Bryant 580F installation instructions EconoMi$er+ Controller Board, DS1 DS2 DS3 DS4

Page 53

tens digit and the DS4 LED will then display the ones digit. For example to display 54, the DS3 LED will flash 1 group of 5 at a high flash rate to indicate 50, and then follow with 4 flashes (DS4) at 1-second intervals to complete the display of the number 54.

NOTE: Do not try to count the “5 Fast Flashes” individually, but instead count how many groups of 5 flashes were displayed. In this case, 1 group of 5 flashes, plus the 4 flashes at 1 second results in the value of 54.

To read the display again, push the READ/ADJUST (#1) but- ton and the sequence will repeat as many times as needed.

To advance to the next setup point, push the ADVANCE/ MANUAL (#2) button. The controller will cycle through all the setup channels (Table 34) and then the I/O channels (Table 35) and then back to the first setup channel.

date or serial no

NOTE: The user can only advance forward, not reset to #1 or go backwards. Cycling the EconoMi$er+ power will reset the item number (but not the item value) to item #1.

In the Read mode for setup variables, the LEDs will not turn on steady; the LEDs will always flash. Steady-on indicators are reserved for the configuration modes. No data is modified in the Read mode. The controller will always remain at the last read number even if reset back to normal operation.

NOTE: To enter another mode, the user first must exit the Read mode.

If no button is pushed in 10 minutes, Read mode will auto- matically be exited. Also, if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons are pushed and held for more than 3 seconds, then Read mode will be exited to Run mode. While in the Read mode, the controller will continue to operate with normal unit control.

READ/

ADVANCE

DS1

DS2

DS3 DS4

ADJUST

MANUAL

 

 

 

# 1

 

RED

YELLOW

GREEN

# 2 SETPOINT DISPLAY

 

PUSH BUTTONS

1

J1

INPUTS

 

 

 

 

 

 

 

 

Y1 (cool 1)

 

 

 

Y1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y2

 

 

Y2 (cool 2)

THERMOSTAT

Occupied/unoccupied

5

 

 

 

 

G

 

 

 

G (fan)

 

I/O support dry circuit

 

 

 

OCC

 

 

OCC

 

contact (min 24 mA I)

 

 

 

 

 

 

 

 

 

24 VAC

 

 

 

24V

 

 

 

 

 

POWER

 

2-10 VDC

ECONOMIZER

SUPPLY

 

 

CONTROL

24 VAC

24 VAC

Control

J2

24V

24V

CNT

 

1

5

 

 

 

Relays rated at 24 VAC 3A

RELAYS

CP1

24 VAC

cooling, 2 stages of power

and traces for 8A.

 

CP2

NOTE: For 1 and 2 stage

 

 

exhaust will be used.

OUTPUT

24 VAC

For 3 cooling stages, only 1

 

 

24 VAC

stage of power exhaust will be

 

used, and for 4 stages no power

 

EX2/CP3

exhaust will be controlled

 

 

 

directly by the control.

 

EX1/CP4

4-20 mA external powered between signal and ground 4-20 mA loop powered between 24 VDC and signal

ANALOG INPUTS

SAT (10k thermistor)

OAT (10k thermistor)

RAT (10k thermistor)

IRH (4-20 ma)

Vref

ORH (4-20 ma)

Vref

IAQ (4-20ma)

min (10K pot)

Vref

J3

1

SAT

OAT

RAT

IRH

VRF

ORH

VRF

IAQ

MIN

VRF

 

 

 

 

 

 

 

 

 

 

J4

C1

C2

24V

24V

24V

C3

C4

17

Fig. 36 — EconoMi$er+ Controller Board

53

Image 53
Contents Contents Important Read Before InstallingSafety Considerations InstallationBase Unit Dimensions 580F090,102,120,150 Base Unit Dimensions 580F091,103,121,151 Alternate Unit Support III. Install External Trap for CONDEN- Sate DrainSlab Mount Horizontal Units Only II. Field Fabricate DuctworkCRBTMPWR003A01 CRBTMPWR002A01CRBTMPWR004A01 CRRFCURB003A01Unit Leveling Tolerances Operating Dimensions Unit Weight Physical Data 580F090, 102, 120, 150 Units LOW Furnace SectionMED High091 103 121 151 Nominal Capacity tons 091 103 121 151 VI. Install GAS Piping Install Flue HoodField Power Supply Field Control WiringElectrical Data Without Convenience Outlet Heat Anticipator SettingsUnbalanced 3-Phase Supply Voltage Power Exhaust Electrical Data MCA MocpVoltage Type Electrical Data With Convenience OutletRLA LRA FLA FAN Motor MCA Mocp LRANEC IFCManual Outdoor-Air Damper VIII. Adjust FACTORY-INSTALLED OptionsWith Hood Attached ScrewsBracket Optional EconoMi$er+Hood BOX IAQ OATORH IarhThermostats EconoMi$er+ Controller WiringDamper Movement Outdoor Air Temperature OAT Sensor Provided EconoMi$er+ Field-Installed AccessoriesSupply Air Temperature SAT Sensor Provided Return Air Temperature RAT SensorVertical ECONOMI$ER+ 3 to 12 1/2 TON Units Outdoor Air Humidity SensorIndoor Air Humidity Sensor Temperature Resistance Low High Range ResolutionRemote Potentiometer Occupied Minimum Position Power ExhaustRemote EconoMi$er+ Enable Control Demand Ventilation Control CO2 Sensor ConfigurationIX. Adjust EVAPORATOR-FAN Speed CO2 Sensor* Standard SettingsUnit Motor Efficiency Evaporator-Fan Motor EfficiencyGeneral Notes for FAN Performance Data Tables Evaporator-Fan Motor PerformanceUnit EVAPORATOR-FAN Maximum Acceptable Continuous BHP2300 521 531 2250 513 5052400 535 584 2500 551 642741 671 972 713 665 940802 684 8661222 791 1489 2400 535 584 1187 786 1453 2300 521 5311293 802 1566 2500 551 642 866 6963900 38004000 4100 4200 42502156 3800 761 18423900 777 1974 2296978 1447 3200 962 1373 3100942 1323 993 1524 3300 958 1400 1008 1604 34003100 746 713 811 883 3000 726 656 793 8223200 766 773 829 947 3300 786 836Airflow 3800 744 1361 804 1572 3700 728 1266 789 1473 8483900 760 1460 819 1676 4000 777 1563 834 17854000 777 1563 3700 728 1266 789 14734100 793 1672 1139 4208 5200681 2250 505 4842300 513 509 2400 527 561708 663 931 681 657 901766 674 993 8941174 787 1437 2400 527 561 1142 782 1403 2300 513 5091241 796 1508 2500 543 617 828 6864200 4250 2074 3800 753 17833900 770 1912 2209765 3000 555 6303100 568 686 8251048 814 1198 3100 568 686 765 696 904825 706 968 1115 823 1269 3200 582 745955 728 1106 888 717 10351026 739 1181 1100 750 12591328 811 3700 676 11063800 690 1185 1414 8233800 690 1185 760 1414 823 3700 676 1106 747 1328 8113900 705 1269 773 1503 4000 719 1357 786 1597VII. Refrigerant Service Ports Internal WiringPRE-START-UP START-UP Unit PreparationXII. Heating CoolingXI. Main Burners XVI. ECONOMI$ER+ Controller XIV. Safety ReliefXIII. Integrated GAS Controller IGC Operation DS1 DS2 DS3 DS4 EconoMi$er+ Controller BoardEconoMi$er+ Inputs and Outputs Start-Up Mode SequenceSetup Points Units Minimum Maximum Factory INC Comments Configuration Variables Read and Setup ModesValue Setting Input/Output ChannelsSetup Mode Error Mode Manual ModeVentilation Air And Free Cooling XVII. ECONOMI$ER+ ConfigurationCompressor Configuration And Control Power Exhaust Configuration Demand Ventilation ConfigurationCooling, Units Without EconoMi$er+ XVIII. Operating SequenceHeating, Units Without EconoMi$er+ Cooling, Units With EconoMi$er+Service Cleaning VI. Economizer Adjustment IV. Blower Belt AdjustmentVIII. HIGH-PRESSURE Switch IX. LOSS-OF-CHARGE SwitchCooling Charging Chart 580F090 To Use Cooling Charging ChartCooling Charging Chart 580F120 Cooling Charging Chart 580F091 Cooling Charging Chart 580F121 XII. Flue GAS Passageways XIV. Limit SwitchXIII. COMBUSTION-AIR Blower XV. Burner IgnitionXVII. Replacement Parts Cleaning and AdjustmentTroubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Problem Cause Remedy Cooling Service TroubleshootingHeating Service Troubleshooting Typical Unit Wiring Schematic 208/230-3-60 Unit Shown Appendix a ECONOMI$ER+ Label Startup ModeAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuraiton Settings Index Call for Free Catalog Service TrainingPage Remove and Store in Job File START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 64 pages 4.35 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.