Kenmore 153.33115, 153.33114 manual Replacing the Manifold/Burner Assembly, Explosion Hazard

Page 32

Replacing the Manifold/Burner

Assembly

10 Follow the lighting instructions on the

front of the water

 

 

heater. With the main burner lit, check for leaks at

 

 

the manifold and pilot connections by brushing on an

 

 

approved noncorrosive leak detection solution, or a

 

 

mixture of hand dish washing soap and water (one part

 

 

soap to 15 parts water) or childrens soap bubble solution.

 

 

Bubbles forming indicate a leak. Correct any leak found.

 

 

Verify proper operation and then replace the outer door.

 

 

FLAMEARRESTOR

BRACKET

Explosion Hazard

Tighten both manifold door screws securely.

Remove any fiberglass between gasket and combustion chamber.

Replace viewport if glass is missing or damaged.

Replace manifold component block if missing or removed.

Replace door gasket if damaged.

Failure to follow these instructions can result in death, explosion, or fire.

1.Check the door gasket for damage or imbedded debris prior to installation.

2.Inspect the view port for damage and replace as required.

3.Insert the manifold/burner assembly into the burner compartment, making sure that the tip of the manifold tube engages in the slot of the bracket inside the combustion chamber (Figures 40 & 41).

4.Inspect the door gasket and make sure there is no fiberglass insulation between the gasket and the combustion chamber.

5.Tighten the two screws which secure the burner/

manifold assembly to the combustion chamber. There should be no space between the gasket part

of the manifold door and combustion chamber. IMPORTANT: Do not operate the water heater if the door gasket does not create a seal between the manifold door and the combustion chamber.

6.Reconnect the manifold tube (3/4" wrench) and pilot tube

(7/16" wrench) to the gas control valve/thermostat. Do not cross-thread or apply any thread sealant to the fittings. IMPORTANT: If you were supplied with a new ferrule nut in a parts kit, follow these steps:

1 .) Install the ferrule nut into the gas valve at the pilot tube location, hand tight only. 2.) Insert the pilot tube into the ferrule nut until the tube bottoms out, then tighten the nut with a 7/16" wrench until the crimp connection seals to the pilot tube. Continue to tighten until the nut is tight in the gas valve.

NOTE: L.R Gas systems use reverse (left-hand) threads on the manifold tube.

7.Connect the white (-) thermopile wire to the gas control valve/thermostat. Then connect the red thermal switch wires to the thermal switch on the on the manifold door. (Figure 38).

8.Reconnect the igniter wire (Figure 33).

9.Turn on the gas supply to the water heater at the manual gas shut-off valve (Figure 11).

TiP

FIGURE 40.

CLOSE-UPINSIDE VIEW OF

THE COMBUSTION CHAMBER.

__SLOT

TIPBRACKET

MANIFOLD TUBE

FIGURE 41.

Piezoelectric Igniter System

The piezoelectric igniter system consists of the igniter button, electrode, and wire. The pilot is ignited by an electric spark generated when the igniter button is pressed. (See Figure 42).

)lie

Pilot/

3lie

Bracket

Electrode

Igniter Button

FIGURE 42.

Testing the Igniter System

Turn off the gas to the water heater at the manual gas shut-off valve. Watch the electrode tip while activating the igniter. A visible spark should jump from the electrode. To avoid shock, do not touch the burner or any metal part on the pilot or pilot assembly. If no spark is visible, check the wire connections and make sure the electrode is not broken. Replace the igniter if defective. Dirt and rust on the pilot or electrode tip can prevent the igniter spark. Wipe clean with a damp cloth and dry completely. Rust can be removed from the electrode tip and metal surfaces by lightly sanding with an emery cloth or fine grit sandpaper.

32

Image 32
Contents Sears Brands Management Corporation Model No153.331140 40 Gallon 153.331150 50 Gallon 320391-000Read and follow water heater warnings and instructions Important DefinitionsImproper installation and use may result in property damage Fire or Explosion HazardFire Hazard Explosion HazardInstallation Vent Pipe System Draft Hood InstallationVent Connectors 19-20 12-15OperatingtheTemperatureControlSystem ServiceLightingInstructions StartUpConditionsYear Limited Warranty on Water Heater Excessive Weight Hazard Important Information About This Water HeaterModel Materials Needed Control/Temperature Knob Temperatures shown are approximates and may varyVent Pipe Inner Door Status Mark LightInstallation Checklist Removing the Old Water Heater Manual GASLocation Requirements Site LocationCarbon Monoxide Poisoning Hazard Fire or Explosion HazardInsulation Blankets Property Damage HazardBreathing Hazard Carbon Monoxide Gas All water heaters eventually leakFilling the Water Heater Gas RequirementsGas Piping Property Damage HazardGas Pressure Testing Gas PressureLP Gas Only Explosion HazardCarbon Monoxide Warning Unconfined SpaceAll Air from Inside the Building Confined SpaceAll Air from Outdoors Louvers and GrillesDraft Hood Installation Vent ConnectorsVent Pipe Size Vent Pipe SystemChimney Connection Vertical Exhaust Gas VentChimney as it may restrict the space between it Opposite wall of the chimney FigureLminimum Piping InstallationIsectn 19 MGL Temperature and Pressure Relief Valve Closed System/Thermal ExpansionLighting Instructions Lighting the PilotIf the Status Light Does Not Blink If the Pilot Does Not LightSTOP!It is imyou readall safety lightingthe pilot Refertothe UghtingInstructionsinthe InstallationPhone. Follow the gas supptiersinstructions IgniterGASCONTROLWater Temperature Regulation Checking the DraftBurner Flames Emergency Shut DownOperating the Temperature Control System Status Light Code Normal FlashesVent System Inspection Burner InspectionCarbon Monoxide and Fire Hazard Fiue gases may escape if ,vent pipe is not connectedHousekeeping Anode Rod InspectionDraining and Flushing Fire and Explosion HazardService Replacement Parts External Inspection & Cleaning Base-Ring FilterRemoving the Manifold/Burner Assembly Removing the Burner from the Manifold Burner AssemblyCleaning the Combustion Chamber and Flame-arrestor Burneran otherPiezoelectric Igniter System Replacing the Manifold/Burner AssemblyExplosion Hazard Removing and Replacing the Gas Control Valve/Thermostat Removing the Gas Control Valve/ThermostatThermal Ex ansion Tank Specifications Expansion Tank Sizing ChartStart Up Conditions Strange SoundsSafety Shut-off and Thermal Switch Operational ConditionsCondensation AIR In Hot Water FaucetsBefore installing, operating or servicing this water heater Problem Water heater flue or vent system BlockedExcessive Waterpressure Use Pressure Reducing Valve Thermostat Not functioning properly ReplacePilot light was recently extinguished Thermopile is coolingDown Normal OperationTemperature Sensor Thermistor Is defective Gas Control Valve failureSection Pilot light Repeatedly Goes out =N01800-4694663 Model 153.331140 Gallon153.331150 Gallon Page MY-HOME

153.33114, 153.33115 specifications

The Kenmore 153.33115 and 153.33114 are high-efficiency dehumidifiers designed to effectively manage moisture levels in residential spaces, providing comfort and safeguarding homes against the damaging effects of excess humidity. Both models embody Kenmore's commitment to quality, innovative technologies, and user-friendly features, making them ideal choices for maintaining optimal indoor air quality.

One of the standout features of the Kenmore 153.33115 and 153.33114 is their powerful dehumidification capability. With the capacity to remove up to 70 pints of moisture per day, these dehumidifiers efficiently tackle dampness in areas of up to 1,500 square feet. This makes them suitable for various spaces, including basements, laundry rooms, and even larger living areas, ensuring a healthy environment free from mold and mildew growth.

The models are equipped with an adjustable humidistat, which allows users to set their desired humidity levels easily. This feature not only enhances user control but also ensures energy efficiency by allowing the machines to operate only when necessary. Alongside energy efficiency, these dehumidifiers are designed to comply with Department of Energy guidelines, making them an eco-friendly choice.

Both models also feature a continuous drainage option, enabling hassle-free operation without the need for constant manual emptying of the water tank. When the water tank reaches capacity, an automatic shut-off function prevents overflow, ensuring peace of mind for users.

In terms of convenience, the Kenmore 153.33115 and 153.33114 have a user-friendly digital control panel with an easy-to-read LED display. This intuitive interface makes it simple to adjust settings, check humidity levels, and monitor overall performance. Additionally, the inclusion of wheels and a lightweight design enhances portability, allowing users to move the dehumidifiers where they are needed most.

Another notable aspect is the enhanced air filtration system. These dehumidifiers come with a removable, washable filter that effectively captures dust, allergens, and other airborne particles, contributing to better indoor air quality.

In conclusion, the Kenmore 153.33115 and 153.33114 are exemplary dehumidifiers that combine efficient moisture removal, user-friendly features, and eco-conscious designs. With their robust performance, effective humidity control, and added convenience features, these models stand out as reliable solutions for maintaining a comfortable and healthy indoor environment.