Carrier 48PG20-28 specifications Condenser-Fan Adjustment Fig, Belt Tension Adjustment

Page 49

Table 30 — Belt Tension Adjustment

 

 

 

 

 

BELT TENSION (lb)

 

 

 

48PG

VOLTAGE

 

 

 

Unit Model Number Position 10

 

 

 

 

 

A,J

B,K

C,L

D,M

E,N

 

F,P

G,Q

H,R

 

230

4.8

5.1

5.6

4.5

NA

 

4.7

5.0

5.5

20

460

4.8

5.1

5.6

4.5

NA

 

4.7

5.0

5.5

 

575

5.3

5.1

5.6

4.5

NA

 

5.2

5.0

5.5

 

230

4.8

5.1

5.6

4.5

NA

 

4.7

5.0

5.5

24

460

4.8

5.1

5.6

4.5

NA

 

4.7

5.0

5.5

 

575

5.3

5.1

5.6

4.5

NA

 

5.2

5.0

5.5

 

230

4.5

5.4

5.9

4.5

4.5

 

5.4

5.9

4.5

28

460

4.5

5.4

5.9

4.5

4.5

 

5.4

5.9

4.5

 

575

4.5

5.4

5.9

4.5

4.5

 

5.4

5.9

4.5

Condenser-Fan Adjustment (Fig. 35)

1.Shut off unit power supply.

2.Remove condenser-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews.

3.Adjust fan height as shown in Fig. 35.

4.Tighten setscrews and replace condenser-fan assembly.

5.Turn on power to unit.

Fig. 35 — Condenser-Fan Adjustment

Verify Sensor Performance — Using an ohmmeter and a thermometer, compare measured temperature to the resistance shown in Table 31.

Table 31 — Sensor Temperature/Resistance Values

TEMPERATURE (F)

RESISTANCE (ohms)

–58

200,250

–40

100,680

–22

53,010

–4

29,091

14

16,590

32

9,795

50

5,970

68

3,747

77

3,000

86

2,416

104

1,597

122

1,080

140

746

158

525

176

376

185

321

194

274

212

203

230

153

248

116

257

102

266

89

284

70

302

55

Economizer Operation During Power Fail- ure — Dampers have a spring return. In event of power fail- ure, dampers will return to fully closed position until power is restored. Do not manually operate damper motor.

Evacuation — Proper evacuation of the system will re- move noncondensables and ensure a tight, dry system before charging. Evacuate from both high and low side ports. Never use the system compressor as a vacuum pump. Refrigerant tubes and indoor coil should be evacuated to 500 microns. Always break a vacuum with dry nitrogen. The two possible methods are the deep vacuum method and the triple evacuation method

DEEP VACUUM METHOD — The deep vacuum method requires a vacuum pump capable of pulling a minimum vacu- um of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 36.)

TRIPLE EVACUATION METHOD — The triple evacuation method should only be used when vacuum pump is capable of pumping down to 28 in. of mercury and system does not con- tain any liquid water. Proceed as follows:

1.Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.

2.Close service valves and shut off vacuum pump.

3.Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.

4.Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system, absorbing moisture.

5.Repeat this procedure. System will then contain minimal amounts of contaminants and water vapor.

 

5000

 

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

 

4000

 

 

 

 

 

 

 

 

3500

 

 

 

 

 

 

LEAK IN

MICRONS

 

 

 

 

 

 

SYSTEM

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1500

 

 

 

 

 

 

VACUUM TIGHT

 

 

 

 

 

 

 

TOO WET

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

TIGHT

 

 

 

 

 

 

 

DRY SYSTEM

 

 

 

 

 

 

 

 

 

0

1

2

3

4

5

6

7

 

 

 

 

MINUTES

 

 

 

Fig. 36 — Deep Vacuum Graph

49

Image 49
Contents Installation, Start-Up and Service Instructions Provide Unit Support InstallationRoof Curb Details Shipping Rail Removal Base Unit Dimensions Compressor Physical DataFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Alignment Hole Details Make Unit Duct ConnectionsConcentric Duct Details Install Flue Hood and Inlet HoodCondensate Drain Details Make Electrical ConnectionsField Power Wiring Connections Supply Optional Hacr Size Supply Optional Hacr Size Voltage Breaker Outdoor-Air Hood Details Outdoor-Air Hood Assembled Power Exhaust or Barometric Relief Damper Mounting Details PRE-START-UP Fan Performance 48PGD20 Vertical Supply/Return Units Fan Performance 48PGE20 Vertical Supply/Return Units 8500 940 Fan Performance 48PGF20 Vertical Supply/Return UnitsFan Performance 48PGD24 Vertical Supply/Return Units Fan Performance 48PGE24 Vertical Supply/Return Units 500 940 Fan Performance 48PGF24 Vertical Supply/Return Units10,500 Fan Performance 48PGD28 Vertical Supply/Return Units11,000 1310 11.76 1342 12.33 11,5001327 11.47 11,000 Fan Performance 48PGE28 Vertical Supply/Return Units1304 000 1309 1341 10.09 500Fan Performance 48PGF28 Vertical Supply/Return Units Fan Performance 48PGD20 Horizontal Supply and Return Units Fan Performance 48PGE20 Horizontal Supply and Return Units Fan Performance 48PGF20 Horizontal Supply and Return Units Fan Performance 48PGD24 Horizontal Supply and Return Units Fan Performance 48PGE24 Horizontal Supply and Return Units 1354 1391 000 1381 500 10,000 Fan Performance 48PGF24 Horizontal Supply and Return Units1328 10.37 1358 10.87 10,000 Fan Performance 48PGD28 Horizontal Supply and Return Units1308 1340 10.08 500 Fan Performance 48PGE28 Horizontal Supply and Return UnitsGeneral Notes for FAN Performance Data Tables Fan Performance 48PGF28 Horizontal Supply and Return UnitsEvaporator Fan Motor Specifications Power Exhaust Fan Performance 48PG20-28Operation Air Quantity Limits Evaporator Fan Motor Specifications Fan Rpm at Motor Pulley Settings Accessory/FIOP Static Pressure in. wg* 48PG20-28EconoMi$er IV Sensor Usage EconoMi$er IV Wiring Enthalpy Changeover Set Points Page Operating Sequence CO2 Sensor Standard SettingsSubcooler Operation Service Removing Heat Exchanger Ceramic LubricationEvaporator-Fan Motor Adjustment Belt Tension Adjustment Condenser-Fan Adjustment FigSensor Temperature/Resistance Values Unit Model Number PositionCharging Chart 48PG20 Gas Valve AdjustmentGas Valve Altitude Compensation Protective DevicesTypical Low Voltage Control Schematic Typical Power Schematic Typical Component Arrangement 48PG20,24 Typical Component Arrangement 48PG28 Cooling Service Analysis TroubleshootingBurners Will Not Ignite Gas Heating Service AnalysisIGC Control Heating and Cooling IGC Board LED Alarm Codes EconoMi$er IV TroubleshootingFlash FlashesLED Status Function Copyright 2005 Carrier Corporation Page Unit START-UP Checklist