and does not mean they are certified for use on this water heater.

U.L. recognized fuel gas and carbon monoxide (CO) detectors are recommended in all applications and should be installed

Vent Connectors

1.Type B, Double wall, U.L. Listed Vent Pipe.

2.Single walt Vent Pipe.

Maintain the manufacturer's specified minimum clearance from combustible materials when using type B double walt vent pipe. Vent connectors made of type B, double walt vent pipe material

may pass through walls or partitions constructed of combustible material if the minimum listed clearance is maintained.

Maintain a six inch minimum clearance from all combustible materials when using single walt vent pipe.

IMPORTANT: Single walt vent pipe cannot be used for water heaters located in attics and may not pass through attic spaces, crawl spaces or any confined or inaccessible location. A single wall metal vent connector cannot pass through any interior walt.

When installing a vent connector, please note the following (See Figures 19-21):

Install the vent connector avoiding unnecessary bends, which create resistance to the flow of vent gases.

Install without dips or sags with an upward slope of at least 1/4-inch per foot.

Joints must be fastened by sheet metal screws or other approved means. It must be supported to maintain clearances and prevent separation of joints and damage.

The length of the vent connector cannot exceed 75% of the vertical vent height.

The vent connector must be accessible for cleaning,

19

Image 19
Contents 320391-000 Sears Brands Management CorporationModel No 153.331140 40 Gallon 153.331150 50 GallonImportant Definitions Read and follow water heater warnings and instructionsExplosion Hazard Improper installation and use may result in property damageFire or Explosion Hazard Fire Hazard12-15 InstallationVent Pipe System Draft Hood Installation Vent Connectors 19-20StartUpConditions OperatingtheTemperatureControlSystemService LightingInstructionsYear Limited Warranty on Water Heater Important Information About This Water Heater Excessive Weight HazardModel Materials Needed Status Mark Light Control/Temperature KnobTemperatures shown are approximates and may vary Vent Pipe Inner DoorInstallation Checklist Manual GAS Removing the Old Water HeaterFire or Explosion Hazard Location RequirementsSite Location Carbon Monoxide Poisoning HazardAll water heaters eventually leak Insulation BlanketsProperty Damage Hazard Breathing Hazard Carbon Monoxide GasProperty Damage Hazard Filling the Water HeaterGas Requirements Gas PipingExplosion Hazard Gas Pressure TestingGas Pressure LP Gas OnlyConfined Space Carbon Monoxide WarningUnconfined Space All Air from Inside the BuildingLouvers and Grilles All Air from OutdoorsVent Pipe System Draft Hood InstallationVent Connectors Vent Pipe SizeOpposite wall of the chimney Figure Chimney ConnectionVertical Exhaust Gas Vent Chimney as it may restrict the space between itIsectn 19 MGL Piping InstallationLminimum Closed System/Thermal Expansion Temperature and Pressure Relief ValveIf the Pilot Does Not Light Lighting InstructionsLighting the Pilot If the Status Light Does Not BlinkIgniterGASCONTROL STOP!It is imyou readall safety lightingthe pilotRefertothe UghtingInstructionsinthe Installation Phone. Follow the gas supptiersinstructionsEmergency Shut Down Water Temperature RegulationChecking the Draft Burner FlamesStatus Light Code Normal Flashes Operating the Temperature Control SystemFiue gases may escape if ,vent pipe is not connected Vent System InspectionBurner Inspection Carbon Monoxide and Fire HazardFire and Explosion Hazard HousekeepingAnode Rod Inspection Draining and FlushingService Removing the Burner from the Manifold Burner Assembly Replacement PartsExternal Inspection & Cleaning Base-Ring Filter Removing the Manifold/Burner AssemblyBurneran other Cleaning the Combustion Chamber and Flame-arrestorExplosion Hazard Replacing the Manifold/Burner AssemblyPiezoelectric Igniter System Removing the Gas Control Valve/Thermostat Removing and Replacing the Gas Control Valve/ThermostatStrange Sounds Thermal Ex ansion Tank SpecificationsExpansion Tank Sizing Chart Start Up ConditionsAIR In Hot Water Faucets Safety Shut-off and Thermal SwitchOperational Conditions CondensationBefore installing, operating or servicing this water heater Problem Thermostat Not functioning properly Replace Water heater flue or vent systemBlocked Excessive Waterpressure Use Pressure Reducing ValveNormal Operation Pilot light was recently extinguishedThermopile is cooling DownGas Control Valve failure Temperature Sensor Thermistor Is defective800-4694663 =N01Section Pilot light Repeatedly Goes out 153.331150 Gallon 153.331140 GallonModel Page MY-HOME

153.33114, 153.33115 specifications

The Kenmore 153.33115 and 153.33114 are high-efficiency dehumidifiers designed to effectively manage moisture levels in residential spaces, providing comfort and safeguarding homes against the damaging effects of excess humidity. Both models embody Kenmore's commitment to quality, innovative technologies, and user-friendly features, making them ideal choices for maintaining optimal indoor air quality.

One of the standout features of the Kenmore 153.33115 and 153.33114 is their powerful dehumidification capability. With the capacity to remove up to 70 pints of moisture per day, these dehumidifiers efficiently tackle dampness in areas of up to 1,500 square feet. This makes them suitable for various spaces, including basements, laundry rooms, and even larger living areas, ensuring a healthy environment free from mold and mildew growth.

The models are equipped with an adjustable humidistat, which allows users to set their desired humidity levels easily. This feature not only enhances user control but also ensures energy efficiency by allowing the machines to operate only when necessary. Alongside energy efficiency, these dehumidifiers are designed to comply with Department of Energy guidelines, making them an eco-friendly choice.

Both models also feature a continuous drainage option, enabling hassle-free operation without the need for constant manual emptying of the water tank. When the water tank reaches capacity, an automatic shut-off function prevents overflow, ensuring peace of mind for users.

In terms of convenience, the Kenmore 153.33115 and 153.33114 have a user-friendly digital control panel with an easy-to-read LED display. This intuitive interface makes it simple to adjust settings, check humidity levels, and monitor overall performance. Additionally, the inclusion of wheels and a lightweight design enhances portability, allowing users to move the dehumidifiers where they are needed most.

Another notable aspect is the enhanced air filtration system. These dehumidifiers come with a removable, washable filter that effectively captures dust, allergens, and other airborne particles, contributing to better indoor air quality.

In conclusion, the Kenmore 153.33115 and 153.33114 are exemplary dehumidifiers that combine efficient moisture removal, user-friendly features, and eco-conscious designs. With their robust performance, effective humidity control, and added convenience features, these models stand out as reliable solutions for maintaining a comfortable and healthy indoor environment.