Bryant 581A IX. Make Electrical Connections, Field Power Supply, Field Control Wiring

Page 11

WARNING: Do not pressure test gas supply while connected to unit. Always disconnect union before ser- vicing. A hazardous condition could occur resulting in serious injury.

IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5.5 in. wg or greater than 13.0 in. wg.

Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.

Fig. 12 — Condensate Drain Details

NOTE: Trap should be deep enough to offset maximum unit static dif- ference. A 4-in. trap is recommended.

Fig. 13 — Condensate Drain Piping Details

Fig. 14 — Field Gas Piping

IX. STEP 9 — MAKE ELECTRICAL CONNECTIONS

A. Field Power Supply

Unit is factory wired for voltage shown on unit nameplate. Be sure to check for correct voltage.

When installing units, provide disconnect per NEC (National Electrical Code) of adequate size (MOCP [Maximum Over- current protection] of unit is on the informative plate). See Tables 4A and 4B. All field wiring must comply with NEC and local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 15 for power wiring connection to the unit power terminal block and equipment ground.

Route power and ground lines through control box end panel or unit basepan (see Fig. 4) to connections as shown on unit wiring diagram and Fig. 15.

CAUTION: The correct power phasing is critical to the operation of the scroll compressors. An incorrect phasing will result in compressor shutdown on thermal overload and possible damage to compressor. Should this occur, power phase correction must be made to the incoming power.

WARNING: Unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for personal injury of others.

Field wiring must conform to temperature limitations for type “T” wire. All field wiring must comply with NEC and local requirements.

Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt- ages between phases must be balanced within 2%.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.

B. Field Control Wiring

Unit must be controlled with a Bryant-approved accessory thermostat. Install thermostat according to the installation instructions included with accessory. Locate thermostat assembly on a solid interior wall in the conditioned space to sense average temperature.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit into unit to low-voltage connections as shown on unit label wiring dia- gram and in Fig. 16.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.

11

Image 11
Contents Installation Provide Unit Support ContentsSafety Considerations III. RIG and Place Unit II. Remove Shipping RailsRoof Curb Details Shipping Rail Removal Base Unit Dimensions Compressor Physical DataFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Horizontal Applications Vertical ConfigurationIV. Field Fabricate Ductwork Make Unit Duct ConnectionsVII. Trap Condensate Drain VI. Install Flue Hood and Inlet HoodVIII. Install GAS Piping IX. Make Electrical Connections Field Power SupplyField Control Wiring Manual Damper Assembly Install OUTDOOR-AIR HoodFLA MCA Mocp Electrical Data Units Without Convenience OutletElectrical Data Units With Optional Convenience Outlet Outdoor-Air Hood Details XII. NON-FUSED Disconnect XIII. Install ALL AccessoriesSTART-UP III. Refrigerant Service PortsVI. Internal Wiring PRE-START-UPXI. GAS Heat VIII. Condenser Fans and MotorsIX. RETURN-AIR Filters OUTDOOR-AIR Inlet ScreensFan Performance 581A210 Medium Heat Vertical Discharge Units Fan Performance 581A240 Low Heat Vertical Discharge Units Fan Performance 581A210 High Heat Vertical Discharge UnitsFan Performance 581A240 High Heat Vertical Discharge Units Fan Performance 581A240 Medium Heat Vertical Discharge UnitsFan Performance 581A300 Medium Heat Vertical Discharge Units Fan Performance 581A300 Low Heat Vertical Discharge UnitsGeneral Notes for Tables Fan Performance 581A300 High Heat Vertical Discharge UnitsFan Performance 581A210 Low Heat Horizontal Discharge Units Fan Performance 581A240 Low Heat Horizontal Discharge Units Fan Performance 581A210 High Heat Horizontal Discharge UnitsFan Performance 581A240 High Heat Horizontal Discharge Units Fan Performance 581A300 Low Heat Horizontal Discharge Units Fan Performance 581A300 High Heat Horizontal Discharge Units Power Exhaust Fan PerformanceOperation Air Quantity Limits Evaporator Fan Motor SpecificationsXII. Optional ECONOMI$ER Accessory/FIOP Static Pressure in. wgFan Rpm at Motor Pulley Settings EconoMi$er IV Controller Wiring and Operational ModesEconoMi$er IV Component Locations Exploded View Supply-Air Temperature Sensor LocationEconoMi$er IV Wiring Enthalpy Changeover Set Points Page Cooling, Units Without Economizer CO2 Sensor Standard SettingsXII. Operating Sequence Cooling, Units With EconoMi$er Service CleaningCoil Maintenance and Cleaning Recommendation Heating, Units Without EconomizerMain Burner Condensate DrainFilters Outdoor-Air Inlet ScreensII. Lubrication III. Evaporator FAN Service and ReplacementVI. CONDENSER-FAN Adjustment Fig IV. Evaporator FAN Performance AdjustmentBelt Tension Adjustment Belt Tension AdjustmentVIII. Refrigerant Charge VII. Power FailureIX. GAS Valve Adjustment XII. Protective Devices Main BurnersXI. Filter Drier XIV. Control Circuit XV. Replacement PartsXIII. Relief Devices Low Voltage Control Schematic Low Voltage Control Schematic Power Schematic Component Arrangement Cooling Service Analysis Troubleshooting Unit TroubleshootingProblem Cause Remedy Heating Service AnalysisIGC Control Heating and Cooling II. ECONOMI$ER IV Troubleshooting EconoMi$er IV Input/Output Logic EconoMi$er IV Troubleshooting CompletionCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Page Page Pressures START-UP ChecklistTemperatures Electrical
Related manuals
Manual 40 pages 46.88 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.