Bryant 580F installation instructions Setup Mode

Page 56

After advancing through all the configuration variables in the Read mode, the controller will then advance through the status of the I/O channels. As in the Read mode, there will be no LEDs on. Push the READ/ADJUST (#1) button and the yellow LED will flash the “I/O Point” number and the green LEDs will flash the “I/O Values” in the same manner described in the Read mode section. See Table 35. At the first I/O point (Compressor 1 Output), the DS2 LED (Yellow) will flash with the number of the I/O channel and the DS1 LED (red) will stop flashing. This will be followed by the I/O chan- nel status. To read the value again, push the READ/ADJUST (#1) button.

To advance to the next channel, push the ADVANCE/ MANUAL (#2) button. If the number of the channel or the status value is greater than 4 the controller will count out the increments of 5 at a high flash rate followed by the remaining digits. The channel number will be counted out through the DS2 LED (yellow). The status value will be counted out through the DS3 and DS4 LEDs (green).

If the status value is an analog value then the numeric value will be displayed by using the DS3 Green LED to display the tens digit and the DS4 will be used to display the ones digit.

If the channel is a digital output (relay), the DS3 LED (flash- ing green) will indicate ON status and the DS4 LED (flash- ing green) will indicate OFF status. If the output is the economizer control signal then the DS3 LED will be used to indicate the motor is being driven open, and the DS4 LED will be used to indicate it is being closed. If the motor is not being commanded in either direction then both the DS3 and DS4 LEDs will be on. The controller will first go through the output relays, then the economizer motor, and will then fol- low with the values currently being read for the analog input channels as defined in the configuration table. All values are maintained in memory even during a power loss. To exit Setup mode, push and hold the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons for more than 3 seconds. Setup mode will automatically be exited after 10 minutes of no activity.

E. Setup Mode

The Setup mode is used to change set points and configura- tion values.

Enter the Setup mode by pushing and holding the READ/ ADJUST (#1) button 1 for at least 3 seconds until all LEDs flash once. Then, the yellow LED will come on steady. A user can only enter the Setup mode from the Run mode (to get to Run mode, press buttons both buttons #1 and #2 for at least 3 seconds).

In Setup mode, all configurations can be modified even while the unit is running, but the user will not be able to adjust the I/O channels. Only channels 1 through 20 on Table 34 will be accessible in the Setup mode. Channel 20 will be used to reset any alarms that may have occurred. As an option, alarms can also be reset by cycling power to the controller.

NOTE: During the Setup mode, all routines including safety routines will continue to run and control the unit.

While in this mode, the DS1 LED (red) will flash to indicate the number of the configuration item. The DS2 LED (yellow) will be on continuously to indicate that the unit is in configu- ration mode. Use the ADVANCE/MANUAL button to sequence through the setup channels. If the value of the channel is less than 5 it will count out the value of the chan- nel on the DS1 LED at 1-second intervals. If the channel value is 5 or greater, the DS1 LED will first count out the groups of 5 and then following with the remaining digit.

Verify what Setup Point is being read by pushing the READ/ ADJUST button (#1). First the Red LED will flash the set point number, then the Green LEDs will flash the value. Then, the green DS3 and DS4 LEDs will each come on steady for about 2 seconds. While DS3 is on steady, its new value can be entered by pushing READ/ADJUST (#1), and entering the value for the ten’s digit. When the DS4 comes on steady, enter the value for the one's digit. After the green LEDs are off, push the READ/ADJUST button (#1) again to verify that the correct value has been entered. If the configu- ration is a discrete On/off setting, push the READ/ADJUST button (#1) to toggle LED 3 or 4 on or off.

Setup Example 1: Change “Occupied Minimum Position” (configuration item 2) to 53%.

1.Read the General Notes about reading and entering values found on the label on the top of the EconoMi$er+.

2.Push and hold button #1 (READ/ADJUST) for at least 3 seconds until all LEDs flash. The yellow LED will go on steady.

3.Read the current configuration point by pushing but- ton #1. The red LED flashes the configuration point number and the green LEDs flash the current setting for that setup point number.

4.On the label (on top of the EconoMi$er+), read Step 2 and Note 1 for Setup mode operation.

5.Use button #2 (ADVANCE/MANUAL) to advance to configuration point number 2, Occupied Min.

NOTE: Before performing Step 6, be ready to push button #1; there is a limited time window that can easily be missed when the DS3 green LED comes on, and again when the DS4 green LED comes on.

6.Verify the configuration point by pushing button #1. The red LED should flash twice to indicate point 2, and then the green LEDs will flash the current set- ting.

7.Next, the green DS3 LED will turn on steady for 2 seconds. During this time, push button #1 five times.

8.The DS3 LED will turn off and the green DS4 LED will go on steady for 2 seconds. During this time, push button #1 three times.

9.The 5 button #1 pushes, followed by the 3 button #1 pushes is the sequence that sets the occupied mini- mum position to 53%.

10.Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. There should be 5 fast blinks of DS3 and 3 slow blinks of DS4.

Setup Example 2: Change the Occupied Minimum Position (item 2) to 2% (lowest value).

1.Read the General Notes about reading and entering values found on the label on the top of the EconoMi$er+.

2.Push and hold button #1 (READ/ADJUST) for at least 3 seconds until all LEDs flash. The yellow LED will go on steady.

3.Read the current configuration point by pushing but- ton #1. The red LED flashes the configuration point number and the green LEDs flash the current setting for that setup point number.

4.On the label (on top of the EconoMi$er+), read Step 2 and Note 1 for Setup mode operation.

56

Image 56
Contents Important Read Before Installing ContentsSafety Considerations InstallationBase Unit Dimensions 580F090,102,120,150 Base Unit Dimensions 580F091,103,121,151 III. Install External Trap for CONDEN- Sate Drain Alternate Unit SupportSlab Mount Horizontal Units Only II. Field Fabricate DuctworkCRBTMPWR002A01 CRBTMPWR003A01CRBTMPWR004A01 CRRFCURB003A01Unit Leveling Tolerances Operating Dimensions Unit Weight Physical Data 580F090, 102, 120, 150 Units Furnace Section LOWMED High091 103 121 151 Nominal Capacity tons 091 103 121 151 Install Flue Hood VI. Install GAS PipingField Power Supply Field Control WiringHeat Anticipator Settings Electrical Data Without Convenience OutletPower Exhaust Electrical Data MCA Mocp Unbalanced 3-Phase Supply VoltageElectrical Data With Convenience Outlet Voltage TypeRLA LRA FLA FAN Motor MCA Mocp LRAIFC NECVIII. Adjust FACTORY-INSTALLED Options Manual Outdoor-Air DamperWith Hood Attached ScrewsBracket Optional EconoMi$er+Hood BOX OAT IAQORH IarhThermostats EconoMi$er+ Controller WiringDamper Movement EconoMi$er+ Field-Installed Accessories Outdoor Air Temperature OAT Sensor ProvidedSupply Air Temperature SAT Sensor Provided Return Air Temperature RAT SensorVertical ECONOMI$ER+ 3 to 12 1/2 TON Units Outdoor Air Humidity SensorIndoor Air Humidity Sensor Temperature Resistance Range Resolution Low HighRemote Potentiometer Occupied Minimum Position Power ExhaustRemote EconoMi$er+ Enable Control CO2 Sensor Configuration Demand Ventilation ControlCO2 Sensor* Standard Settings IX. Adjust EVAPORATOR-FAN SpeedEvaporator-Fan Motor Efficiency Unit Motor EfficiencyEvaporator-Fan Motor Performance General Notes for FAN Performance Data TablesUnit EVAPORATOR-FAN Maximum Acceptable Continuous BHP2250 513 505 2300 521 5312400 535 584 2500 551 642713 665 940 741 671 972802 684 8661187 786 1453 2300 521 531 1222 791 1489 2400 535 5841293 802 1566 2500 551 642 866 6963800 39004000 4100 4200 42503800 761 1842 21563900 777 1974 2296962 1373 3100 978 1447 3200942 1323 993 1524 3300 958 1400 1008 1604 34003000 726 656 793 822 3100 746 713 811 8833200 766 773 829 947 3300 786 836Airflow 3700 728 1266 789 1473 848 3800 744 1361 804 15723900 760 1460 819 1676 4000 777 1563 834 17853700 728 1266 789 1473 4000 777 15634100 793 1672 1139 4208 52002250 505 484 6812300 513 509 2400 527 561681 657 901 708 663 931766 674 993 8941142 782 1403 2300 513 509 1174 787 1437 2400 527 5611241 796 1508 2500 543 617 828 6864200 4250 3800 753 1783 20743900 770 1912 22093000 555 630 7653100 568 686 825765 696 904 1048 814 1198 3100 568 686825 706 968 1115 823 1269 3200 582 745888 717 1035 955 728 11061026 739 1181 1100 750 12593700 676 1106 1328 8113800 690 1185 1414 8233700 676 1106 747 1328 811 3800 690 1185 760 1414 8233900 705 1269 773 1503 4000 719 1357 786 1597Internal Wiring VII. Refrigerant Service PortsPRE-START-UP START-UP Unit PreparationXII. Heating CoolingXI. Main Burners XVI. ECONOMI$ER+ Controller XIV. Safety ReliefXIII. Integrated GAS Controller IGC Operation EconoMi$er+ Controller Board DS1 DS2 DS3 DS4Start-Up Mode Sequence EconoMi$er+ Inputs and OutputsConfiguration Variables Read and Setup Modes Setup Points Units Minimum Maximum Factory INC CommentsValue Setting Input/Output ChannelsSetup Mode Manual Mode Error ModeVentilation Air And Free Cooling XVII. ECONOMI$ER+ ConfigurationCompressor Configuration And Control Demand Ventilation Configuration Power Exhaust ConfigurationXVIII. Operating Sequence Cooling, Units Without EconoMi$er+Heating, Units Without EconoMi$er+ Cooling, Units With EconoMi$er+Service Cleaning IV. Blower Belt Adjustment VI. Economizer AdjustmentVIII. HIGH-PRESSURE Switch IX. LOSS-OF-CHARGE SwitchTo Use Cooling Charging Chart Cooling Charging Chart 580F090Cooling Charging Chart 580F120 Cooling Charging Chart 580F091 Cooling Charging Chart 580F121 XIV. Limit Switch XII. Flue GAS PassagewaysXIII. COMBUSTION-AIR Blower XV. Burner IgnitionCleaning and Adjustment XVII. Replacement PartsTroubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Cooling Service Troubleshooting Problem Cause RemedyHeating Service Troubleshooting Typical Unit Wiring Schematic 208/230-3-60 Unit Shown Startup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuraiton Settings Index Service Training Call for Free CatalogPage START-UP Checklist Remove and Store in Job FilePreliminary Information III. START-UP Electrical
Related manuals
Manual 64 pages 4.35 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.