Replacing the Manifold/Burner | Assembly | 10 Follow the lighting instructions on the | front of the water |
|
| heater. With the main burner lit, check for leaks at | |
|
| the manifold and pilot connections by brushing on an | |
|
| approved noncorrosive leak detection solution, or a | |
|
| mixture of hand dish washing soap and water (one part | |
|
| soap to 15 parts water) or childrens soap bubble solution. | |
|
| Bubbles forming indicate a leak. Correct any leak found. | |
|
| Verify proper operation and then replace the outer door. | |
|
| FLAMEARRESTOR | BRACKET |
Explosion Hazard
Tighten both manifold door screws securely.
Remove any fiberglass between gasket and combustion chamber.
Replace viewport if glass is missing or damaged.
Replace manifold component block if missing or removed.
•Replace door gasket if damaged.
•Failure to follow these instructions can result in death, explosion, or fire.
1.Check the door gasket for damage or imbedded debris prior to installation.
2.Inspect the view port for damage and replace as required.
3.Insert the manifold/burner assembly into the burner compartment, making sure that the tip of the manifold tube engages in the slot of the bracket inside the combustion chamber (Figures 40 & 41).
4.Inspect the door gasket and make sure there is no fiberglass insulation between the gasket and the combustion chamber.
5.Tighten the two screws which secure the burner/
manifold assembly to the combustion chamber. There should be no space between the gasket part
of the manifold door and combustion chamber. IMPORTANT: Do not operate the water heater if the door gasket does not create a seal between the manifold door and the combustion chamber.
6.Reconnect the manifold tube (3/4" wrench) and pilot tube
(7/16" wrench) to the gas control valve/thermostat. Do not
1 .) Install the ferrule nut into the gas valve at the pilot tube location, hand tight only. 2.) Insert the pilot tube into the ferrule nut until the tube bottoms out, then tighten the nut with a 7/16" wrench until the crimp connection seals to the pilot tube. Continue to tighten until the nut is tight in the gas valve.
NOTE: L.R Gas systems use reverse
7.Connect the white
8.Reconnect the igniter wire (Figure 33).
9.Turn on the gas supply to the water heater at the manual gas
TiP
FIGURE 40.
THE COMBUSTION CHAMBER.
__SLOT
TIPBRACKET
MANIFOLD TUBE
FIGURE 41.
Piezoelectric Igniter System
The piezoelectric igniter system consists of the igniter button, electrode, and wire. The pilot is ignited by an electric spark generated when the igniter button is pressed. (See Figure 42).
)lie
Pilot/
3lie
Bracket
Electrode
Igniter Button
FIGURE 42.
Testing the Igniter System
Turn off the gas to the water heater at the manual gas
32