Carrier 48PG20-28 specifications Protective Devices, Altitude Compensation

Page 52

Table 32 — Altitude Compensation*

NATURAL GAS

ELEVATION

 

NATURAL GAS ORIFICE SIZE†

 

(ft)

 

Low Heat

Medium Heat

High Heat (6 Cell)

High Heat (8 Cell)

0-1,999

 

29

30

29

29

2,000

 

29

30

29

29

3,000

 

30

31

30

30

4,000

 

30

31

30

30

5,000

 

30

31

30

30

6,000

 

30

31

30

30

7,000

 

31

32

31

31

8,000

 

31

32

31

31

9,000

 

31

32

31

31

10,000

 

32

33

32

32

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input

 

rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.

 

†Orifices available through the local Carrier dealer.

 

 

 

PROPANE GAS

ELEVATION

 

PROPANE GAS ORIFICE SIZE†

 

(ft)

Low Heat

Medium Heat

High Heat (6 Cell)

High Heat (8 Cell)

0-1,999

35

38

35

35

2,000

36

39

36

36

3,000

36

39

36

36

4,000

37

40

37

37

5,000

37

40

37

37

6,000

38

41

38

38

7,000

39

42

39

39

8,000

40

43

40

40

9,000

41

44

41

41

10,000

42

45

42

42

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input ate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.

†Orifices available through the local Carrier dealer.

Filter Drier — Replace whenever refrigerant system is ex- posed to atmosphere. Only use factory specified liquid-line filter driers with working pressures no less than 650 psig. Do not install a suction-line filter drier in liquid line. A liquid-line filter drier designed for use with Puron® refrigerant is required for each circuit.

Protective Devices

COMPRESSOR PROTECTION

Overcurrent — Each compressor has internal line break motor protection.

Overtemperature — Each compressor has an internal protector to protect it against excessively high discharge gas temperatures.

High-Pressure Switch — If the high-pressure switch opens, the compressor will shut down and the compressor lockout (CLO) device will energize to block further compressor operation. The high-pressure switch will reset automatically as the refrigerant pressure drops below its reset level. The CLO will remain ener- gized until manually reset or cooling demand is removed.

Low-Pressure Switch — If the low-pressure switch opens, the compressor will shut down and the compressor lockout (CLO) device will energize to block further compressor opera- tion. The low-pressure switch will reset automatically as the refrigerant pressure rises above its reset level. The CLO will remain energized until manually reset or cooling demand is removed.

Freeze Protection Switch — This switch is installed on each evaporator coil section to provide protection against continued unit operation with a frosted evaporator surface. If the freeze protection switch opens, the compressor on this circuit will shut down and the compressor lockout (CLO) device will ener- gize to block further compressor operation. The freeze protec- tion switch will reset as the evaporator tube temperature rises above its reset level. The CLO will remain energized until manually reset or cooling demand is removed.

Compressor Lockout (CLO) Device — The CLO prevents automatic recycling of the compressor as safety controls reset. If the high-pressure switch, low-pressure switch or freeze pro- tection switch opens, the CLO device will energize to block further compressor operation. To reset the CLO (after all safety switches have reset), either open the thermostat to remove the cooling demand signal (and then re-close) or cycle the control power in the unit.

EVAPORATOR FAN MOTOR PROTECTION — A manu- al reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker.

CONDENSER-FAN MOTOR PROTECTION — Each condenser-fan motor is internally protected against overtemperature.

Fuses are also located in the control box and feed power to the condenser fan motors. Always replace blown fuses with the correct size fuse as indicated on the unit fuse label.

Relief Devices — All units have relief devices to protect against damage from excessive pressures (i.e., fire). These devices protect the high and low side and are located at the suc- tion line service port. Protect joint during brazing operations near joint.

Control Circuit, 24-VEach control circuit is pro- tected against overcurrent by a 3.2 amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting. See Fig. 42-45 for schematics.

Replacement Parts — A complete list of replacement parts may be obtained from any Carrier distributor upon request.

Diagnostic LEDs — The IGC control board has a LED for diagnostic purposes. See Unit Troubleshooting section on page 57 for more information.

52

Image 52
Contents Installation, Start-Up and Service Instructions Installation Provide Unit SupportRoof Curb Details Shipping Rail Removal Base Unit Dimensions Physical Data CompressorFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Make Unit Duct Connections Alignment Hole DetailsInstall Flue Hood and Inlet Hood Concentric Duct DetailsMake Electrical Connections Condensate Drain DetailsField Power Wiring Connections Supply Optional Hacr Size Supply Optional Hacr Size Voltage Breaker Outdoor-Air Hood Details Outdoor-Air Hood Assembled Power Exhaust or Barometric Relief Damper Mounting Details PRE-START-UP Fan Performance 48PGD20 Vertical Supply/Return Units Fan Performance 48PGE20 Vertical Supply/Return Units Fan Performance 48PGF20 Vertical Supply/Return Units 8500 940Fan Performance 48PGD24 Vertical Supply/Return Units Fan Performance 48PGE24 Vertical Supply/Return Units Fan Performance 48PGF24 Vertical Supply/Return Units 500 940Fan Performance 48PGD28 Vertical Supply/Return Units 10,50011,000 1310 11.76 1342 12.33 11,500Fan Performance 48PGE28 Vertical Supply/Return Units 1327 11.47 11,0001304 000 1309 1341 10.09 500Fan Performance 48PGF28 Vertical Supply/Return Units Fan Performance 48PGD20 Horizontal Supply and Return Units Fan Performance 48PGE20 Horizontal Supply and Return Units Fan Performance 48PGF20 Horizontal Supply and Return Units Fan Performance 48PGD24 Horizontal Supply and Return Units Fan Performance 48PGE24 Horizontal Supply and Return Units Fan Performance 48PGF24 Horizontal Supply and Return Units 1354 1391 000 1381 500 10,000Fan Performance 48PGD28 Horizontal Supply and Return Units 1328 10.37 1358 10.87 10,000Fan Performance 48PGE28 Horizontal Supply and Return Units 1308 1340 10.08 500Fan Performance 48PGF28 Horizontal Supply and Return Units General Notes for FAN Performance Data TablesEvaporator Fan Motor Specifications Power Exhaust Fan Performance 48PG20-28Operation Air Quantity Limits Evaporator Fan Motor Specifications Accessory/FIOP Static Pressure in. wg* 48PG20-28 Fan Rpm at Motor Pulley SettingsEconoMi$er IV Sensor Usage EconoMi$er IV Wiring Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings Operating SequenceSubcooler Operation Service Lubrication Removing Heat Exchanger CeramicEvaporator-Fan Motor Adjustment Condenser-Fan Adjustment Fig Belt Tension AdjustmentSensor Temperature/Resistance Values Unit Model Number PositionGas Valve Adjustment Charging Chart 48PG20Gas Valve Protective Devices Altitude CompensationTypical Low Voltage Control Schematic Typical Power Schematic Typical Component Arrangement 48PG20,24 Typical Component Arrangement 48PG28 Troubleshooting Cooling Service AnalysisGas Heating Service Analysis Burners Will Not IgniteIGC Control Heating and Cooling EconoMi$er IV Troubleshooting IGC Board LED Alarm CodesFlash FlashesLED Status Function Copyright 2005 Carrier Corporation Page Unit START-UP Checklist