Bryant 581A operation manual EconoMi$er IV Wiring

Page 32

Differential Dry Bulb Control

For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional acces- sory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 26.

In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower tem- perature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy set point potentiom- eter fully clockwise to the D setting.

Outdoor Enthalpy Changeover

For enthalpy control, accessory enthalpy sensor (part num- ber HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum posi- tion. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. The set points are A, B, C, and D. See Fig. 27. The factory-installed 620-ohm jumper must be in place across terminals SR and + on the EconoMi$er IV con- troller. See Fig. 26.

Differential Enthalpy Control

For differential enthalpy control, the EconoMi$er IV control- ler uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.

Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. Mount the return-air enthalpy sensor in the return-air duct. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 26. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting. See Fig. 28.

Indoor Air Quality (IAQ) Sensor Input

The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return-air duct.

Mount the optional IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV (demand controlled ventilation) potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined set point. See Fig. 29.

If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.

Exhaust Set Point Adjustment

The exhaust set point will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 28. The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.

LEGEND

IA — Indoor Air

IAQ — Indoor Air Quality

OA — Outdoor Air

OAS— Outdoor-Air Temperature Sensor

PL — Plug

RAS— Return-Air Temperature Sensor

SAT — Supply-Air Temperature Sensor

Fig. 26 — EconoMi$er IV Wiring

32

Image 32
Contents Installation Provide Unit Support ContentsSafety Considerations II. Remove Shipping Rails III. RIG and Place UnitRoof Curb Details Shipping Rail Removal Base Unit Dimensions Physical Data CompressorFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Vertical Configuration IV. Field Fabricate DuctworkMake Unit Duct Connections Horizontal ApplicationsVII. Trap Condensate Drain VI. Install Flue Hood and Inlet HoodVIII. Install GAS Piping IX. Make Electrical Connections Field Power SupplyField Control Wiring Install OUTDOOR-AIR Hood Manual Damper AssemblyElectrical Data Units Without Convenience Outlet FLA MCA MocpElectrical Data Units With Optional Convenience Outlet Outdoor-Air Hood Details XIII. Install ALL Accessories XII. NON-FUSED DisconnectIII. Refrigerant Service Ports VI. Internal WiringPRE-START-UP START-UPVIII. Condenser Fans and Motors IX. RETURN-AIR FiltersOUTDOOR-AIR Inlet Screens XI. GAS HeatFan Performance 581A210 Medium Heat Vertical Discharge Units Fan Performance 581A210 High Heat Vertical Discharge Units Fan Performance 581A240 Low Heat Vertical Discharge UnitsFan Performance 581A240 Medium Heat Vertical Discharge Units Fan Performance 581A240 High Heat Vertical Discharge UnitsFan Performance 581A300 Low Heat Vertical Discharge Units Fan Performance 581A300 Medium Heat Vertical Discharge UnitsFan Performance 581A300 High Heat Vertical Discharge Units General Notes for TablesFan Performance 581A210 Low Heat Horizontal Discharge Units Fan Performance 581A210 High Heat Horizontal Discharge Units Fan Performance 581A240 Low Heat Horizontal Discharge UnitsFan Performance 581A240 High Heat Horizontal Discharge Units Fan Performance 581A300 Low Heat Horizontal Discharge Units Power Exhaust Fan Performance Fan Performance 581A300 High Heat Horizontal Discharge UnitsEvaporator Fan Motor Specifications Operation Air Quantity LimitsAccessory/FIOP Static Pressure in. wg Fan Rpm at Motor Pulley SettingsEconoMi$er IV Controller Wiring and Operational Modes XII. Optional ECONOMI$ERSupply-Air Temperature Sensor Location EconoMi$er IV Component Locations Exploded ViewEconoMi$er IV Wiring Enthalpy Changeover Set Points Page Cooling, Units Without Economizer CO2 Sensor Standard SettingsXII. Operating Sequence Service Cleaning Coil Maintenance and Cleaning RecommendationHeating, Units Without Economizer Cooling, Units With EconoMi$erCondensate Drain FiltersOutdoor-Air Inlet Screens Main BurnerIII. Evaporator FAN Service and Replacement II. LubricationIV. Evaporator FAN Performance Adjustment Belt Tension AdjustmentBelt Tension Adjustment VI. CONDENSER-FAN Adjustment FigVIII. Refrigerant Charge VII. Power FailureIX. GAS Valve Adjustment XII. Protective Devices Main BurnersXI. Filter Drier XIV. Control Circuit XV. Replacement PartsXIII. Relief Devices Low Voltage Control Schematic Low Voltage Control Schematic Power Schematic Component Arrangement Troubleshooting Unit Troubleshooting Cooling Service AnalysisHeating Service Analysis Problem Cause RemedyIGC Control Heating and Cooling II. ECONOMI$ER IV Troubleshooting EconoMi$er IV Troubleshooting Completion EconoMi$er IV Input/Output LogicCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Page Page START-UP Checklist TemperaturesElectrical Pressures
Related manuals
Manual 40 pages 46.88 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.