Carrier 48PG20-28 specifications Fan Performance 48PGD20 Vertical Supply/Return Units

Page 19

Condenser Fans and Motors — Condenser fans and motors are factory set. Refer to Condenser-Fan Adjustment section (page 49) as required.

Return-Air Filters — Check that correct filters are in- stalled in filter tracks (see Table 1). Do not operate unit without return-air filters.

NOTE: For units with 4-in. filter option, units are shipped with standard 2-in. filters. To install 4-in. filters, the filter spacers must be removed.

Outdoor-Air Inlet Screens — Outdoor-air inlet screens must be in place before operating unit.

Gas Heat — Verify gas pressures before turning on heat as follows:

1.Turn off field-supplied manual gas stop, located external to unit.

2.Connect pressure gage to supply gas tap, located on field- supplied manual shutoff valve (see Fig. 14).

3.Connect pressure gage to manifold pressure tap.

4.Turn on field-supplied manual gas stop. Temporarily install the jumper wire between “R” and “W1” on TB2. Set thermostat to HEAT and raise set point until heat comes on.

5.After the unit has run for several minutes, verify the sup- ply gas pressure is between 5.5 in. wg to 13.0 in. wg, and the manifold pressure is 2.95 in. wg on horizontal dis- charge applications and 3.00 on vertical discharge appli- cations. If manifold pressure must be adjusted, refer to Gas Valve Adjustment section.

NOTE: Supply gas pressure must not exceed 13.0 in. wg.

6.Set thermostat to OFF.

7.Remove jumper wire if the unit will be operating under thermostat mode.

8.Return thermostat to desired set point.

Table 5 — Fan Performance — 48PGD20 Vertical Supply/Return Units

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

0.2

 

0.4

 

 

0.6

 

 

0.8

 

 

 

1.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

5000

 

590

 

1.47

 

663

 

1.74

 

727

 

2.01

 

786

 

2.26

 

840

 

2.52

5500

 

633

 

1.82

 

703

 

2.11

 

764

 

2.40

 

820

 

2.67

A

872

 

2.94

6000

 

677

 

2.21

 

744

 

2.53

A

803

 

2.84

A

857

 

3.13

 

907

 

3.42

6500

 

722

 

2.67

A

786

 

3.01

 

842

 

3.33

 

894

 

3.64

 

942

 

3.95

7000

A

767

 

3.17

 

828

 

3.53

 

883

 

3.88

 

933

 

4.21

B

979

 

4.53

7500

 

813

 

3.74

 

871

 

4.12

 

924

 

4.48

B

972

 

4.83

1017

 

5.18

 

 

 

 

 

 

 

 

 

8000

 

859

 

4.36

 

915

 

4.77

B

966

 

5.15

1012

 

5.52

 

1056

 

5.88

 

 

 

 

 

 

 

 

 

8500

 

906

 

5.05

B

959

 

5.47

C

1008

 

5.87

C

1053

 

6.26

C

1096

 

6.64

9000

C

952

 

5.81

C

1004

 

6.25

1051

 

6.67

1095

 

7.07

 

1136

 

7.47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

1.2

 

1.4

 

 

1.6

 

 

1.8

 

 

 

2.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

5000

 

891

 

2.77

 

940

 

3.02

 

987

 

3.27

 

1032

 

3.52

 

1076

 

3.77

5500

A

921

 

3.21

 

968

 

3.48

 

1014

 

3.74

B

1057

 

4.01

B

1099

 

4.27

6000

 

954

 

3.70

B

999

 

3.99

B

1042

 

4.27

1084

 

4.55

1125

 

4.83

 

 

 

 

 

 

 

 

6500

 

988

 

4.25

1032

 

4.55

 

1073

 

4.85

 

1114

 

5.14

 

1153

 

5.44

 

 

 

 

 

 

 

 

 

 

7000

B

1024

 

4.85

 

1066

 

5.17

 

1106

 

5.48

C

1145

 

5.79

 

1183

 

6.10

7500

 

1060

 

5.51

 

1101

 

5.84

C

1140

 

6.17

 

1178

 

6.50

D

1215

 

6.82

8000

 

1098

 

6.23

C

1138

 

6.58

1176

 

6.92

D

1213

 

7.26

1249

 

7.60

 

 

 

 

 

 

 

 

8500

C

1137

 

7.01

 

1175

 

7.38

D

1212

 

7.74

1248

 

8.09

 

1283

 

8.45

 

 

 

 

 

 

 

 

9000

1176

 

7.86

D

1214

 

8.24

1250

 

8.61

 

1285

 

8.99

 

1319

 

9.36

 

 

 

 

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

Boldface indicates field-supplied motor/drive required.

NOTES:

1.Motor drive ranges:

(A)Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)

(B)Mid-Low Range: 949-1206 rpm, 5.75 bhp

(C)Mid-High Range: 941-1176 rpm, 8.63 bhp

(D)High Range: 1014-1297 rpm, 11.50 bhp

All other rpms require field-supplied motor or drive.

2. See page 36 for general fan performance notes.

19

Image 19
Contents Installation, Start-Up and Service Instructions Provide Unit Support InstallationRoof Curb Details Shipping Rail Removal Base Unit Dimensions Compressor Physical DataFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Alignment Hole Details Make Unit Duct ConnectionsConcentric Duct Details Install Flue Hood and Inlet HoodCondensate Drain Details Make Electrical ConnectionsField Power Wiring Connections Supply Optional Hacr Size Supply Optional Hacr Size Voltage Breaker Outdoor-Air Hood Details Outdoor-Air Hood Assembled Power Exhaust or Barometric Relief Damper Mounting Details PRE-START-UP Fan Performance 48PGD20 Vertical Supply/Return Units Fan Performance 48PGE20 Vertical Supply/Return Units 8500 940 Fan Performance 48PGF20 Vertical Supply/Return UnitsFan Performance 48PGD24 Vertical Supply/Return Units Fan Performance 48PGE24 Vertical Supply/Return Units 500 940 Fan Performance 48PGF24 Vertical Supply/Return Units1310 11.76 1342 12.33 11,500 Fan Performance 48PGD28 Vertical Supply/Return Units10,500 11,0001309 1341 10.09 500 Fan Performance 48PGE28 Vertical Supply/Return Units1327 11.47 11,000 1304 000Fan Performance 48PGF28 Vertical Supply/Return Units Fan Performance 48PGD20 Horizontal Supply and Return Units Fan Performance 48PGE20 Horizontal Supply and Return Units Fan Performance 48PGF20 Horizontal Supply and Return Units Fan Performance 48PGD24 Horizontal Supply and Return Units Fan Performance 48PGE24 Horizontal Supply and Return Units 1354 1391 000 1381 500 10,000 Fan Performance 48PGF24 Horizontal Supply and Return Units1328 10.37 1358 10.87 10,000 Fan Performance 48PGD28 Horizontal Supply and Return Units1308 1340 10.08 500 Fan Performance 48PGE28 Horizontal Supply and Return UnitsGeneral Notes for FAN Performance Data Tables Fan Performance 48PGF28 Horizontal Supply and Return UnitsEvaporator Fan Motor Specifications Power Exhaust Fan Performance 48PG20-28Operation Air Quantity Limits Evaporator Fan Motor Specifications Fan Rpm at Motor Pulley Settings Accessory/FIOP Static Pressure in. wg* 48PG20-28EconoMi$er IV Sensor Usage EconoMi$er IV Wiring Enthalpy Changeover Set Points Page Operating Sequence CO2 Sensor Standard SettingsSubcooler Operation Service Removing Heat Exchanger Ceramic LubricationEvaporator-Fan Motor Adjustment Unit Model Number Position Condenser-Fan Adjustment FigBelt Tension Adjustment Sensor Temperature/Resistance ValuesCharging Chart 48PG20 Gas Valve AdjustmentGas Valve Altitude Compensation Protective DevicesTypical Low Voltage Control Schematic Typical Power Schematic Typical Component Arrangement 48PG20,24 Typical Component Arrangement 48PG28 Cooling Service Analysis TroubleshootingBurners Will Not Ignite Gas Heating Service AnalysisIGC Control Heating and Cooling Flashes EconoMi$er IV TroubleshootingIGC Board LED Alarm Codes FlashLED Status Function Copyright 2005 Carrier Corporation Page Unit START-UP Checklist