Kenmore 153.33114 Carbon Monoxide Warning, Unconfined Space, All Air from Inside the Building

Page 17

Carbon Monoxide Warning

Follow all the local and state codes or, in the absence of local and state codes, the "National Fuel Gas Code",

ANSI Z223.1 (NFPA 54)- current edition to properly install vent system.

Failure to do so can result in death, explosion, or carbon monoxide poisoning.

IMPORTANT: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage.

The following types of installation (not limited to the following) wilt require outdoor air for combustion due to chemical exposure and may reduce but not eliminate the presence of corrosive chemicals in the air:

beauty shops

photo processing labs

buildings with indoor pools

water heaters installed in laundry, hobby, or craft rooms

water heaters installed near chemical storage areas

Combustion air must be free of acid-forming chemicals such as sulfur, fluorine, and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint, and vamish removers, refrigerants, and many other commercial and household products. When bumed, vapors from these products

form highly corrosive acid compounds. These products should not be stored or used near the water heater or air inlet.

Combustion and ventilation air requirements are determined by the location of the water heater. The water heater may be located in either an open (unconfined) area or in a confined area or small enclosure such as a closet or small room. Confined spaces are areas with tess than 50 cubic feet for each 1,000 BTUH of the total input for all gas-using appliances.

Unconfined Space

A water heater in an unconfined space uses indoor air for combustion and requires at least 50 cubic feet for each 1,000 BTUH of the total input for ait gas appliances. The table below shows a few examples of the minimum square footage (area) required for various BTUH inputs.

TABLE 3

Minimum Square

Typical Room

BTUH Input

Feet with

with 8'Ceiling

 

8'Ceiling

 

 

 

30,000

188

9 x 21

45,000

281

14 x 20

60,000

375

15 x 25

75,000

469

15 x 31

90,000

563

20

x 28

105,000

657

20

x 33

TABLE 3

 

 

 

120,000

750

25

x 30

135,000

844

28

x 30

IMPORTANT:

The area must be open and be able to provide the proper air requirements to the water heater. Areas that are being

used for storage or contain large objects may not be suitable for water heater installation.

Water heaters installed in open spaces in buildings with unusually tight construction may still require outdoor air to function properly. In this situation, outside air openings should be sized the same as for a confined space.

Modern home construction usually requires supplying outside air into the water heater area.

Confined Space

For the correct and proper operation of this water heater, ample air must be supplied for the combustion, ventilation, and dilution of flue gases. Small enclosures and confined areas must have two permanent openings so that sufficient fresh air can be drawn from outside of the enclosure. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure as shown in Figure 12.

The size of each opening (free area) is determined by the total BTUH input of all gas utilization equipment (i.e., water heaters, furnaces, clothes dryers, etc.) and the method by which the air is provided. The BTUH input can be found on the water heater rating plate. Additional air can be provided by two methods:

1.All air from inside the building.

2.All air from outdoors.

12" MAXIMUM

 

 

___

CLOSET

 

 

OR

PERMANENT

--

--

OTHER

OPENINGS TO

 

CONFINED

THE OUTSIDE

OR

 

SPACE

ADDITIONAL

 

 

 

ROOMS WITHIN

THE BUILDING

=:_

12" MAXIMUM /

FIGURE 12.

All Air from Inside the Building

When additional air is to be provided to the confined area from additional room(s) within the building, the total volume of the room(s) must be of sufficient size to properly provide the necessary amount of fresh air to the water heater and other

17

Image 17
Contents Model No Sears Brands Management Corporation153.331140 40 Gallon 153.331150 50 Gallon 320391-000Important Definitions Read and follow water heater warnings and instructionsFire or Explosion Hazard Improper installation and use may result in property damageFire Hazard Explosion HazardVent Pipe System Draft Hood Installation InstallationVent Connectors 19-20 12-15Service OperatingtheTemperatureControlSystemLightingInstructions StartUpConditionsYear Limited Warranty on Water Heater Important Information About This Water Heater Excessive Weight HazardModel Materials Needed Temperatures shown are approximates and may vary Control/Temperature KnobVent Pipe Inner Door Status Mark LightInstallation Checklist Manual GAS Removing the Old Water HeaterSite Location Location RequirementsCarbon Monoxide Poisoning Hazard Fire or Explosion Hazard Property Damage Hazard Insulation Blankets Breathing Hazard Carbon Monoxide Gas All water heaters eventually leakGas Requirements Filling the Water HeaterGas Piping Property Damage HazardGas Pressure Gas Pressure TestingLP Gas Only Explosion HazardUnconfined Space Carbon Monoxide WarningAll Air from Inside the Building Confined SpaceLouvers and Grilles All Air from OutdoorsVent Connectors Draft Hood InstallationVent Pipe Size Vent Pipe SystemVertical Exhaust Gas Vent Chimney ConnectionChimney as it may restrict the space between it Opposite wall of the chimney FigureLminimum Piping InstallationIsectn 19 MGL Closed System/Thermal Expansion Temperature and Pressure Relief ValveLighting the Pilot Lighting InstructionsIf the Status Light Does Not Blink If the Pilot Does Not LightRefertothe UghtingInstructionsinthe Installation STOP!It is imyou readall safety lightingthe pilotPhone. Follow the gas supptiersinstructions IgniterGASCONTROLChecking the Draft Water Temperature RegulationBurner Flames Emergency Shut DownStatus Light Code Normal Flashes Operating the Temperature Control SystemBurner Inspection Vent System InspectionCarbon Monoxide and Fire Hazard Fiue gases may escape if ,vent pipe is not connectedAnode Rod Inspection HousekeepingDraining and Flushing Fire and Explosion HazardService External Inspection & Cleaning Base-Ring Filter Replacement PartsRemoving the Manifold/Burner Assembly Removing the Burner from the Manifold Burner AssemblyBurneran other Cleaning the Combustion Chamber and Flame-arrestorPiezoelectric Igniter System Replacing the Manifold/Burner AssemblyExplosion Hazard Removing the Gas Control Valve/Thermostat Removing and Replacing the Gas Control Valve/ThermostatExpansion Tank Sizing Chart Thermal Ex ansion Tank SpecificationsStart Up Conditions Strange SoundsOperational Conditions Safety Shut-off and Thermal SwitchCondensation AIR In Hot Water FaucetsBefore installing, operating or servicing this water heater Problem Blocked Water heater flue or vent systemExcessive Waterpressure Use Pressure Reducing Valve Thermostat Not functioning properly ReplaceThermopile is cooling Pilot light was recently extinguishedDown Normal OperationGas Control Valve failure Temperature Sensor Thermistor Is defectiveSection Pilot light Repeatedly Goes out =N01800-4694663 Model 153.331140 Gallon153.331150 Gallon Page MY-HOME