Bryant 580F installation instructions Power Exhaust, Remote EconoMi$er+ Enable Control

Page 25

CURRENT IN mA

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RH (%)

 

CURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(mA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

5.6

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

7.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

8.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

10.4

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

12.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

13.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

15.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

16.8

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90

18.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

10

20

30

40

50

60

70

80

90

100

 

 

 

HUMIDITY IN % RH

RH — Relative Humidity

Fig. 30 — Humidity Sensor Current vs. Humidity

ECONOMI$ER+

ECONOMI$ER+

CONTROLLER

GROMMET

RETURN AIR

HUMIDITY SENSOR

RETURN DUCT (FIELD-PROVIDED)

An occupied/unoccupied switch can be field-installed in place of the jumper to allow the user to force the control into occu- pied or unoccupied mode of operation for EconoMi$er+ damper position. The occupied/unoccupied switch is required if the user wants to use unoccupied free cooling or different EconoMi$er+ damper vent positions in the unoccupied mode.

N. Power Exhaust

Refer to the Accessory Power Exhaust installation instructions for information on installing the power exhaust accessory.

O. Remote EconoMi$er+ Enable Control

When the control is used with energy management systems that enable and disable the EconoMi$er+, the user can install a field- supplied enable/disable switch. The switch must be wired in series with a 3K ohm, 1 watt or greater resistor. The switch is wired to terminals ORH (pin 11) and VREF (pin 12) on J3. Refer to the Start-Up section for details on how to configure the control.

P. Remote Potentiometer Occupied Minimum Position

The occupied minimum position set point remote potentiom- eter (field-supplied) is used when requiring additional tem-

Fig. 31 — Return Air Humidity Sensor

M. Occupied/Unoccupied Switch

The EconoMi$er+ supports the use of a field-supplied occupied/ unoccupied switch. When the switch is closed it provides a 24-vac signal to the unit for occupied mode and when open, there is no signal to indicate unoccupied mode. The control can be configured to allow different minimum economizer damper positions and to control how mechanical cooling will and will not be used in the occupied mode.

NOTE: The remote potentiometer (see below) will override the occupied minimum position if the potentiometer setting is greater than the occupied minimum position.

For 3 to 121/2 ton units, a wire from J1-OCC (pin 4) and a wire from J1-24V (pin 5) are wire-nutted together to jumper the terminals.

porary ventilation. The remote potentiometer (10K ohm - closed damper, 100K ohm - open damper) will only control the occupied minimum position.

The accessory 5-in wiring plug, CRE+PLUG001A00 is required to connect the potentiometer.

The plug is installed on pins 15, 16 and 17 on J3 of the EconoMi$er+ controller. The pins are labeled with the ground symbol, MIN and VREF on the EconoMi$er+ controller. See Fig. 22. The pink wire from the harness is connected to pin 15 (ground symbol). The gray wire from the harness is con- nected to pin 16 (MIN). The yellow wire from the harness is connected to pin 16 (VREF). The wiring harness should be extended with wires and wire nuts and routed from the EconoMi$er+ controller to the remote potentiometer location.

NOTE: Pins 13 (ground symbol) and 14 (IAQ), which are wired to the accessory 5-pin plug, are not used for the remote potentiometer installation. They are used for an accessory IAQ sensor (if required).

25

Image 25
Contents Contents Important Read Before InstallingSafety Considerations InstallationBase Unit Dimensions 580F090,102,120,150 Base Unit Dimensions 580F091,103,121,151 Alternate Unit Support III. Install External Trap for CONDEN- Sate DrainSlab Mount Horizontal Units Only II. Field Fabricate DuctworkCRBTMPWR003A01 CRBTMPWR002A01CRBTMPWR004A01 CRRFCURB003A01Unit Leveling Tolerances Operating Dimensions Unit Weight Physical Data 580F090, 102, 120, 150 Units LOW Furnace SectionMED High091 103 121 151 Nominal Capacity tons 091 103 121 151 VI. Install GAS Piping Install Flue HoodField Power Supply Field Control WiringElectrical Data Without Convenience Outlet Heat Anticipator SettingsUnbalanced 3-Phase Supply Voltage Power Exhaust Electrical Data MCA MocpVoltage Type Electrical Data With Convenience OutletRLA LRA FLA FAN Motor MCA Mocp LRANEC IFCManual Outdoor-Air Damper VIII. Adjust FACTORY-INSTALLED OptionsWith Hood Attached ScrewsHood BOX Optional EconoMi$er+Bracket IAQ OATORH IarhDamper Movement EconoMi$er+ Controller WiringThermostats Outdoor Air Temperature OAT Sensor Provided EconoMi$er+ Field-Installed AccessoriesSupply Air Temperature SAT Sensor Provided Return Air Temperature RAT SensorIndoor Air Humidity Sensor Outdoor Air Humidity SensorVertical ECONOMI$ER+ 3 to 12 1/2 TON Units Temperature Resistance Low High Range ResolutionRemote EconoMi$er+ Enable Control Power ExhaustRemote Potentiometer Occupied Minimum Position Demand Ventilation Control CO2 Sensor ConfigurationIX. Adjust EVAPORATOR-FAN Speed CO2 Sensor* Standard SettingsUnit Motor Efficiency Evaporator-Fan Motor EfficiencyGeneral Notes for FAN Performance Data Tables Evaporator-Fan Motor PerformanceUnit EVAPORATOR-FAN Maximum Acceptable Continuous BHP2300 521 531 2250 513 5052400 535 584 2500 551 642741 671 972 713 665 940802 684 8661222 791 1489 2400 535 584 1187 786 1453 2300 521 5311293 802 1566 2500 551 642 866 6963900 38004000 4100 4200 42502156 3800 761 18423900 777 1974 2296978 1447 3200 962 1373 3100942 1323 993 1524 3300 958 1400 1008 1604 34003100 746 713 811 883 3000 726 656 793 8223200 766 773 829 947 3300 786 836Airflow 3800 744 1361 804 1572 3700 728 1266 789 1473 8483900 760 1460 819 1676 4000 777 1563 834 17854000 777 1563 3700 728 1266 789 14734100 793 1672 1139 4208 5200681 2250 505 4842300 513 509 2400 527 561708 663 931 681 657 901766 674 993 8941174 787 1437 2400 527 561 1142 782 1403 2300 513 5091241 796 1508 2500 543 617 828 6864200 4250 2074 3800 753 17833900 770 1912 2209765 3000 555 6303100 568 686 8251048 814 1198 3100 568 686 765 696 904825 706 968 1115 823 1269 3200 582 745955 728 1106 888 717 10351026 739 1181 1100 750 12591328 811 3700 676 11063800 690 1185 1414 8233800 690 1185 760 1414 823 3700 676 1106 747 1328 8113900 705 1269 773 1503 4000 719 1357 786 1597VII. Refrigerant Service Ports Internal WiringPRE-START-UP START-UP Unit PreparationXI. Main Burners CoolingXII. Heating XIII. Integrated GAS Controller IGC Operation XIV. Safety ReliefXVI. ECONOMI$ER+ Controller DS1 DS2 DS3 DS4 EconoMi$er+ Controller BoardEconoMi$er+ Inputs and Outputs Start-Up Mode SequenceSetup Points Units Minimum Maximum Factory INC Comments Configuration Variables Read and Setup ModesValue Setting Input/Output ChannelsSetup Mode Error Mode Manual ModeCompressor Configuration And Control XVII. ECONOMI$ER+ ConfigurationVentilation Air And Free Cooling Power Exhaust Configuration Demand Ventilation ConfigurationCooling, Units Without EconoMi$er+ XVIII. Operating SequenceHeating, Units Without EconoMi$er+ Cooling, Units With EconoMi$er+Service Cleaning VI. Economizer Adjustment IV. Blower Belt AdjustmentVIII. HIGH-PRESSURE Switch IX. LOSS-OF-CHARGE SwitchCooling Charging Chart 580F090 To Use Cooling Charging ChartCooling Charging Chart 580F120 Cooling Charging Chart 580F091 Cooling Charging Chart 580F121 XII. Flue GAS Passageways XIV. Limit SwitchXIII. COMBUSTION-AIR Blower XV. Burner IgnitionXVII. Replacement Parts Cleaning and AdjustmentTroubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Problem Cause Remedy Cooling Service TroubleshootingHeating Service Troubleshooting Typical Unit Wiring Schematic 208/230-3-60 Unit Shown Appendix a ECONOMI$ER+ Label Startup ModeAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuraiton Settings Index Call for Free Catalog Service TrainingPage Remove and Store in Job File START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 64 pages 4.35 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.