Bryant 580F installation instructions II. Unit Troubleshooting

Page 70

Required Action

Shut the unit off and check wiring.

Reset Method

This error must be manually reset and requires a power reset.

H. Error Code 8 — E2 Test Failure

Error Criteria

This error occurs if internal hardware detects an E2 failure.

Required Action

Shut the unit off.

Reset Method

This error must be manually reset and requires a power reset.

I. Error Mode

When an error occurs, the red and yellow LEDs both come on steady. To determine the error, follow these steps:

1.Enter the Run mode by pushing buttons #1 and #2 for at least 3 seconds until all LEDs flash.

2.Press and release the #1 button to enter the Read mode.

3.Push the ADVANCE/MANUAL (#2) button to advance to item number 20, “1st Most Recent Error.” Determine the error(s) by reading the values in items 20-24 and referring to the error codes described above.

4.Fix the error(s).

5.Press buttons 1 and 2 to exit read mode. Enter Setup mode by pressing button #1 for at least 3 seconds until all the LEDs flash.

6.Push button #2 to advance to item number 20.

7.To reset the error code while the green DS4 LEDS is ON, press the READ/ADJUST (#1) button once. This resets the error mode and erases all repaired error codes.

NOTE: Cycling power to the board will also erase the repaired error codes.

J. RAM Test Failure

Error Criteria

If internal hardware detects a RAM failure, this alarm will be displayed by alternately flashing DS1+DS3 and DS2+DS4.

Required Action

Shut the unit off.

Reset Method

This error must be manually reset and requires a power reset.

K. ROM Test Failure

Error Criteria

If internal hardware detects a ROM failure, the alarm is dis- played by alternately flashing DS1+DS2 and DS3+DS4.

Required Action

Shut the unit off.

Reset Method

This error must be manually reset and requires a power reset.

L. Unit Always In Unoccupied Mode

A jumper wire is factory-installed to force the unit into occu- pied configuration whenever G or Y1 are closed. Without the jumper wire, the unit will always be in unoccupied mode. Check the wire. An occupied/unoccupied switch may be installed in place of the jumper. Check the wiring and setting of the switch.

II. UNIT TROUBLESHOOTING

Refer to Tables 38-40 and Fig. 52.

Table 38 — LED Troubleshooting — Error Code

SYMPTOM

CAUSE

REMEDY

Hardware Failure.

Loss of power to control module (IGC).

Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and

(LED OFF)

 

transformer. Units without a 24-v circuit breaker have an internal

 

 

overload in the 24-v transformer. If the overload trips, allow

 

 

10 minutes for automatic reset.

Fan ON/OFF Delay Modified

High limit switch opens during heat

Ensure unit is fired on rate and temperature rise is correct.

(LED/FLASH)

exchanger warm-up period

 

 

before fan-on delay expires.

 

 

Limit switch opens within three

Ensure unit’s external static pressure is within application guidelines.

 

minutes after blower-off delay

 

 

timing in Heating mode.

 

Limit Switch Fault.

High temperature limit switch is open.

Check the operation of the indoor (evaporator) fan motor.

(LED 2 flashes)

 

Ensure that the supply-air temperature rise is in accordance with the range on the

 

 

unit nameplate.

Flame Sense Fault.

The IGC sensed flame that

Reset unit. If problem persists, replace control board.

(LED 3 flashes)

should not be present.

 

4 Consecutive Limit Switch Faults.

Inadequate airflow to unit.

Check operation of indoor (evaporator) fan motor and that supply-air

(LED 4 flashes)

 

temperature rise agrees with range on unit nameplate information.

Ignition Lockout.

Unit unsuccessfully attempted

Check ignitor and flame sensor electrode spacing, gaps, etc.

(LED 5 flashes)

ignition for 15 minutes.

Ensure that flame sense and ignition wires are properly terminated.

 

 

Verify that unit is obtaining proper amount of gas.

Induced-Draft Motor Fault.

IGC does not sense that

Check for proper voltage. If motor is operating, check the

(LED 6 flashes)

induced-draft motor is operating.

speed sensor plug/IGC Terminal J2 connection. Proper

 

 

connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.

Rollout Switch Fault.

Rollout switch has opened.

Rollout switch will automatically reset, but IGC will continue to lock

(LED 7 flashes)

 

out unit. Check gas valve operation. Ensure that induced-draft blower

 

 

wheel is properly secured to motor shaft. Reset unit at unit disconnect.

Internal Control Fault.

Microprocessor has sensed an

If error code is not cleared by resetting unit power, replace the IGC.

(LED 8 flashes)

error in the software or hardware.

 

Temporary Software Lockout

Electrical interference is impeding the IGC

Reset 24-v to control board or turn the thermostat off and on. Fault will automatically

(LED 9 flashes)

software

reset itself in one hour.

CAUTION: If the IGC must be replaced, be sure to ground your- self to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.

IMPORTANT: Refer to Heating troubleshooting chart for additional troubleshoot- ing analysis.

LEGEND

IGC — Integrated Gas Unit Controller

LED — Light-Emitting Diode

70

Image 70
Contents Safety Considerations Important Read Before InstallingContents InstallationBase Unit Dimensions 580F090,102,120,150 Base Unit Dimensions 580F091,103,121,151 Slab Mount Horizontal Units Only III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support II. Field Fabricate DuctworkCRBTMPWR004A01 CRBTMPWR002A01CRBTMPWR003A01 CRRFCURB003A01Unit Leveling Tolerances Operating Dimensions Unit Weight Physical Data 580F090, 102, 120, 150 Units MED Furnace SectionLOW High091 103 121 151 Nominal Capacity tons 091 103 121 151 Field Power Supply Install Flue HoodVI. Install GAS Piping Field Control WiringHeat Anticipator Settings Electrical Data Without Convenience OutletPower Exhaust Electrical Data MCA Mocp Unbalanced 3-Phase Supply VoltageRLA LRA Electrical Data With Convenience OutletVoltage Type FLA FAN Motor MCA Mocp LRAIFC NECWith Hood Attached VIII. Adjust FACTORY-INSTALLED OptionsManual Outdoor-Air Damper ScrewsHood BOX Optional EconoMi$er+Bracket ORH OATIAQ IarhDamper Movement EconoMi$er+ Controller WiringThermostats Supply Air Temperature SAT Sensor Provided EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Return Air Temperature RAT SensorIndoor Air Humidity Sensor Outdoor Air Humidity SensorVertical ECONOMI$ER+ 3 to 12 1/2 TON Units Temperature Resistance Range Resolution Low HighRemote EconoMi$er+ Enable Control Power ExhaustRemote Potentiometer Occupied Minimum Position CO2 Sensor Configuration Demand Ventilation ControlCO2 Sensor* Standard Settings IX. Adjust EVAPORATOR-FAN SpeedEvaporator-Fan Motor Efficiency Unit Motor EfficiencyUnit EVAPORATOR-FAN Maximum Acceptable Evaporator-Fan Motor PerformanceGeneral Notes for FAN Performance Data Tables Continuous BHP2400 535 584 2250 513 5052300 521 531 2500 551 642802 684 713 665 940741 671 972 8661293 802 1566 2500 551 642 1187 786 1453 2300 521 5311222 791 1489 2400 535 584 866 6964000 38003900 4100 4200 42503900 777 1974 3800 761 18422156 2296942 1323 993 1524 3300 962 1373 3100978 1447 3200 958 1400 1008 1604 34003200 766 773 829 947 3000 726 656 793 8223100 746 713 811 883 3300 786 836Airflow 3900 760 1460 819 1676 3700 728 1266 789 1473 8483800 744 1361 804 1572 4000 777 1563 834 17854100 793 1672 3700 728 1266 789 14734000 777 1563 1139 4208 52002300 513 509 2250 505 484681 2400 527 561766 674 993 681 657 901708 663 931 8941241 796 1508 2500 543 617 1142 782 1403 2300 513 5091174 787 1437 2400 527 561 828 6864200 4250 3900 770 1912 3800 753 17832074 22093100 568 686 3000 555 630765 825825 706 968 765 696 9041048 814 1198 3100 568 686 1115 823 1269 3200 582 7451026 739 1181 888 717 1035955 728 1106 1100 750 12593800 690 1185 3700 676 11061328 811 1414 8233900 705 1269 773 1503 3700 676 1106 747 1328 8113800 690 1185 760 1414 823 4000 719 1357 786 1597PRE-START-UP Internal WiringVII. Refrigerant Service Ports START-UP Unit PreparationXI. Main Burners CoolingXII. Heating XIII. Integrated GAS Controller IGC Operation XIV. Safety ReliefXVI. ECONOMI$ER+ Controller EconoMi$er+ Controller Board DS1 DS2 DS3 DS4Start-Up Mode Sequence EconoMi$er+ Inputs and OutputsValue Setting Configuration Variables Read and Setup ModesSetup Points Units Minimum Maximum Factory INC Comments Input/Output ChannelsSetup Mode Manual Mode Error ModeCompressor Configuration And Control XVII. ECONOMI$ER+ ConfigurationVentilation Air And Free Cooling Demand Ventilation Configuration Power Exhaust ConfigurationHeating, Units Without EconoMi$er+ XVIII. Operating SequenceCooling, Units Without EconoMi$er+ Cooling, Units With EconoMi$er+Service Cleaning VIII. HIGH-PRESSURE Switch IV. Blower Belt AdjustmentVI. Economizer Adjustment IX. LOSS-OF-CHARGE SwitchTo Use Cooling Charging Chart Cooling Charging Chart 580F090Cooling Charging Chart 580F120 Cooling Charging Chart 580F091 Cooling Charging Chart 580F121 XIII. COMBUSTION-AIR Blower XIV. Limit SwitchXII. Flue GAS Passageways XV. Burner IgnitionCleaning and Adjustment XVII. Replacement PartsTroubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Cooling Service Troubleshooting Problem Cause RemedyHeating Service Troubleshooting Typical Unit Wiring Schematic 208/230-3-60 Unit Shown Startup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuraiton Settings Index Service Training Call for Free CatalogPage Preliminary Information START-UP ChecklistRemove and Store in Job File III. START-UP Electrical
Related manuals
Manual 64 pages 4.35 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.