Bryant 581A VII. Power Failure, VIII. Refrigerant Charge, IX. GAS Valve Adjustment

Page 40

VII. POWER FAILURE

Dampers have a spring return. In event of power failure, dampers will return to fully closed position until power is restored. Do not manually operate damper motor.

VIII. REFRIGERANT CHARGE

Amount of refrigerant charge is listed on unit nameplate and in Table 1. Refer to GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures. Unit panels must be in place when unit is operating during charging procedure.

NOTE: Do not use recycled refrigerant as it may contain contaminants.

A. No Charge

Use standard evacuating techniques. After evacuating sys- tem, weigh in the specified amount of refrigerant (refer to Table 1).

B. Low Charge Cooling

Using cooling charging chart (see Fig. 35-37), add or remove refrigerant until conditions of the chart are met. An accurate pressure gage and temperature-sensing device is required. Charging is accomplished by ensuring the proper amount of liquid subcooling. Measure liquid line pressure at the liquid line service valve using pressure gage. Connect temperature sensing device to the liquid line near the liquid line service valve and insulate it so that outdoor ambient temperature does not affect reading.

C. To Use the Cooling Charging Chart

Use the above temperature and pressure readings, and find the intersection point on the cooling charging chart. If inter- section point on chart is above line, add refrigerant. If inter- section point on chart is below line, carefully recover some of the charge. Recheck suction pressure as charge is adjusted.

NOTE: Indoor-air cfm must be within normal operating range of unit. All outdoor fans must be operating.

The TXV (thermostatic expansion valve) is set to maintain between 10 and 15 degrees of superheat at the com- pressors. The valves are factory set and should not require re-adjustment.

IX. GAS VALVE ADJUSTMENT

A. Natural Gas

The gas valve opens and closes in response to the thermostat or limit control.

When power is supplied to valve terminals W2 (High Fire) and C1, the main valve opens to its preset position.

The regular factory setting is stamped on the valve body. The setting is 3.00 in. wg for vertical supply/discharge units. The setting is 2.95 in. wg for horizontal supply/discharge units.

To adjust regulator:

1.Set unit at setting for no call for heat.

2.Turn main gas valve to OFF position.

3.Remove 1/8-in. pipe plug from manifold or gas valve pressure tap connection. Install a suitable pressure- measuring device.

4.Set main gas valve to ON position.

5.Set thermostat at setting to call for heat.

6.Remove screw cap covering regulator adjustment screw (see Fig. 38).

7.Turn adjustment screw clockwise to increase pres- sure or counterclockwise to decrease pressure.

LEGEND

TXV — Thermostatic Expansion Valve

Fig. 35 — Cooling Charging Chart — 581A210 Units

LEGEND

TXV — Thermostatic Expansion Valve

Fig. 36 — Cooling Charging Chart — 581A240 Units

LEGEND

TXV — Thermostatic Expansion Valve

Fig. 37 — Cooling Charging Chart — 581A300 Units

40

Image 40
Contents Safety Considerations ContentsInstallation Provide Unit Support II. Remove Shipping Rails III. RIG and Place UnitRoof Curb Details Shipping Rail Removal Base Unit Dimensions Physical Data CompressorFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Vertical Configuration IV. Field Fabricate DuctworkMake Unit Duct Connections Horizontal ApplicationsVIII. Install GAS Piping VI. Install Flue Hood and Inlet HoodVII. Trap Condensate Drain Field Control Wiring Field Power SupplyIX. Make Electrical Connections Install OUTDOOR-AIR Hood Manual Damper AssemblyElectrical Data Units Without Convenience Outlet FLA MCA MocpElectrical Data Units With Optional Convenience Outlet Outdoor-Air Hood Details XIII. Install ALL Accessories XII. NON-FUSED DisconnectIII. Refrigerant Service Ports VI. Internal WiringPRE-START-UP START-UPVIII. Condenser Fans and Motors IX. RETURN-AIR FiltersOUTDOOR-AIR Inlet Screens XI. GAS HeatFan Performance 581A210 Medium Heat Vertical Discharge Units Fan Performance 581A210 High Heat Vertical Discharge Units Fan Performance 581A240 Low Heat Vertical Discharge UnitsFan Performance 581A240 Medium Heat Vertical Discharge Units Fan Performance 581A240 High Heat Vertical Discharge UnitsFan Performance 581A300 Low Heat Vertical Discharge Units Fan Performance 581A300 Medium Heat Vertical Discharge UnitsFan Performance 581A300 High Heat Vertical Discharge Units General Notes for TablesFan Performance 581A210 Low Heat Horizontal Discharge Units Fan Performance 581A210 High Heat Horizontal Discharge Units Fan Performance 581A240 Low Heat Horizontal Discharge UnitsFan Performance 581A240 High Heat Horizontal Discharge Units Fan Performance 581A300 Low Heat Horizontal Discharge Units Power Exhaust Fan Performance Fan Performance 581A300 High Heat Horizontal Discharge UnitsEvaporator Fan Motor Specifications Operation Air Quantity LimitsAccessory/FIOP Static Pressure in. wg Fan Rpm at Motor Pulley SettingsEconoMi$er IV Controller Wiring and Operational Modes XII. Optional ECONOMI$ERSupply-Air Temperature Sensor Location EconoMi$er IV Component Locations Exploded ViewEconoMi$er IV Wiring Enthalpy Changeover Set Points Page XII. Operating Sequence CO2 Sensor Standard SettingsCooling, Units Without Economizer Service Cleaning Coil Maintenance and Cleaning RecommendationHeating, Units Without Economizer Cooling, Units With EconoMi$erCondensate Drain FiltersOutdoor-Air Inlet Screens Main BurnerIII. Evaporator FAN Service and Replacement II. LubricationIV. Evaporator FAN Performance Adjustment Belt Tension AdjustmentBelt Tension Adjustment VI. CONDENSER-FAN Adjustment FigIX. GAS Valve Adjustment VII. Power FailureVIII. Refrigerant Charge XI. Filter Drier Main BurnersXII. Protective Devices XIII. Relief Devices XV. Replacement PartsXIV. Control Circuit Low Voltage Control Schematic Low Voltage Control Schematic Power Schematic Component Arrangement Troubleshooting Unit Troubleshooting Cooling Service AnalysisHeating Service Analysis Problem Cause RemedyIGC Control Heating and Cooling II. ECONOMI$ER IV Troubleshooting EconoMi$er IV Troubleshooting Completion EconoMi$er IV Input/Output LogicCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Page Page START-UP Checklist TemperaturesElectrical Pressures
Related manuals
Manual 40 pages 46.88 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.