Bryant 580F installation instructions Demand Ventilation Control, CO2 Sensor Configuration

Page 26

The unoccupied minimum position can only be set at the con- troller. The occupied minimum position set point configured at the EconoMi$er+ controller should be set to 0 when using a remote potentiometer. The occupied minimum position will also be used as part of the IAQ routing; it will be the maximum position the damper moves to when there is an IAQ call.

If the remote potentiometer (occupied) position is greater than the EconoMi$er+ controller unoccupied minimum posi- tion, then the remote potentiometer setting will be used. The remote potentiometer is field supplied and must be a 3-wire, linear potentiometer with a resistance between 10K ohm and 100K ohm (such as the Honeywell S963B1128).

Q. Demand Ventilation Control

Demand ventilation control uses an IAQ sensor (CRE+PLUG001A00 required) to control the amount of out- side air admitted into the system. Normally, the minimum position of the EconoMi$er+ damper is established based on the demand occupancy of the space. The IAQ sensor will be used to modulate the EconoMi$er+ minimum damper posi- tion below the normal minimum position based on full occu- pancy. The lower limit is called the base ventilation rate. See Fig. 32.

If there is no IAQ signal the damper will be in the unoccu- pied minimum position (configuration item number 3). If there is an IAQ signal the damper will be in the occupied minimum position (configuration item number 15), unless the remote potentiometer is used to override it.

For the demand ventilation control logic, the user configures the lower and upper actuator position to establish the base ventilation rate (IAQMIN_SP) and the design ventilation rate (ECONOMIN_SP) for full occupancy. When the EconoMi$er+ damper is being modulated for demand ventilation control, the damper position will be between IAQMIN_SP and ECONOMIN_SP. The upper IAQ differential set point is DAQHI. The lower IAQ differential set point is DAQLO.

The differential set points represent the differential CO2 level (in ppm) above the outdoor reference IAQ levels. Nor- mally, the outdoor reference IAQ levels are around 400 ppm, but the value should be configured based on the reference levels taken at the job site.

DAMPER

 

 

 

POSTION

 

 

 

 

 

FULL OCCUPANCY

 

ECONOMIZER

 

VENTILATION RATE

 

MINIMUM

 

 

 

OCCUPIED

 

 

 

DAMPER

 

 

 

POSITION

 

 

 

(ECONOMIN_SP)

 

 

 

 

VENTILATION FOR PEOPLE

IAQ

 

 

 

MINIMUM

 

 

 

ECONOMIZER

 

 

 

POSITION

 

 

 

SET POINT

VENTILATION FOR SOURCES

(IAQMIN_SP)

 

 

 

 

 

 

CO2 LEVEL

OUTDOOR REFERENCE

100

700

INSIDE/OUTSIDE CO2 DIFFERENTIAL

LEVEL (OAQ)= 400

500

1100

INSIDE CO2 CONCENTRATION

AQ

AQ

DIFFERENTIAL

DIFFERENTIAL

LOW (DAQLO)

HIGH (DAQHI)

Fig. 32 — Demand Ventilation Control

The following equation is used to determine EconoMi$er+ damper position (ECONOMIN_POS):

(ECONOMIN_SP – IAQMIN_SP) * (IAQ – OAQ – DAQLO)

IAQMIN_SP + =

(DAQHI – DAQLO)

R. CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. See Table 7.

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode 2 times. The STDSET Menu will appear.

3.Use the Up/Down button to select the preset number. See Table 7.

4.Press Enter to lock in the selection.

Press Mode to exit and resume normal operation. The cus- tom settings of the CO2 sensor can be changed any time after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of

the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

S.Dehumidification of Fresh Air with Demand Control Ventilation (DCV)

Information from ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) indicates that the largest humidity load on any zone is the fresh air intro- duced. For some applications, a device such as a energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling pro- cesses are more than adequate to remove the humidity loads for most commercial applications.

This makes the control of the dehumidification device simple when using the enthalpy or differential enthalpy sensor. The enthalpy sensor or differential enthalpy sensor is installed on the equipment to determine economizer operation. The high enthalpy signal from the temperature and humidity sensors or differential temperature and humidity sensors can be used to turn on the outdoor air moisture removal device any time fresh air is required for the space.

The energy recovery device should be sized for maximum latent and sensible conditioning at maximum ventilation on a design day.

A calculation for leaving-air temperature on a low ambient, low ventilation day should also be done to determine the supply-air temperature of the return and pre-conditioned outside air. The design should produce air temperature somewhat near room conditions to prevent reheat of the air mixture. The energy recovery device should be interlocked with the heat to turn off the device when in the heat mode.

26

Image 26
Contents Safety Considerations Important Read Before InstallingContents InstallationBase Unit Dimensions 580F090,102,120,150 Base Unit Dimensions 580F091,103,121,151 Slab Mount Horizontal Units Only III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support II. Field Fabricate DuctworkCRBTMPWR004A01 CRBTMPWR002A01CRBTMPWR003A01 CRRFCURB003A01Unit Leveling Tolerances Operating Dimensions Unit Weight Physical Data 580F090, 102, 120, 150 Units MED Furnace SectionLOW High091 103 121 151 Nominal Capacity tons 091 103 121 151 Field Power Supply Install Flue HoodVI. Install GAS Piping Field Control WiringHeat Anticipator Settings Electrical Data Without Convenience OutletPower Exhaust Electrical Data MCA Mocp Unbalanced 3-Phase Supply VoltageRLA LRA Electrical Data With Convenience OutletVoltage Type FLA FAN Motor MCA Mocp LRAIFC NECWith Hood Attached VIII. Adjust FACTORY-INSTALLED OptionsManual Outdoor-Air Damper ScrewsBracket Optional EconoMi$er+Hood BOX ORH OATIAQ IarhThermostats EconoMi$er+ Controller WiringDamper Movement Supply Air Temperature SAT Sensor Provided EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Return Air Temperature RAT SensorVertical ECONOMI$ER+ 3 to 12 1/2 TON Units Outdoor Air Humidity SensorIndoor Air Humidity Sensor Temperature Resistance Range Resolution Low HighRemote Potentiometer Occupied Minimum Position Power ExhaustRemote EconoMi$er+ Enable Control CO2 Sensor Configuration Demand Ventilation ControlCO2 Sensor* Standard Settings IX. Adjust EVAPORATOR-FAN SpeedEvaporator-Fan Motor Efficiency Unit Motor EfficiencyUnit EVAPORATOR-FAN Maximum Acceptable Evaporator-Fan Motor PerformanceGeneral Notes for FAN Performance Data Tables Continuous BHP2400 535 584 2250 513 5052300 521 531 2500 551 642802 684 713 665 940741 671 972 8661293 802 1566 2500 551 642 1187 786 1453 2300 521 5311222 791 1489 2400 535 584 866 6964000 38003900 4100 4200 42503900 777 1974 3800 761 18422156 2296942 1323 993 1524 3300 962 1373 3100978 1447 3200 958 1400 1008 1604 34003200 766 773 829 947 3000 726 656 793 8223100 746 713 811 883 3300 786 836Airflow 3900 760 1460 819 1676 3700 728 1266 789 1473 8483800 744 1361 804 1572 4000 777 1563 834 17854100 793 1672 3700 728 1266 789 14734000 777 1563 1139 4208 52002300 513 509 2250 505 484681 2400 527 561766 674 993 681 657 901708 663 931 8941241 796 1508 2500 543 617 1142 782 1403 2300 513 5091174 787 1437 2400 527 561 828 6864200 4250 3900 770 1912 3800 753 17832074 22093100 568 686 3000 555 630765 825825 706 968 765 696 9041048 814 1198 3100 568 686 1115 823 1269 3200 582 7451026 739 1181 888 717 1035955 728 1106 1100 750 12593800 690 1185 3700 676 11061328 811 1414 8233900 705 1269 773 1503 3700 676 1106 747 1328 8113800 690 1185 760 1414 823 4000 719 1357 786 1597PRE-START-UP Internal WiringVII. Refrigerant Service Ports START-UP Unit PreparationXII. Heating CoolingXI. Main Burners XVI. ECONOMI$ER+ Controller XIV. Safety ReliefXIII. Integrated GAS Controller IGC Operation EconoMi$er+ Controller Board DS1 DS2 DS3 DS4Start-Up Mode Sequence EconoMi$er+ Inputs and OutputsValue Setting Configuration Variables Read and Setup ModesSetup Points Units Minimum Maximum Factory INC Comments Input/Output ChannelsSetup Mode Manual Mode Error ModeVentilation Air And Free Cooling XVII. ECONOMI$ER+ ConfigurationCompressor Configuration And Control Demand Ventilation Configuration Power Exhaust ConfigurationHeating, Units Without EconoMi$er+ XVIII. Operating SequenceCooling, Units Without EconoMi$er+ Cooling, Units With EconoMi$er+Service Cleaning VIII. HIGH-PRESSURE Switch IV. Blower Belt AdjustmentVI. Economizer Adjustment IX. LOSS-OF-CHARGE SwitchTo Use Cooling Charging Chart Cooling Charging Chart 580F090Cooling Charging Chart 580F120 Cooling Charging Chart 580F091 Cooling Charging Chart 580F121 XIII. COMBUSTION-AIR Blower XIV. Limit SwitchXII. Flue GAS Passageways XV. Burner IgnitionCleaning and Adjustment XVII. Replacement PartsTroubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Cooling Service Troubleshooting Problem Cause RemedyHeating Service Troubleshooting Typical Unit Wiring Schematic 208/230-3-60 Unit Shown Startup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuraiton Settings Index Service Training Call for Free CatalogPage Preliminary Information START-UP ChecklistRemove and Store in Job File III. START-UP Electrical
Related manuals
Manual 64 pages 4.35 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.