Bryant 580F 3700 728 1266 789 1473 848, 3800 744 1361 804 1572, 3900 760 1460 819 1676, 5100

Page 38

Table 19 — Fan Performance 580F150,151 — Vertical Discharge Units; Standard Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3700

728

1.36

1266

789

1.58

1473

848

1.81

1686

904

2.04

1906

957

2.29

2132

3800

744

1.46

1361

804

1.69

1572

861

1.92

1790

916

2.16

2015

969

2.41

2246

3900

760

1.57

1460

819

1.80

1676

875

2.04

1899

929

2.28

2128

981

2.53

2364

4000

777

1.68

1563

834

1.91

1785

889

2.16

2012

942

2.41

2247

993

2.67

2487

4100

793

1.79

1672

850

2.04

1899

904

2.29

2132

956

2.54

2371

1006

2.80

2615

4200

810

1.92

1786

865

2.16

2018

918

2.42

2255

969

2.68

2499

1018

2.95

2748

4300

826

2.04

1906

880

2.30

2142

932

2.56

2385

983

2.82

2633

1031

3.10

2888

4400

843

2.18

2031

896

2.44

2272

947

2.70

2520

996

2.97

2773

1044

3.25

3032

4500

860

2.32

2161

912

2.58

2408

962

2.85

2660

1010

3.13

2918

1057

3.41

3182

4600

876

2.46

2297

927

2.73

2549

977

3.01

2807

1024

3.29

3070

1070

3.58

3338

4700

893

2.62

2439

943

2.89

2696

992

3.17

2958

1038

3.46

3226

4800

910

2.77

2587

959

3.06

2849

1007

3.34

3116

1053

3.63

3390

4900

927

2.94

2741

975

3.23

3008

1022

3.52

3280

5000

944

3.11

2901

991

3.40

3173

1037

3.70

3451

5100

961

3.29

3068

1007

3.59

3345

5200

978

3.48

3241

5300

995

3.67

3420

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3700

1008

2.54

2364

1058

2.79

2602

1106

3.05

2846

1152

3.32

3094

1198

3.59

3348

3800

1019

2.66

2482

1068

2.92

2725

1116

3.19

2972

1162

3.46

3226

3900

1031

2.79

2605

1079

3.06

2852

1126

3.33

3104

1171

3.61

3362

4000

1042

2.93

2733

1090

3.20

2984

1136

3.48

3241

4100

1054

3.07

2866

1101

3.35

3122

1146

3.63

3383

4200

1066

3.22

3004

1112

3.50

3264

4300

1078

3.38

3148

1123

3.66

3413

4400

1090

3.54

3297

4500

1103

3.70

3451

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 3.70.

3.See page 29 for General Fan Performance Notes.

38

Image 38
Contents Safety Considerations Important Read Before InstallingContents InstallationBase Unit Dimensions 580F090,102,120,150 Base Unit Dimensions 580F091,103,121,151 Slab Mount Horizontal Units Only III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support II. Field Fabricate DuctworkCRBTMPWR004A01 CRBTMPWR002A01CRBTMPWR003A01 CRRFCURB003A01Unit Leveling Tolerances Operating Dimensions Unit Weight Physical Data 580F090, 102, 120, 150 Units MED Furnace SectionLOW High091 103 121 151 Nominal Capacity tons 091 103 121 151 Field Power Supply Install Flue HoodVI. Install GAS Piping Field Control WiringHeat Anticipator Settings Electrical Data Without Convenience OutletPower Exhaust Electrical Data MCA Mocp Unbalanced 3-Phase Supply VoltageRLA LRA Electrical Data With Convenience OutletVoltage Type FLA FAN Motor MCA Mocp LRAIFC NECWith Hood Attached VIII. Adjust FACTORY-INSTALLED OptionsManual Outdoor-Air Damper ScrewsBracket Optional EconoMi$er+Hood BOX ORH OATIAQ IarhThermostats EconoMi$er+ Controller WiringDamper Movement Supply Air Temperature SAT Sensor Provided EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Return Air Temperature RAT SensorVertical ECONOMI$ER+ 3 to 12 1/2 TON Units Outdoor Air Humidity SensorIndoor Air Humidity Sensor Temperature Resistance Range Resolution Low HighRemote Potentiometer Occupied Minimum Position Power ExhaustRemote EconoMi$er+ Enable Control CO2 Sensor Configuration Demand Ventilation ControlCO2 Sensor* Standard Settings IX. Adjust EVAPORATOR-FAN SpeedEvaporator-Fan Motor Efficiency Unit Motor EfficiencyUnit EVAPORATOR-FAN Maximum Acceptable Evaporator-Fan Motor PerformanceGeneral Notes for FAN Performance Data Tables Continuous BHP2400 535 584 2250 513 5052300 521 531 2500 551 642802 684 713 665 940741 671 972 8661293 802 1566 2500 551 642 1187 786 1453 2300 521 5311222 791 1489 2400 535 584 866 6964000 38003900 4100 4200 42503900 777 1974 3800 761 18422156 2296942 1323 993 1524 3300 962 1373 3100978 1447 3200 958 1400 1008 1604 34003200 766 773 829 947 3000 726 656 793 8223100 746 713 811 883 3300 786 836Airflow 3900 760 1460 819 1676 3700 728 1266 789 1473 8483800 744 1361 804 1572 4000 777 1563 834 17854100 793 1672 3700 728 1266 789 14734000 777 1563 1139 4208 52002300 513 509 2250 505 484681 2400 527 561766 674 993 681 657 901708 663 931 8941241 796 1508 2500 543 617 1142 782 1403 2300 513 5091174 787 1437 2400 527 561 828 6864200 4250 3900 770 1912 3800 753 17832074 22093100 568 686 3000 555 630765 825825 706 968 765 696 9041048 814 1198 3100 568 686 1115 823 1269 3200 582 7451026 739 1181 888 717 1035955 728 1106 1100 750 12593800 690 1185 3700 676 11061328 811 1414 8233900 705 1269 773 1503 3700 676 1106 747 1328 8113800 690 1185 760 1414 823 4000 719 1357 786 1597PRE-START-UP Internal WiringVII. Refrigerant Service Ports START-UP Unit PreparationXII. Heating CoolingXI. Main Burners XVI. ECONOMI$ER+ Controller XIV. Safety ReliefXIII. Integrated GAS Controller IGC Operation EconoMi$er+ Controller Board DS1 DS2 DS3 DS4Start-Up Mode Sequence EconoMi$er+ Inputs and OutputsValue Setting Configuration Variables Read and Setup ModesSetup Points Units Minimum Maximum Factory INC Comments Input/Output ChannelsSetup Mode Manual Mode Error ModeVentilation Air And Free Cooling XVII. ECONOMI$ER+ ConfigurationCompressor Configuration And Control Demand Ventilation Configuration Power Exhaust ConfigurationHeating, Units Without EconoMi$er+ XVIII. Operating SequenceCooling, Units Without EconoMi$er+ Cooling, Units With EconoMi$er+Service Cleaning VIII. HIGH-PRESSURE Switch IV. Blower Belt AdjustmentVI. Economizer Adjustment IX. LOSS-OF-CHARGE SwitchTo Use Cooling Charging Chart Cooling Charging Chart 580F090Cooling Charging Chart 580F120 Cooling Charging Chart 580F091 Cooling Charging Chart 580F121 XIII. COMBUSTION-AIR Blower XIV. Limit SwitchXII. Flue GAS Passageways XV. Burner IgnitionCleaning and Adjustment XVII. Replacement PartsTroubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Cooling Service Troubleshooting Problem Cause RemedyHeating Service Troubleshooting Typical Unit Wiring Schematic 208/230-3-60 Unit Shown Startup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuraiton Settings Index Service Training Call for Free CatalogPage Preliminary Information START-UP ChecklistRemove and Store in Job File III. START-UP Electrical
Related manuals
Manual 64 pages 4.35 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.