Bryant operation manual Fan Performance 581A210 Medium Heat Vertical Discharge Units

Page 19

Table 6 — Fan Performance — 581A210 Medium Heat Vertical Discharge Units*

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

3500

470

611

0.70

556

791

0.91

630

967

1.11

697

1141

1.31

760

1314

1.51

4000

511

802

0.92

591

1001

1.15

661

1194

1.37

725

1383

1.59

784

1572

1.81

4500

553

1029

1.18

629

1248

1.44

695

1458

1.68

756

1663

1.91

812

1866

2.15

5000

597

1297

1.49

669

1534

1.76

732

1761

2.03

789

1982

2.28

843

2201

2.53

5500

641

1606

1.85

709

1862

2.14

770

2106

2.42

825

2343

2.70

876

2577

2.96

6000

686

1961

2.26

751

2234

2.57

809

2495

2.87

862

2749

3.16

911

2997

3.45

6500

732

2363

2.72

794

2653

3.05

849

2931

3.37

900

3201

3.68

948

3465

3.99

7000

779

2815

3.24

837

3122

3.59

891

3416

3.93

940

3702

4.26

986

3981

4.58

7500

826

3320

3.82

882

3642

4.19

933

3953

4.55

980

4254

4.89

1025

4549

5.23

8000

873

3879

4.46

926

4217

4.85

975

4542

5.22

1021

4860

5.59

1065

5169

5.95

8500

921

4495

5.17

972

4847

5.57

1019

5189

5.97

1063

5521

6.35

1105

5846

6.72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

3500

818

1488

1.71

874

1661

1.91

927

1835

2.11

978

2008

2.31

1026

2182

2.51

4000

840

1760

2.02

893

1948

2.24

943

2136

2.46

992

2324

2.67

1039

2512

2.89

4500

865

2068

2.38

915

2270

2.61

964

2472

2.84

1011

2673

3.07

1056

2876

3.31

5000

893

2417

2.78

942

2632

3.03

988

2848

3.28

1033

3063

3.52

1076

3278

3.77

5500

925

2808

3.23

971

3037

3.49

1016

3266

3.76

1059

3494

4.02

1100

3721

4.28

6000

958

3243

3.73

1003

3486

4.01

1045

3728

4.29

1087

3970

4.57

1127

4210

4.84

6500

993

3725

4.28

1036

3982

4.58

1077

4238

4.87

1117

4492

5.17

1156

4745

5.46

7000

1029

4256

4.90

1071

4528

5.21

1111

4797

5.52

1150

5064

5.82

1187

5330

6.13

7500

1067

4838

5.56

1107

5124

5.89

1146

5407

6.22

1184

5688

6.54

1220

5967

6.86

8000

1106

5474

6.30

1145

5774

6.64

1182

6071

6.98

1219

6365

7.32

1254

6657

7.66

8500

1145

6165

7.09

1183

6479

7.45

1220

6790

7.81

1255

7098

8.16

1290

7403

8.51

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

*Motor drive ranges:

Low Range: 647-886 (208/230 and 460-v), 810-1072 (575-v)

High Range: 897-1139 (208/230 and 460-v), 873-1108 (575-v) All other rpms require field-supplied drive.

Refer to page 23 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is:

Low Range: 4.25 (208/230 and 460-v), 3.45 (575-v)

High Range: 5.75

19

Image 19
Contents Safety Considerations ContentsInstallation Provide Unit Support III. RIG and Place Unit II. Remove Shipping RailsRoof Curb Details Shipping Rail Removal Base Unit Dimensions Compressor Physical DataFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Horizontal Applications Vertical ConfigurationIV. Field Fabricate Ductwork Make Unit Duct ConnectionsVIII. Install GAS Piping VI. Install Flue Hood and Inlet HoodVII. Trap Condensate Drain Field Control Wiring Field Power SupplyIX. Make Electrical Connections Manual Damper Assembly Install OUTDOOR-AIR HoodFLA MCA Mocp Electrical Data Units Without Convenience OutletElectrical Data Units With Optional Convenience Outlet Outdoor-Air Hood Details XII. NON-FUSED Disconnect XIII. Install ALL AccessoriesSTART-UP III. Refrigerant Service PortsVI. Internal Wiring PRE-START-UPXI. GAS Heat VIII. Condenser Fans and MotorsIX. RETURN-AIR Filters OUTDOOR-AIR Inlet ScreensFan Performance 581A210 Medium Heat Vertical Discharge Units Fan Performance 581A240 Low Heat Vertical Discharge Units Fan Performance 581A210 High Heat Vertical Discharge UnitsFan Performance 581A240 High Heat Vertical Discharge Units Fan Performance 581A240 Medium Heat Vertical Discharge UnitsFan Performance 581A300 Medium Heat Vertical Discharge Units Fan Performance 581A300 Low Heat Vertical Discharge UnitsGeneral Notes for Tables Fan Performance 581A300 High Heat Vertical Discharge UnitsFan Performance 581A210 Low Heat Horizontal Discharge Units Fan Performance 581A240 Low Heat Horizontal Discharge Units Fan Performance 581A210 High Heat Horizontal Discharge UnitsFan Performance 581A240 High Heat Horizontal Discharge Units Fan Performance 581A300 Low Heat Horizontal Discharge Units Fan Performance 581A300 High Heat Horizontal Discharge Units Power Exhaust Fan PerformanceOperation Air Quantity Limits Evaporator Fan Motor SpecificationsXII. Optional ECONOMI$ER Accessory/FIOP Static Pressure in. wgFan Rpm at Motor Pulley Settings EconoMi$er IV Controller Wiring and Operational ModesEconoMi$er IV Component Locations Exploded View Supply-Air Temperature Sensor LocationEconoMi$er IV Wiring Enthalpy Changeover Set Points Page XII. Operating Sequence CO2 Sensor Standard SettingsCooling, Units Without Economizer Cooling, Units With EconoMi$er Service CleaningCoil Maintenance and Cleaning Recommendation Heating, Units Without EconomizerMain Burner Condensate DrainFilters Outdoor-Air Inlet ScreensII. Lubrication III. Evaporator FAN Service and ReplacementVI. CONDENSER-FAN Adjustment Fig IV. Evaporator FAN Performance AdjustmentBelt Tension Adjustment Belt Tension AdjustmentIX. GAS Valve Adjustment VII. Power FailureVIII. Refrigerant Charge XI. Filter Drier Main BurnersXII. Protective Devices XIII. Relief Devices XV. Replacement PartsXIV. Control Circuit Low Voltage Control Schematic Low Voltage Control Schematic Power Schematic Component Arrangement Cooling Service Analysis Troubleshooting Unit TroubleshootingProblem Cause Remedy Heating Service AnalysisIGC Control Heating and Cooling II. ECONOMI$ER IV Troubleshooting EconoMi$er IV Input/Output Logic EconoMi$er IV Troubleshooting CompletionCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Page Page Pressures START-UP ChecklistTemperatures Electrical
Related manuals
Manual 40 pages 46.88 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.