Kenmore 153.33115 Start Up Conditions, Thermal Ex ansion Tank Specifications, Strange Sounds

Page 34

Start Up Conditions

Thermal Expansion

Property Damage Hazard

Avoid water heater damage.

Install thermal expansion tank or device if necessary.

Contact qualified installer or service agency.

As water is heated, it expands (thermal expansion). In a closed system, the volume of water wilt grow. As the volume of water grows, there wilt be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve operation: water discharged from the valve due to excessive pressure build up. The temperature-pressure relief valve is not intended for the constant relief of thermal expansion. This condition is not covered under the limited warranty.

A properly sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Thermal expansion tanks are available from Sears stores and through the Sears Service Centers. Contact the local plumbing inspector, water supplier and/or the Sears Service Center for assistance in controlling these situations. See Figure 43.

Table 5: Thermal Ex )ansion Tank Specifications

 

Tank

Dimensions

 

Pipe

Model

Capacity

in Inches

 

Fitting

Number

In Gallons

Diameter

Len£1th

On Tank

153.331020

2

8 (203 mm)

12-3/4 (323

mm)

3/4" Male

 

 

 

153.331050

5

11 (279 mm)

14-3/4 (375

mm)

3/4" Male

Table 6: Expansion Tank Sizing Chart

Inlet* Water Heater Capacity (Gallons)

 

Water

 

 

 

 

 

 

Pressure

30

40

50

66

82

Expansion

40psi

2

2

2

5

5

Tank

50psi

2

2

2

5

5

Capacity

60psi

2

2

5

5

5

Needed

70psi

2

2

5

5

5

 

80psi

2

5

5

5

5

*Highest recorded inlet water pressure in a 24 hour period or regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air charge. If the inlet water pressure is higher than 40 psi, the expansion tank's air pressure must be adjusted to match that pressure, but must not be higher than 80 psi.

WATER HEATER

(3)

HOT

INLET FITTINGREDUCING

_LD_COLD WATERVALVEPRESSUREWITH

BY-PASS

(2)

PRESSURE GAUGEINLET COLD

WATER SHUT-OFF

I

RECOMMENDED

INSTALLATION

I

MOUNTING)

 

(VERTICAL

WATER

HEATER

 

COLD

WATER

 

INLET

FITTING

FLOOR, CEILING JOIST, ETC,

HOT COLD

(3)

PRESSURE

REDUCING

VALVE WITH

(1)BY-PASS

EXPANSION /

/I' t

PRESSURE

GAUGE

INLET COLD

WATER SHUT-OFF

ALTERNATE RECOMMENDED INSTALLATION

(HORIZONTAL MOUNTING)

FIGURE 43.

Strange Sounds

Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not represent harmful or dangerous conditions.

Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal. See "Condensation" section.

Draft Hood Operation

Check draft hood operation by performing a worst case depressurization of the building. With all doors and windows closed, and with all air handling equipment and exhaust fans operating such as furnaces, clothes dryers, range hoods and bathroom fans, a match flame should still be drawn into the draft hood of the water heater with its burner firing. If the flame is not drawn toward the draft hood, shut off water heater and make necessary air supply changes to correct.

34

Image 34
Contents 153.331140 40 Gallon 153.331150 50 Gallon Sears Brands Management CorporationModel No 320391-000Read and follow water heater warnings and instructions Important DefinitionsFire Hazard Improper installation and use may result in property damageFire or Explosion Hazard Explosion HazardVent Connectors 19-20 InstallationVent Pipe System Draft Hood Installation 12-15LightingInstructions OperatingtheTemperatureControlSystemService StartUpConditionsYear Limited Warranty on Water Heater Excessive Weight Hazard Important Information About This Water HeaterModel Materials Needed Vent Pipe Inner Door Control/Temperature KnobTemperatures shown are approximates and may vary Status Mark LightInstallation Checklist Removing the Old Water Heater Manual GASCarbon Monoxide Poisoning Hazard Location RequirementsSite Location Fire or Explosion HazardBreathing Hazard Carbon Monoxide Gas Insulation BlanketsProperty Damage Hazard All water heaters eventually leakGas Piping Filling the Water HeaterGas Requirements Property Damage HazardLP Gas Only Gas Pressure TestingGas Pressure Explosion HazardAll Air from Inside the Building Carbon Monoxide WarningUnconfined Space Confined SpaceAll Air from Outdoors Louvers and GrillesVent Pipe Size Draft Hood InstallationVent Connectors Vent Pipe SystemChimney as it may restrict the space between it Chimney ConnectionVertical Exhaust Gas Vent Opposite wall of the chimney FigureIsectn 19 MGL Piping InstallationLminimum Temperature and Pressure Relief Valve Closed System/Thermal ExpansionIf the Status Light Does Not Blink Lighting InstructionsLighting the Pilot If the Pilot Does Not LightPhone. Follow the gas supptiersinstructions STOP!It is imyou readall safety lightingthe pilotRefertothe UghtingInstructionsinthe Installation IgniterGASCONTROLBurner Flames Water Temperature RegulationChecking the Draft Emergency Shut DownOperating the Temperature Control System Status Light Code Normal FlashesCarbon Monoxide and Fire Hazard Vent System InspectionBurner Inspection Fiue gases may escape if ,vent pipe is not connectedDraining and Flushing HousekeepingAnode Rod Inspection Fire and Explosion HazardService Removing the Manifold/Burner Assembly Replacement PartsExternal Inspection & Cleaning Base-Ring Filter Removing the Burner from the Manifold Burner AssemblyCleaning the Combustion Chamber and Flame-arrestor Burneran otherExplosion Hazard Replacing the Manifold/Burner AssemblyPiezoelectric Igniter System Removing and Replacing the Gas Control Valve/Thermostat Removing the Gas Control Valve/ThermostatStart Up Conditions Thermal Ex ansion Tank SpecificationsExpansion Tank Sizing Chart Strange SoundsCondensation Safety Shut-off and Thermal SwitchOperational Conditions AIR In Hot Water FaucetsBefore installing, operating or servicing this water heater Problem Excessive Waterpressure Use Pressure Reducing Valve Water heater flue or vent systemBlocked Thermostat Not functioning properly ReplaceDown Pilot light was recently extinguishedThermopile is cooling Normal OperationTemperature Sensor Thermistor Is defective Gas Control Valve failure800-4694663 =N01Section Pilot light Repeatedly Goes out 153.331150 Gallon 153.331140 GallonModel Page MY-HOME

153.33114, 153.33115 specifications

The Kenmore 153.33115 and 153.33114 are high-efficiency dehumidifiers designed to effectively manage moisture levels in residential spaces, providing comfort and safeguarding homes against the damaging effects of excess humidity. Both models embody Kenmore's commitment to quality, innovative technologies, and user-friendly features, making them ideal choices for maintaining optimal indoor air quality.

One of the standout features of the Kenmore 153.33115 and 153.33114 is their powerful dehumidification capability. With the capacity to remove up to 70 pints of moisture per day, these dehumidifiers efficiently tackle dampness in areas of up to 1,500 square feet. This makes them suitable for various spaces, including basements, laundry rooms, and even larger living areas, ensuring a healthy environment free from mold and mildew growth.

The models are equipped with an adjustable humidistat, which allows users to set their desired humidity levels easily. This feature not only enhances user control but also ensures energy efficiency by allowing the machines to operate only when necessary. Alongside energy efficiency, these dehumidifiers are designed to comply with Department of Energy guidelines, making them an eco-friendly choice.

Both models also feature a continuous drainage option, enabling hassle-free operation without the need for constant manual emptying of the water tank. When the water tank reaches capacity, an automatic shut-off function prevents overflow, ensuring peace of mind for users.

In terms of convenience, the Kenmore 153.33115 and 153.33114 have a user-friendly digital control panel with an easy-to-read LED display. This intuitive interface makes it simple to adjust settings, check humidity levels, and monitor overall performance. Additionally, the inclusion of wheels and a lightweight design enhances portability, allowing users to move the dehumidifiers where they are needed most.

Another notable aspect is the enhanced air filtration system. These dehumidifiers come with a removable, washable filter that effectively captures dust, allergens, and other airborne particles, contributing to better indoor air quality.

In conclusion, the Kenmore 153.33115 and 153.33114 are exemplary dehumidifiers that combine efficient moisture removal, user-friendly features, and eco-conscious designs. With their robust performance, effective humidity control, and added convenience features, these models stand out as reliable solutions for maintaining a comfortable and healthy indoor environment.