Page 42

B. High-Pressure and Low-Pressure Switches

If either switch trips, or if the compressor overtemperature switch activates, that refrigerant circuit will be automati- cally locked out by the CLO. To reset, manually move the thermostat setting.

C. Freeze Protection Thermostat (FPT)

An FPT is located on the top and bottom of the evaporator coil. They detect frost build-up and turn off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized by resetting the compressor lockout.

D. Evaporator Fan Motor Protection

A manual reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker.

E. Condenser-Fan Motor Protection

Each condenser-fan motor is internally protected against overtemperature.

Fuses are also located in the control box and feed power to the condenser fan motors. Always replace blown fuses with the correct size fuse as indicated on the unit fuse label.

XIII. RELIEF DEVICES

All units have relief devices to protect against damage from excessive pressures (i.e., fire). These devices protect the high and low side.

XIV. CONTROL CIRCUIT, 24-V

Each control circuit is protected against overcurrent by a

3.2amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting. See Fig. 40-42 for wiring.

SEE DETAIL “C”

XV. REPLACEMENT PARTS

A complete list of replacement parts may be obtained from any Bryant distributor upon request.

XVI. DIAGNOSTIC LEDs

The IGC control board has a LED for diagnostic purposes. The IGC error codes are shown in Table 33.

Table 33 — IGC LED Indications

ERROR CODE

LED INDICATION

Normal Operation

On

Hardware Failure

Off

Fan On/Off Delay Modified

1 Flash

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Five Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Inducer Switch Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

Software Lockout

9 Flashes

LEGEND

 

IGC — Integrated Gas Unit Controller

 

LED — Light-Emitting Diode

 

NOTES:

1.There is a 3-second pause between error code displays.

2.If more than one error code exists, all applicable error codes will be displayed in numerical sequence.

3.Error codes on the IGC will be lost if power to the unit is interrupted.

Fig. 39 — Spark Gap Adjustment

42

Image 42
Contents Contents Safety ConsiderationsInstallation Provide Unit Support II. Remove Shipping Rails III. RIG and Place UnitRoof Curb Details Shipping Rail Removal Base Unit Dimensions Physical Data CompressorFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Make Unit Duct Connections Vertical ConfigurationIV. Field Fabricate Ductwork Horizontal ApplicationsVI. Install Flue Hood and Inlet Hood VIII. Install GAS PipingVII. Trap Condensate Drain Field Power Supply Field Control WiringIX. Make Electrical Connections Install OUTDOOR-AIR Hood Manual Damper AssemblyElectrical Data Units Without Convenience Outlet FLA MCA MocpElectrical Data Units With Optional Convenience Outlet Outdoor-Air Hood Details XIII. Install ALL Accessories XII. NON-FUSED DisconnectPRE-START-UP III. Refrigerant Service PortsVI. Internal Wiring START-UPOUTDOOR-AIR Inlet Screens VIII. Condenser Fans and MotorsIX. RETURN-AIR Filters XI. GAS HeatFan Performance 581A210 Medium Heat Vertical Discharge Units Fan Performance 581A210 High Heat Vertical Discharge Units Fan Performance 581A240 Low Heat Vertical Discharge UnitsFan Performance 581A240 Medium Heat Vertical Discharge Units Fan Performance 581A240 High Heat Vertical Discharge UnitsFan Performance 581A300 Low Heat Vertical Discharge Units Fan Performance 581A300 Medium Heat Vertical Discharge UnitsFan Performance 581A300 High Heat Vertical Discharge Units General Notes for TablesFan Performance 581A210 Low Heat Horizontal Discharge Units Fan Performance 581A210 High Heat Horizontal Discharge Units Fan Performance 581A240 Low Heat Horizontal Discharge UnitsFan Performance 581A240 High Heat Horizontal Discharge Units Fan Performance 581A300 Low Heat Horizontal Discharge Units Power Exhaust Fan Performance Fan Performance 581A300 High Heat Horizontal Discharge UnitsEvaporator Fan Motor Specifications Operation Air Quantity LimitsEconoMi$er IV Controller Wiring and Operational Modes Accessory/FIOP Static Pressure in. wgFan Rpm at Motor Pulley Settings XII. Optional ECONOMI$ERSupply-Air Temperature Sensor Location EconoMi$er IV Component Locations Exploded ViewEconoMi$er IV Wiring Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings XII. Operating SequenceCooling, Units Without Economizer Heating, Units Without Economizer Service CleaningCoil Maintenance and Cleaning Recommendation Cooling, Units With EconoMi$erOutdoor-Air Inlet Screens Condensate DrainFilters Main BurnerIII. Evaporator FAN Service and Replacement II. LubricationBelt Tension Adjustment IV. Evaporator FAN Performance AdjustmentBelt Tension Adjustment VI. CONDENSER-FAN Adjustment FigVII. Power Failure IX. GAS Valve AdjustmentVIII. Refrigerant Charge Main Burners XI. Filter DrierXII. Protective Devices XV. Replacement Parts XIII. Relief DevicesXIV. Control Circuit Low Voltage Control Schematic Low Voltage Control Schematic Power Schematic Component Arrangement Troubleshooting Unit Troubleshooting Cooling Service AnalysisHeating Service Analysis Problem Cause RemedyIGC Control Heating and Cooling II. ECONOMI$ER IV Troubleshooting EconoMi$er IV Troubleshooting Completion EconoMi$er IV Input/Output LogicCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Page Page Electrical START-UP ChecklistTemperatures Pressures
Related manuals
Manual 40 pages 46.88 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.