Bryant 581A operation manual Install OUTDOOR-AIR Hood, Manual Damper Assembly

Page 12

 

LEGEND

EQUIP — Equipment

GND

Ground

NEC

National Electrical Code

TB

Terminal Board

NOTE: The maximum wire size for TB1 is 2/0.

Fig. 15 — Field Power Wiring Connections

THERMOSTAT ASSEMBLY

 

REMOVABLE JUMPER

 

 

 

 

 

 

 

RH RC

Y1

Y2

W1

W2

G

L

X

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB2-

R

Y1

Y2

W1

W2

G

C

X

 

J11

1

2

3

4

5

6

7

8

 

 

 

 

 

 

 

 

Fig. 16 — Field Control Thermostat Wiring

 

 

Set heat anticipator settings as follows:

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE

 

STAGE 1

 

 

STAGE 1 AND 2

 

 

 

(W1) ON

 

(W1 AND W2) ON

 

 

 

 

 

 

 

 

 

All

 

0.15

 

 

 

0.30

 

 

Settings may be changed slightly to provide a greater degree of comfort for a particular installation.

X. STEP 10 — INSTALL OUTDOOR-AIR HOOD

Perform the following procedure to install the outdoor-air hood on units equipped with an economizer, two-position damper, or manual outdoor air damper:

1.Remove blank panel from return end of unit (hood section). Save the screws. See Fig. 17 for shipping location of components.

2.Hood sides are fastened to sides of outdoor air open- ing. Remove the hood sides and save the screws (3 each side).

3.Remove the bracket holding the bottom half of the hood in the shipping position. Remove the hood bot- tom half and filters (or manual dampers on units so equipped) from outdoor section.

NOTE: On units without economizers, the compo- nents are attached to the unit basepan. To access the components, remove the panel below the outdoor air intake section.

4.Remove inner filter track from shipping position in outdoor section. Position inner filter track so the

track is facing outward from the unit. Install the fil- ter track with 4 screws provided.

5.Apply seal strip (provided) to back flange of both hood sides where hood side connects to the unit back panel. See Fig. 18.

6.Apply seal strip (provided) to top flange of both hood sides where hood sides connect to the hood top pan- els. See Fig. 18.

7.Install hood sides to the back panels using the screws from Step 2. The sloped flanges point outward. The drip edges of the side panels should face outward as well. Attach the filter guides to the hood sides. The flanges of the filter guides should face inward to hold the filters in place. See Fig. 18.

8.Apply seal strip along the entire length of the bottom flange of the hood top. See Fig. 18.

9.Install the bottom part of the hood top using 4 screws provided. See Fig. 18.

10.Remove the packaging from filters (3) and install into the filter tracks. Slide the filters to the sides then place the last filter into the center of the filter track.

NOTE: For units with manual dampers, replace the end filters with the manual dampers. Install the filter in the center between the manual dampers.

11.Install the filter retainer track along the bottom edge of the outdoor air hood using 4 screws provided. See Fig. 18.

12. Install top section of the outdoor air hood using 9 screws provided. See Fig. 18. See Fig. 19 for a pic- ture of the assembled outdoor air hood.

NOTE: For filter removal, remove the four screws holding the filter retainer. The filters can then be removed, cleaned, or replaced. Install the filters by reversing the procedure.

A. Manual Damper Assembly

For units equipped with manual dampers, the assembly pro- cess is similar to the outdoor air hood for units with econo- mizers. There are two slide dampers shipped with the unit to allow for manual setting of the outside air volume. When assembling the hood, place one of the manual slide dampers in each of the end positions and the remaining filter in the center position. The manual dampers can then be moved to the appropriate position and then locked into place using the screws mounted in the adjustment slots. See Fig. 20.

 

HOOD

HOOD TOP

HOOD TOP

SIDE

(BOTTOM HALF)

 

 

(TOP HALF)

 

 

HOOD

 

 

SIDE

 

 

RETURN AIR

 

 

SECTION

 

 

Fig. 17 — Outdoor-Air Hood Component

Shipping Location

12

Image 12
Contents Contents Safety ConsiderationsInstallation Provide Unit Support II. Remove Shipping Rails III. RIG and Place UnitRoof Curb Details Shipping Rail Removal Base Unit Dimensions Physical Data CompressorFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Vertical Configuration IV. Field Fabricate DuctworkMake Unit Duct Connections Horizontal ApplicationsVI. Install Flue Hood and Inlet Hood VIII. Install GAS PipingVII. Trap Condensate Drain Field Power Supply Field Control WiringIX. Make Electrical Connections Install OUTDOOR-AIR Hood Manual Damper AssemblyElectrical Data Units Without Convenience Outlet FLA MCA MocpElectrical Data Units With Optional Convenience Outlet Outdoor-Air Hood Details XIII. Install ALL Accessories XII. NON-FUSED DisconnectIII. Refrigerant Service Ports VI. Internal WiringPRE-START-UP START-UPVIII. Condenser Fans and Motors IX. RETURN-AIR FiltersOUTDOOR-AIR Inlet Screens XI. GAS HeatFan Performance 581A210 Medium Heat Vertical Discharge Units Fan Performance 581A210 High Heat Vertical Discharge Units Fan Performance 581A240 Low Heat Vertical Discharge UnitsFan Performance 581A240 Medium Heat Vertical Discharge Units Fan Performance 581A240 High Heat Vertical Discharge UnitsFan Performance 581A300 Low Heat Vertical Discharge Units Fan Performance 581A300 Medium Heat Vertical Discharge UnitsFan Performance 581A300 High Heat Vertical Discharge Units General Notes for TablesFan Performance 581A210 Low Heat Horizontal Discharge Units Fan Performance 581A210 High Heat Horizontal Discharge Units Fan Performance 581A240 Low Heat Horizontal Discharge UnitsFan Performance 581A240 High Heat Horizontal Discharge Units Fan Performance 581A300 Low Heat Horizontal Discharge Units Power Exhaust Fan Performance Fan Performance 581A300 High Heat Horizontal Discharge UnitsEvaporator Fan Motor Specifications Operation Air Quantity LimitsAccessory/FIOP Static Pressure in. wg Fan Rpm at Motor Pulley SettingsEconoMi$er IV Controller Wiring and Operational Modes XII. Optional ECONOMI$ERSupply-Air Temperature Sensor Location EconoMi$er IV Component Locations Exploded ViewEconoMi$er IV Wiring Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings XII. Operating SequenceCooling, Units Without Economizer Service Cleaning Coil Maintenance and Cleaning RecommendationHeating, Units Without Economizer Cooling, Units With EconoMi$erCondensate Drain FiltersOutdoor-Air Inlet Screens Main BurnerIII. Evaporator FAN Service and Replacement II. LubricationIV. Evaporator FAN Performance Adjustment Belt Tension AdjustmentBelt Tension Adjustment VI. CONDENSER-FAN Adjustment FigVII. Power Failure IX. GAS Valve AdjustmentVIII. Refrigerant Charge Main Burners XI. Filter DrierXII. Protective Devices XV. Replacement Parts XIII. Relief DevicesXIV. Control Circuit Low Voltage Control Schematic Low Voltage Control Schematic Power Schematic Component Arrangement Troubleshooting Unit Troubleshooting Cooling Service AnalysisHeating Service Analysis Problem Cause RemedyIGC Control Heating and Cooling II. ECONOMI$ER IV Troubleshooting EconoMi$er IV Troubleshooting Completion EconoMi$er IV Input/Output LogicCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Page Page START-UP Checklist TemperaturesElectrical Pressures
Related manuals
Manual 40 pages 46.88 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.