Bryant 580F Demand Ventilation Configuration, Power Exhaust Configuration

Page 59

Maximum Damper Position

Set the maximum EconoMi$er+ position. Normally this is set at 100%. If using 3-position control or there is a reason not to use 100% outside air, this can be set using the EconoMi$er+ Maximum Position (MAX_POS_SP).

Compressor Lockout Temperature

Set the Compressor Lockout Temperature. The Compressor Lockout Temperature (CMP_LOCK) is used to prevent com- pressor from running at low ambient conditions when an EconoMi$er+ can easily satisfy the load.

EconoMi$er+ Changeover Control

Determine the type of EconoMi$er+ changeover control which will be used to enable and disable free cooling. This is done using the EconoMi$er+ Changeover Type.

1.Switch — This changeover setting is used when a remote signal from an energy management system will enable and disable the EconoMi$er+. This is done through a remote EconoMi$er+ enable switch.

2.Outdoor Dry Bulb — For this changeover setting, the EconoMi$er+ will be enabled based on the outdoor-air temperature. The EconoMi$er+ is shipped with an outdoor air temperature sensor. The outdoor air tem- perature set point can be configured by the user. The EconoMi$er+ will be disabled when the outdoor-air temperature rises above the set point. The configura- tion variable is the EconoMi$er+ Changeover set point (OAT_SP).

3.Differential Dry Bulb — For this changeover setting, the EconoMi$er+ will be enabled whenever the out- side-air temperature is lower than the return-air temperature. No configuration of set points is required other than to select the differential dry bulb function.

4.Outdoor Enthalpy — For this changeover setting, the control will enable the EconoMi$er+ based on the outdoor-air enthalpy curves as shown in Fig. 29. Using the EconoMi$er+ Changeover set point (ENTHALPY_SP), select curves A, B, C or D. The control will then use the EconoMi$er+ at conditions below the curve. The control uses the OAT and optional humidity sensor to calculate the enthalpy and also has the A, B, C, and D curves stored in memory.

5.Differential Enthalpy — For this changeover setting, the EconoMi$er+ will be enabled based on the com- parison of the enthalpy of the return air and outside air. If the outside air enthalpy is lower than the return air, then the EconoMi$er+ will be enabled. To use this option, an accessory outside air humidity sensor, a return air dry bulb sensor and a return air humidity sensor must be ordered and installed. No configuration of set points is required other than to select the function.

C.Demand Ventilation Configuration

The EconoMi$er+ control has demand ventilation control capability when using an IAQ sensor. The indoor air quality (IAQ) is measured using a CO2 sensor. The IAQ sensor can be field-installed in the return duct or the occupied space.

The EconoMi$er+ control algorithm modulates the position of the EconoMi$er+ damper between two user configurations depending upon the relationship between the IAQ and the Outdoor Air Quality (OAQ). The lower of these two positions is referred to as the Minimum IAQ Minimum EconoMi$er+ Position (IAQMIN_SP).

The higher position is referred to as the Occupied EconoMi$er+ Minimum Position (ECONOMIN_SP). The IAQMIN_SP should be set to an EconoMi$er+ position that brings in enough fresh air to remove contaminants and CO2 generated by sources other than people. The ECONOMIN_SP should be set to an EconoMi$er+ position that brings in enough fresh air to remove contaminants and CO2 generated by all sources including peo- ple at the design value for maximum occupancy.

Areference differential CO2 level above the outside CO2 level is used as the starting point for IAQ control and another reference differential level for maximum ventilation at design occupancy is used for the end of IAQ control. Between these points the control will modulate the dampers open from the IAQMIN_SP and the ECONOMIN_SP set- points. The damper position will never go above ECONOMIN_SP or below IAQMIN_SP.

The control does not measure the outdoor IAQ reference level as these levels are relatively constant. The installer should take a measurement at start-up of the unit and enter this value into the control using the Outdoor Air IAQ refer- ence level configuration.

The control is configured for air quality sensors which pro- vide 4 mA at 0 ppm and 20 mA at 2000 ppm. If a sensor has a different range, these bounds must be reconfigured.

To configure the control for an IAQ sensor perform the fol- lowing steps:

1.Determine the Occupied EconoMi$er+ Minimum posi- tion (ECONOMIN_SP) and enter it into the control.

2.Determine the IAQ minimum EconoMi$er+ position (IAQMIN_SP) and enter it into the control.

3.Enable IAQ control using IAQ Enable (IAQ_FLG).

4.Determine the Outdoor Air IAQ Reference (OAQ) and enter it into the control.

NOTE: The value entered into the control will be the CO2 ppm level divided by 10. For example, 400 ppm would be entered as 40.

5.Determine the lower control point differential level (DAQLO) and enter it into the control. This is a dif- ferential level so if the desired level to start IAQ con- trol is 500 ppm and the OAQ reference level is 400 then a value of 100 would be used.

NOTE: The value entered into the control will be the CO2 ppm level divided by 10. For example 100 ppm would be entered as 10.

6.Determine the upper control point differential level (DAQHI) and enter it into the control. This is a differ- ential level so if the desired level to start IAQ control is 1100 ppm and the OAQ reference level is 400 then a value of 700 would be used.

NOTE: The value entered into the control will be the CO2 ppm level divided by 10. For example 700 ppm would be entered as 70.

D. Power Exhaust Configuration

The EconoMi$er+ can control up to 2 stages of power exhaust. Power exhaust activation is done through config- urable damper position set points. The first stage of power is controlled by relay C4 on the EconoMi$er+ board. The acti- vation point for the first stage is set using the Power Exhaust Stage 1 Activation set point (PE_SP1). The second stage of power exhaust must be set at a value greater than the first stage. It is configured using the Power Exhaust Stage 2 Activation set point (PE_SP2).

59

Image 59
Contents Installation Important Read Before InstallingContents Safety ConsiderationsBase Unit Dimensions 580F090,102,120,150 Base Unit Dimensions 580F091,103,121,151 II. Field Fabricate Ductwork III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support Slab Mount Horizontal Units OnlyCRRFCURB003A01 CRBTMPWR002A01CRBTMPWR003A01 CRBTMPWR004A01Unit Leveling Tolerances Operating Dimensions Unit Weight Physical Data 580F090, 102, 120, 150 Units High Furnace SectionLOW MED091 103 121 151 Nominal Capacity tons 091 103 121 151 Field Control Wiring Install Flue HoodVI. Install GAS Piping Field Power SupplyElectrical Data Without Convenience Outlet Heat Anticipator SettingsUnbalanced 3-Phase Supply Voltage Power Exhaust Electrical Data MCA MocpFLA FAN Motor MCA Mocp LRA Electrical Data With Convenience OutletVoltage Type RLA LRANEC IFCScrews VIII. Adjust FACTORY-INSTALLED OptionsManual Outdoor-Air Damper With Hood AttachedBracket Optional EconoMi$er+Hood BOX Iarh OATIAQ ORHThermostats EconoMi$er+ Controller WiringDamper Movement Return Air Temperature RAT Sensor EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Supply Air Temperature SAT Sensor ProvidedVertical ECONOMI$ER+ 3 to 12 1/2 TON Units Outdoor Air Humidity SensorIndoor Air Humidity Sensor Temperature Resistance Low High Range ResolutionRemote Potentiometer Occupied Minimum Position Power ExhaustRemote EconoMi$er+ Enable Control Demand Ventilation Control CO2 Sensor ConfigurationIX. Adjust EVAPORATOR-FAN Speed CO2 Sensor* Standard SettingsUnit Motor Efficiency Evaporator-Fan Motor EfficiencyContinuous BHP Evaporator-Fan Motor PerformanceGeneral Notes for FAN Performance Data Tables Unit EVAPORATOR-FAN Maximum Acceptable2500 551 642 2250 513 5052300 521 531 2400 535 584866 713 665 940741 671 972 802 684866 696 1187 786 1453 2300 521 5311222 791 1489 2400 535 584 1293 802 1566 2500 551 6424100 4200 4250 38003900 40002296 3800 761 18422156 3900 777 1974958 1400 1008 1604 3400 962 1373 3100978 1447 3200 942 1323 993 1524 33003300 786 836 3000 726 656 793 8223100 746 713 811 883 3200 766 773 829 947Airflow 4000 777 1563 834 1785 3700 728 1266 789 1473 8483800 744 1361 804 1572 3900 760 1460 819 16761139 4208 5200 3700 728 1266 789 14734000 777 1563 4100 793 16722400 527 561 2250 505 484681 2300 513 509894 681 657 901708 663 931 766 674 993828 686 1142 782 1403 2300 513 5091174 787 1437 2400 527 561 1241 796 1508 2500 543 6174200 4250 2209 3800 753 17832074 3900 770 1912825 3000 555 630765 3100 568 6861115 823 1269 3200 582 745 765 696 9041048 814 1198 3100 568 686 825 706 9681100 750 1259 888 717 1035955 728 1106 1026 739 11811414 823 3700 676 11061328 811 3800 690 11854000 719 1357 786 1597 3700 676 1106 747 1328 8113800 690 1185 760 1414 823 3900 705 1269 773 1503START-UP Unit Preparation Internal WiringVII. Refrigerant Service Ports PRE-START-UPXII. Heating CoolingXI. Main Burners XVI. ECONOMI$ER+ Controller XIV. Safety ReliefXIII. Integrated GAS Controller IGC Operation DS1 DS2 DS3 DS4 EconoMi$er+ Controller BoardEconoMi$er+ Inputs and Outputs Start-Up Mode SequenceInput/Output Channels Configuration Variables Read and Setup ModesSetup Points Units Minimum Maximum Factory INC Comments Value SettingSetup Mode Error Mode Manual ModeVentilation Air And Free Cooling XVII. ECONOMI$ER+ ConfigurationCompressor Configuration And Control Power Exhaust Configuration Demand Ventilation ConfigurationCooling, Units With EconoMi$er+ XVIII. Operating SequenceCooling, Units Without EconoMi$er+ Heating, Units Without EconoMi$er+Service Cleaning IX. LOSS-OF-CHARGE Switch IV. Blower Belt AdjustmentVI. Economizer Adjustment VIII. HIGH-PRESSURE SwitchCooling Charging Chart 580F090 To Use Cooling Charging ChartCooling Charging Chart 580F120 Cooling Charging Chart 580F091 Cooling Charging Chart 580F121 XV. Burner Ignition XIV. Limit SwitchXII. Flue GAS Passageways XIII. COMBUSTION-AIR BlowerXVII. Replacement Parts Cleaning and AdjustmentTroubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Problem Cause Remedy Cooling Service TroubleshootingHeating Service Troubleshooting Typical Unit Wiring Schematic 208/230-3-60 Unit Shown Appendix a ECONOMI$ER+ Label Startup ModeAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuraiton Settings Index Call for Free Catalog Service TrainingPage III. START-UP Electrical START-UP ChecklistRemove and Store in Job File Preliminary Information
Related manuals
Manual 64 pages 4.35 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.