Bryant 581A operation manual

Page 34

Minimum Position Control

There is a minimum damper position potentiometer on the EconoMi$er IV controller. See Fig. 28. The minimum damper position maintains the minimum airflow into the building during the occupied period.

When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compounds) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation.

When demand ventilation control is not being used, the min- imum position potentiometer should be used to set the occu- pied ventilation position. The maximum demand ventilation position should be turned fully clockwise.

Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10° F temperature difference between the out- door and return-air temperatures. To determine the mini- mum position setting, perform the following procedure:

1.Calculate the appropriate mixed-air temperature using the following formula:

(TO x

OA

) + (TR x

RA

) = TM

100

100

TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature

As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F.

(60 x .10) + (75 x .90) = 73.5 F

2.Disconnect the supply-air sensor from terminals T and T1.

3.Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper posi- tioning is being used, make sure that the terminals are wired according to Fig. 26 and that the minimum position potentiometer is turned fully clockwise.

4.Connect 24 vac across terminals TR and TR1.

5.Carefully adjust the minimum position potentiometer until the measured mixed-air temperature matches the calculated value.

6.Reconnect the supply-air sensor to terminals T and T1.

Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part num- ber S963B1128) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a remote location.

To control the minimum damper position remotely, remove the factory-installed jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied poten- tiometer to the P and P1 terminals on the EconoMi$er IV controller. See Fig. 26.

Damper Movement

Damper movement from full open to full closed (or vice versa) takes up to 21/2 minutes.

Thermostats

The EconoMi$er IV control works with conventional thermo- stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors like the T55 or T56. Connections are made at the thermostat terminal connection board located in the main control box.

Occupancy Control

The factory default configuration for the EconoMi$er IV con- trol is occupied mode. Occupied status is provided by the black jumper from terminal TR to terminal N. When unoccu- pied mode is desired, install a field-supplied timeclock func- tion in place of the jumper between TR and N. See Fig. 26. When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock con- tacts are open (removing the 24-v signal from terminal N), the EconoMi$er IV will be in unoccupied mode.

Demand Control Ventilation

When using the EconoMi$er IV for demand control ventila- tion, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air.

Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.

A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional- anticipatory strategy will cause the fresh air supplied to increase as the room CO2 level increases even though the CO2 set point has not been reached. By the time the CO2 level reaches the set point, the damper will be at maximum ventilation and should maintain the set point.

In order to have the CO2 sensor control the economizer damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.

(TO x

OA

) + (TR x

RA

) = TM

100

100

TO = Outdoor-Air Temperature

OA = Percent of Outdoor Air

TR = Return-Air Temperature

RA = Percent of Return Air

TM = Mixed-Air Temperature

Once base ventilation has been determined, set the mini- mum damper position potentiometer to the correct position.

34

Image 34
Contents Safety Considerations ContentsInstallation Provide Unit Support II. Remove Shipping Rails III. RIG and Place UnitRoof Curb Details Shipping Rail Removal Base Unit Dimensions Physical Data CompressorFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Make Unit Duct Connections Vertical ConfigurationIV. Field Fabricate Ductwork Horizontal ApplicationsVIII. Install GAS Piping VI. Install Flue Hood and Inlet HoodVII. Trap Condensate Drain Field Control Wiring Field Power SupplyIX. Make Electrical Connections Install OUTDOOR-AIR Hood Manual Damper AssemblyElectrical Data Units Without Convenience Outlet FLA MCA MocpElectrical Data Units With Optional Convenience Outlet Outdoor-Air Hood Details XIII. Install ALL Accessories XII. NON-FUSED DisconnectPRE-START-UP III. Refrigerant Service PortsVI. Internal Wiring START-UPOUTDOOR-AIR Inlet Screens VIII. Condenser Fans and MotorsIX. RETURN-AIR Filters XI. GAS HeatFan Performance 581A210 Medium Heat Vertical Discharge Units Fan Performance 581A210 High Heat Vertical Discharge Units Fan Performance 581A240 Low Heat Vertical Discharge UnitsFan Performance 581A240 Medium Heat Vertical Discharge Units Fan Performance 581A240 High Heat Vertical Discharge UnitsFan Performance 581A300 Low Heat Vertical Discharge Units Fan Performance 581A300 Medium Heat Vertical Discharge UnitsFan Performance 581A300 High Heat Vertical Discharge Units General Notes for TablesFan Performance 581A210 Low Heat Horizontal Discharge Units Fan Performance 581A210 High Heat Horizontal Discharge Units Fan Performance 581A240 Low Heat Horizontal Discharge UnitsFan Performance 581A240 High Heat Horizontal Discharge Units Fan Performance 581A300 Low Heat Horizontal Discharge Units Power Exhaust Fan Performance Fan Performance 581A300 High Heat Horizontal Discharge UnitsEvaporator Fan Motor Specifications Operation Air Quantity LimitsEconoMi$er IV Controller Wiring and Operational Modes Accessory/FIOP Static Pressure in. wgFan Rpm at Motor Pulley Settings XII. Optional ECONOMI$ERSupply-Air Temperature Sensor Location EconoMi$er IV Component Locations Exploded ViewEconoMi$er IV Wiring Enthalpy Changeover Set Points Page XII. Operating Sequence CO2 Sensor Standard SettingsCooling, Units Without Economizer Heating, Units Without Economizer Service CleaningCoil Maintenance and Cleaning Recommendation Cooling, Units With EconoMi$erOutdoor-Air Inlet Screens Condensate DrainFilters Main BurnerIII. Evaporator FAN Service and Replacement II. LubricationBelt Tension Adjustment IV. Evaporator FAN Performance AdjustmentBelt Tension Adjustment VI. CONDENSER-FAN Adjustment FigIX. GAS Valve Adjustment VII. Power FailureVIII. Refrigerant Charge XI. Filter Drier Main BurnersXII. Protective Devices XIII. Relief Devices XV. Replacement PartsXIV. Control Circuit Low Voltage Control Schematic Low Voltage Control Schematic Power Schematic Component Arrangement Troubleshooting Unit Troubleshooting Cooling Service AnalysisHeating Service Analysis Problem Cause RemedyIGC Control Heating and Cooling II. ECONOMI$ER IV Troubleshooting EconoMi$er IV Troubleshooting Completion EconoMi$er IV Input/Output LogicCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Page Page Electrical START-UP ChecklistTemperatures Pressures
Related manuals
Manual 40 pages 46.88 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.