New Buck Corporation 32 manual Gas Pressure Check

Page 20
GAS PRESSURE CHECK

GAS PRESSURE CHECK

Check the inlet pressure to the burner to ensure that it is shown in the table below.

NOTE: The pressure check point is located on the right side of the valve facing burner, for SIT Millivolt, and the left side for SIT Modulating.

The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2

psi (3.5kPa).

The appliance must be isolated from the gas supply piping system by closing its equipment shut -off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).

VALVE

(MILLIVOLT)

(SIT MANUAL-MODULATING)

MODEL:

FP32

FP32

FP32

FP32

GAS

Natural

Propane

Natural

Propane

Maximum Heat Input

33,000

33,000

33,000

33,000

Minimum Heat Input

23,000

23,000

12,000

13,000

Gas Inlet Pressure

 

 

 

 

Maximum

10.5ins.W.C.

13ins.W.C.

10.5ins.W.C.

9.0ins.W.C.

Minimum

* 5.0ins.W.C.

*11ins.W.C.

*5.0ins.W.C.

*11ins.W.C.

Manifold Pressure

 

 

 

 

Maximum

3.5ins.W.C.

9.0ins.W.C.

3.5ins.W.C.

9.0ins.W.C.

Minimum

3.0ins.W.C.

8.2ins.W.C.

2.8ins.W.C.

7.2ins.W.C.

NOTE: On initial installation it may be necessary to bleed out air in the gas lines. Do this by holding the control knob and turning the knob to the “PILOT” position for about 30 seconds. To check the regulator pressure, remove the pressure tag plug at the left side of the regulator facing the heater. The pressure should be checked with the heater burning and the control set on high. After measuring the pressure, replace the pressure tap plug, ensuring that there are no leaks.

* For the purpose of minimum input adjustment.

Solid fuels shall not be burned in the same fireplace where an unvented room heater has been installed.

NOTE: The following label has been provided with this appliance and must be read and then attached to the floor of the fireplace or firebox area beneath the appliance. The label is a peel and stick label. Make sure the area is cleaned before attaching the label to it.

Page 18

Image 20
Contents MODEL FREESTANDING FIREPLACE OR WITH ANOPTIONAL WOODEN SURROUND VENT-FREEPage TABLE OF CONTENTS Page SECTION SAFETY INFORMATION WARNINGS Do not try to light any appliance psi 3.5 kPa Figure CEILINGWALL LEFT SIDE7.Place logs on the burner base as shown on page WALL FREESTANDING INSTALLATION MODEL 32 FSWALL WALL ALCOVE INSTALLATIONFOR YOUR SAFETY INSTALLATION OF MODEL 32 WS WS ASSEMBLY INSTRUCTIONSWITH OPTIONAL WOODEN SURROUNDKIT#PA-KDM32 Installation” for minimum clearancesNOTE: See “Producing Adequate Ventilation” page INSTALLATION IN RESIDENTIALOR AFTER-MARKETMOBILE HOMES PRODUCING ADEQUATE VENTILATION DETERMINING FRESH-AIRFLOW FOR HEATER LOCATIONVent-freeheater VENTILATION AIR VENTILATION AIR FROM INSIDE BUILDINGVENTILATION AIR FROM OUTDOORS PREPARING LOG KIT TOP RIGHTTOP LEFT REAR LOG FRONT LOGGAS CONNECTION FLAMEGAS PRESSURE CHECK WHAT TO DO IF YOU SMELL GAS FOR YOUR SAFETY, READ BEFORE LIGHTINGLIGHTING INSTRUCTIONS MILLIVOLT VALVE ITT LIGHTING INSTRUCTIONS PILOT BURNER TO TURN OFF GAS TO APPLIANCEIGNITOR ELECTRODE MANUAL LIGHTING PROCEDURE THERMOSTAT CONTROL OPERATIONOR MANUAL VALVE SIT FOR YOUR SAFETY READ BEFORE LIGHTINGLIGHTING INSTRUCTION MODULATING VALVE SIT LIGHTING INSTRUCTION Page 12.Close access panel door13.Turn on all electrical power to the appliance 15seconds MANUAL LIGHTING PROCEDURETHERMOSTAT CONTROL OPERATION FLAME CHECK FLAMEWIRING DIAGRAM IMPORTANT SAFEGUARDS CLEANINGTROUBLE SHOOTING Air in gas lines when OBSERVED OBSERVED REPAIR PARTS SERVICINGREPLACEMENT PARTS KEY#PART DESCRIPTION PART NUMBERITTGENERAL CONTROLS REPLACEMENT PARTS KEY#PART DESCRIPTION PART NUMBERPILOT 5 6 13Page LIMITED WARRANTY MODEL FP-32 NEW BUCK CORPORATIONPage