17-38
Cisco ONS 15600 Procedure Guide, R8.0
Chapter17 DLPs E100 to E199
DLP- E145 Connect the PDU Ground Cables to the PDU
Note A shunt is preinstalled between logic and frame ground to bond the two grounds. If you are
providing a separate logic ground, remove this shunt on both sides before installing the PDU frame ground.
Figure 17-5 Power Terminal Block (Right Side Shown)
Step 2 Tighten the nuts to 36 in-lb.
Step 3 Repeat Steps 1 and 2 for the left side of the PDU.
Step 4 Replace the PDU safety covers.
Step 5 Return to your originating procedure (NTP).
78396
Bottom
Shelf
Center
Shelf
Top
Shelf
Logic
Ground
Frame
Ground
Supply
power
lugs
Return
power
lugs
Supply
power
lugs
Return
power
lugs
Supply
power
lugs
Return
power
lugs
Bay rearBay front