Bryant 580F 2250 513 505, 2300 521 531, 2400 535 584, 2500 551 642, 2550 558 673, 2600 566 705

Page 30

Table 11 — Fan Performance 580F090,091 — Vertical Discharge Units; Standard Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2250

513

0.54

505

595

0.76

713

665

1.01

940

728

1.27

1187

786

1.56

1453

2300

521

0.57

531

601

0.79

741

671

1.04

972

734

1.31

1222

791

1.60

1489

2400

535

0.63

584

615

0.86

802

684

1.11

1038

745

1.39

1293

802

1.68

1566

2500

551

0.69

642

628

0.93

866

696

1.19

1109

757

1.47

1369

813

1.77

1647

2550

558

0.72

673

635

0.97

900

702

1.23

1146

763

1.51

1409

818

1.81

1689

2600

566

0.76

705

642

1.00

935

709

1.27

1183

769

1.55

1450

824

1.86

1732

2700

582

0.83

771

656

1.08

1008

721

1.35

1263

781

1.65

1535

835

1.95

1823

2800

597

0.90

842

670

1.16

1086

734

1.44

1347

793

1.74

1625

847

2.06

1917

2900

613

0.98

918

684

1.25

1169

748

1.54

1436

805

1.84

1720

859

2.16

2019

3000

629

1.07

999

699

1.35

1256

761

1.64

1530

818

1.95

1820

871

2.28

2125

3100

645

1.16

1085

713

1.45

1349

775

1.75

1630

831

2.06

1925

883

2.40

2235

3200

662

1.26

1176

728

1.55

1448

788

1.86

1734

844

2.18

2036

3300

678

1.36

1272

743

1.66

1551

802

1.98

1845

857

2.31

2152

3400

694

1.47

1374

758

1.78

1660

816

2.10

1961

3500

711

1.59

1482

773

1.90

1775

831

2.23

2082

3600

727

1.71

1596

789

2.03

1896

845

2.37

2210

3700

744

1.84

1716

804

2.17

2023

3750

752

1.91

1778

812

2.24

2089

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2250

839

1.86

1735

889

2.18

2032

2300

844

1.90

1773

893

2.22

2073

2400

854

1.99

1855

903

2.32

2159

2500

865

2.08

1940

2550

870

2.13

1985

2600

875

2.18

2031

2700

886

2.28

2126

2800

897

2.39

2227

2900

3000

3100

3200

3300

3400

3500

3600

3700

3750

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

*Motor drive range: 590 to 840 rpm. All other rpms require field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 2.40.

3.See page 29 for General Fan Performance Notes.

30

Image 30
Contents Safety Considerations Important Read Before InstallingContents InstallationBase Unit Dimensions 580F090,102,120,150 Base Unit Dimensions 580F091,103,121,151 Slab Mount Horizontal Units Only III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support II. Field Fabricate DuctworkCRBTMPWR004A01 CRBTMPWR002A01CRBTMPWR003A01 CRRFCURB003A01Unit Leveling Tolerances Operating Dimensions Unit Weight Physical Data 580F090, 102, 120, 150 Units MED Furnace SectionLOW High091 103 121 151 Nominal Capacity tons 091 103 121 151 Field Power Supply Install Flue HoodVI. Install GAS Piping Field Control WiringHeat Anticipator Settings Electrical Data Without Convenience OutletPower Exhaust Electrical Data MCA Mocp Unbalanced 3-Phase Supply VoltageRLA LRA Electrical Data With Convenience OutletVoltage Type FLA FAN Motor MCA Mocp LRAIFC NECWith Hood Attached VIII. Adjust FACTORY-INSTALLED OptionsManual Outdoor-Air Damper ScrewsOptional EconoMi$er+ Hood BOXBracket ORH OATIAQ IarhEconoMi$er+ Controller Wiring Damper MovementThermostats Supply Air Temperature SAT Sensor Provided EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Return Air Temperature RAT SensorOutdoor Air Humidity Sensor Indoor Air Humidity SensorVertical ECONOMI$ER+ 3 to 12 1/2 TON Units Temperature Resistance Range Resolution Low HighPower Exhaust Remote EconoMi$er+ Enable ControlRemote Potentiometer Occupied Minimum Position CO2 Sensor Configuration Demand Ventilation ControlCO2 Sensor* Standard Settings IX. Adjust EVAPORATOR-FAN SpeedEvaporator-Fan Motor Efficiency Unit Motor EfficiencyUnit EVAPORATOR-FAN Maximum Acceptable Evaporator-Fan Motor PerformanceGeneral Notes for FAN Performance Data Tables Continuous BHP2400 535 584 2250 513 5052300 521 531 2500 551 642802 684 713 665 940741 671 972 8661293 802 1566 2500 551 642 1187 786 1453 2300 521 5311222 791 1489 2400 535 584 866 6964000 38003900 4100 4200 42503900 777 1974 3800 761 18422156 2296942 1323 993 1524 3300 962 1373 3100978 1447 3200 958 1400 1008 1604 34003200 766 773 829 947 3000 726 656 793 8223100 746 713 811 883 3300 786 836Airflow 3900 760 1460 819 1676 3700 728 1266 789 1473 8483800 744 1361 804 1572 4000 777 1563 834 17854100 793 1672 3700 728 1266 789 14734000 777 1563 1139 4208 52002300 513 509 2250 505 484681 2400 527 561766 674 993 681 657 901708 663 931 8941241 796 1508 2500 543 617 1142 782 1403 2300 513 5091174 787 1437 2400 527 561 828 6864200 4250 3900 770 1912 3800 753 17832074 22093100 568 686 3000 555 630765 825825 706 968 765 696 9041048 814 1198 3100 568 686 1115 823 1269 3200 582 7451026 739 1181 888 717 1035955 728 1106 1100 750 12593800 690 1185 3700 676 11061328 811 1414 8233900 705 1269 773 1503 3700 676 1106 747 1328 8113800 690 1185 760 1414 823 4000 719 1357 786 1597PRE-START-UP Internal WiringVII. Refrigerant Service Ports START-UP Unit PreparationCooling XI. Main BurnersXII. Heating XIV. Safety Relief XIII. Integrated GAS Controller IGC OperationXVI. ECONOMI$ER+ Controller EconoMi$er+ Controller Board DS1 DS2 DS3 DS4Start-Up Mode Sequence EconoMi$er+ Inputs and OutputsValue Setting Configuration Variables Read and Setup ModesSetup Points Units Minimum Maximum Factory INC Comments Input/Output ChannelsSetup Mode Manual Mode Error ModeXVII. ECONOMI$ER+ Configuration Compressor Configuration And ControlVentilation Air And Free Cooling Demand Ventilation Configuration Power Exhaust ConfigurationHeating, Units Without EconoMi$er+ XVIII. Operating SequenceCooling, Units Without EconoMi$er+ Cooling, Units With EconoMi$er+Service Cleaning VIII. HIGH-PRESSURE Switch IV. Blower Belt AdjustmentVI. Economizer Adjustment IX. LOSS-OF-CHARGE SwitchTo Use Cooling Charging Chart Cooling Charging Chart 580F090Cooling Charging Chart 580F120 Cooling Charging Chart 580F091 Cooling Charging Chart 580F121 XIII. COMBUSTION-AIR Blower XIV. Limit SwitchXII. Flue GAS Passageways XV. Burner IgnitionCleaning and Adjustment XVII. Replacement PartsTroubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Cooling Service Troubleshooting Problem Cause RemedyHeating Service Troubleshooting Typical Unit Wiring Schematic 208/230-3-60 Unit Shown Startup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuraiton Settings Index Service Training Call for Free CatalogPage Preliminary Information START-UP ChecklistRemove and Store in Job File III. START-UP Electrical
Related manuals
Manual 64 pages 4.35 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.