Bryant 580F XVII. ECONOMI$ER+ Configuration, Compressor Configuration And Control

Page 58

XVII. ECONOMI$ER+ CONFIGURATION

For most applications, the factory setting will be used to con- trol the EconoMi$er+. However, there are 19 different vari- ables that can be used to configure the control for wide range of applications. The factory settings and variables are shown in Table 34.

IMPORTANT: There is no way to reset/restore the factory default configurations; use caution when making changes to any set point or operational variable.

The EconoMi$er+ control accepts an occupied/unoccupied switch input. This input is used to control the occupied and unoccupied minimum ventilation damper position as shown in Table 34 items 2 (ECONOMIN_SP) and 3 (U_ECONOMIN_SP). These values represent the minimum damper position. In addi- tion, the controls allows for different modes of compressor opera- tion in the unoccupied mode. Using item 13 in Table 34 (OCC_MODE), the user can select one of the following unoccu- pied modes:

No unoccupied cooling

Unoccupied free cooling (EconoMi$er+)

Unoccupied free cooling and mechanical cooling

The EconoMi$er+ will control the cooling operation of the unit based on the demand from the thermostat outputs Y1 and Y2. The EconoMi$er+ will monitor the fan output G, but will not control the fan directly. Note that G must be ener- gized for any cooling to take place. Gas or electric heating will be controlled directly from the thermostat.

When a demand for cooling occurs, the control will check to see if it is in the occupied or unoccupied mode. Depending on the configuration, the control will move the outdoor air damper to the ventilation position. If the outdoor air condi- tions are acceptable, then the control will use the EconoMi$er+ for free cooling. If the supply-air temperature does not meet the configurable set point, then the control will turn on additional stages of mechanical cooling. Several compressor sequences can be used depending on the applica- tion requirements; these will be covered in the mechanical compressor staging section.

A. Compressor Configuration And Control

The EconoMi$er+ control can support from 1 to 4 compres- sor stages. For the 3 to 121/2 ton units, there will only be 1 or 2 stages of compressor cooling, so the control is factory configured for 2 stages. There is no difference between 1 and 2 stages. The control also provides the option to configure for high sensible or high latent loads, but for units with only two compressors this option does not apply.

Compressors are configured using item 10 (STAGE_TYPE) in Table 34. The control also has the capability of controlling directly to Y1 and Y2 inputs. The control can be configured to control to the leaving-air temperature using Y1 and Y2 as a low cool and high cool demand based on the supply air set point and the rate of change of supply-air temperature. For low cool the leaving air temperature set point will be SAT_SP +2° F. For high cool the leaving air temperature set point will be the supply-air temperature set point (SAT_SP).

To use this option, configure the compressor sequencing vari- able (STAGE_TYPE) to a value of 3. Configure the supply air temperature set point (SAT_SP) to the desired leaving air temperature.

NOTE: The supply air temperature set point is also the tem- perature used for EconoMi$er+ control.

The logic will control the operation of the compressors depending on the configuration selected. If free cooling can be used, then the compressors will be integrated with the EconoMi$er+ to provide the lowest cost cooling control. The

logic includes time guards on the compressors to provide a minimum of 3 minutes on and 3 minutes off time. The con- trol will also prevent two compressors from starting at the same time. The logic uses the EconoMi$er+ to prevent rapid cycling of the compressors and low air temperatures.

B. Ventilation Air And Free Cooling

In order for the EconoMi$er+ to control ventilation air and free cooling, several items must be configured.

EconoMi$er+ Type

First, select the EconoMi$er+ control type that will be used. This is the EconoMi$er+ Type function (ECONO_TYPE) defined by item 5 in Table 34. The choices are:

1.Vent only — This is used to have just ventilation con- trol. The EconoMi$er+ will not provide free cooling, but the occupied and unoccupied minimum positions can be used.

2.Proportional — In this configuration, full propor- tional EconoMi$er+ control will be used. When

EconoMi$er+ free cooling cannot be used, the damp- ers will be set to the appropriate occupied and unoc- cupied minimum positions.

3.Three-Position — This mode of EconoMi$er+ is used to provide a minimum ventilation EconoMi$er+ posi- tion and a fixed free cooling or high ventilation posi- tion. The high ventilation position is controlled by the optional Remote EconoMi$er+ Enable Switch Input connected to terminals 11 and 12 on T3.

Supply Air Temperature Set Point

Once the type of EconoMi$er+ control has been selected, the user will need to set the Supply Air Temperature set point (SAT_SP). The SAT_SP has a range of 40 to 65 F.

NOTE: This will be the set point when both Y1 and Y2 are closed. When just Y1 is closed, the set point will be ° F higher.

Minimum Damper Position

Set the occupied minimum damper position (ECONOMIN_SP) and unoccupied minimum position (U_ECONOMIN_SP). These should be set to provide the ventilation requirements at full occupancy as defined by the building specifications. When demand ventilation is used, the control will close the dampers below this position based on measured CO2 levels in the space to provide additional operation savings.

The control will also allow for the use of a remote minimum position potentiometer. This will only adjust the Occupied Minimum position. If used, the software set point ECONOMIN_SP should be set to 0 as the control will use the largest set point.

The damper position is not linear with the amount of outside air, so the user will need to set the position of the EconoMi$er+ accordingly. It is best to use the following equa- tion and measured data to set the position:

OA =

SAT – RAT

*100

OAT – RAT

OA = % outdoor air

SAT = supply air temperature

RAT = return air temperature

OAT = outdoor air temperature

The SAT and OAT values can be read from the control and, if the unit is equipped with an RAT sensor, then all three values can be read. For the calculation to work properly, there should be at least a 10° F difference between the OAT and RAT temperatures.

58

Image 58
Contents Safety Considerations Important Read Before InstallingContents InstallationBase Unit Dimensions 580F090,102,120,150 Base Unit Dimensions 580F091,103,121,151 Slab Mount Horizontal Units Only III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support II. Field Fabricate DuctworkCRBTMPWR004A01 CRBTMPWR002A01CRBTMPWR003A01 CRRFCURB003A01Unit Leveling Tolerances Operating Dimensions Unit Weight Physical Data 580F090, 102, 120, 150 Units MED Furnace SectionLOW High091 103 121 151 Nominal Capacity tons 091 103 121 151 Field Power Supply Install Flue HoodVI. Install GAS Piping Field Control WiringHeat Anticipator Settings Electrical Data Without Convenience OutletPower Exhaust Electrical Data MCA Mocp Unbalanced 3-Phase Supply VoltageRLA LRA Electrical Data With Convenience OutletVoltage Type FLA FAN Motor MCA Mocp LRAIFC NECWith Hood Attached VIII. Adjust FACTORY-INSTALLED OptionsManual Outdoor-Air Damper ScrewsHood BOX Optional EconoMi$er+Bracket ORH OATIAQ IarhDamper Movement EconoMi$er+ Controller WiringThermostats Supply Air Temperature SAT Sensor Provided EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Return Air Temperature RAT SensorIndoor Air Humidity Sensor Outdoor Air Humidity SensorVertical ECONOMI$ER+ 3 to 12 1/2 TON Units Temperature Resistance Range Resolution Low HighRemote EconoMi$er+ Enable Control Power ExhaustRemote Potentiometer Occupied Minimum Position CO2 Sensor Configuration Demand Ventilation ControlCO2 Sensor* Standard Settings IX. Adjust EVAPORATOR-FAN SpeedEvaporator-Fan Motor Efficiency Unit Motor EfficiencyUnit EVAPORATOR-FAN Maximum Acceptable Evaporator-Fan Motor PerformanceGeneral Notes for FAN Performance Data Tables Continuous BHP2400 535 584 2250 513 5052300 521 531 2500 551 642802 684 713 665 940741 671 972 8661293 802 1566 2500 551 642 1187 786 1453 2300 521 5311222 791 1489 2400 535 584 866 6964000 38003900 4100 4200 42503900 777 1974 3800 761 18422156 2296942 1323 993 1524 3300 962 1373 3100978 1447 3200 958 1400 1008 1604 34003200 766 773 829 947 3000 726 656 793 8223100 746 713 811 883 3300 786 836Airflow 3900 760 1460 819 1676 3700 728 1266 789 1473 8483800 744 1361 804 1572 4000 777 1563 834 17854100 793 1672 3700 728 1266 789 14734000 777 1563 1139 4208 52002300 513 509 2250 505 484681 2400 527 561766 674 993 681 657 901708 663 931 8941241 796 1508 2500 543 617 1142 782 1403 2300 513 5091174 787 1437 2400 527 561 828 6864200 4250 3900 770 1912 3800 753 17832074 22093100 568 686 3000 555 630765 825825 706 968 765 696 9041048 814 1198 3100 568 686 1115 823 1269 3200 582 7451026 739 1181 888 717 1035955 728 1106 1100 750 12593800 690 1185 3700 676 11061328 811 1414 8233900 705 1269 773 1503 3700 676 1106 747 1328 8113800 690 1185 760 1414 823 4000 719 1357 786 1597PRE-START-UP Internal WiringVII. Refrigerant Service Ports START-UP Unit PreparationXI. Main Burners CoolingXII. Heating XIII. Integrated GAS Controller IGC Operation XIV. Safety ReliefXVI. ECONOMI$ER+ Controller EconoMi$er+ Controller Board DS1 DS2 DS3 DS4Start-Up Mode Sequence EconoMi$er+ Inputs and OutputsValue Setting Configuration Variables Read and Setup ModesSetup Points Units Minimum Maximum Factory INC Comments Input/Output ChannelsSetup Mode Manual Mode Error ModeCompressor Configuration And Control XVII. ECONOMI$ER+ ConfigurationVentilation Air And Free Cooling Demand Ventilation Configuration Power Exhaust ConfigurationHeating, Units Without EconoMi$er+ XVIII. Operating SequenceCooling, Units Without EconoMi$er+ Cooling, Units With EconoMi$er+Service Cleaning VIII. HIGH-PRESSURE Switch IV. Blower Belt AdjustmentVI. Economizer Adjustment IX. LOSS-OF-CHARGE SwitchTo Use Cooling Charging Chart Cooling Charging Chart 580F090Cooling Charging Chart 580F120 Cooling Charging Chart 580F091 Cooling Charging Chart 580F121 XIII. COMBUSTION-AIR Blower XIV. Limit SwitchXII. Flue GAS Passageways XV. Burner IgnitionCleaning and Adjustment XVII. Replacement PartsTroubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Cooling Service Troubleshooting Problem Cause RemedyHeating Service Troubleshooting Typical Unit Wiring Schematic 208/230-3-60 Unit Shown Startup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuraiton Settings Index Service Training Call for Free CatalogPage Preliminary Information START-UP ChecklistRemove and Store in Job File III. START-UP Electrical
Related manuals
Manual 64 pages 4.35 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.