Carrier 48PG20-28 specifications Install Flue Hood and Inlet Hood, Concentric Duct Details

Page 10

NOTE: Dimensions A, A, B, and Bare obtained from field-supplied ceiling diffuser.

Shaded areas indicate block-off pans.

Fig. 9 — Concentric Duct Details

Step 6 — Install Flue Hood and Inlet Hood —

Flue hood (smaller hood), inlet hood (larger hood), and screens are shipped inside the unit in the fan section. To install, remove the heat panel. The flue hood is attached to the heat section panel from the outside using the screws provided. See Fig. 10.

The inlet hood is installed by inserting the hood through the back of the heat panel. Attach the hood by inserting the screws provided through the clearance holes in the heat panel and into the intake hood.

Install the screens into both hoods using the screws and re- taining nuts provided with the unit.

Attach the cover of the observation hole on the intake hood and then replace the heat panel onto the unit to complete the in- stallation.

NOTE: When properly installed, the flue hood will line up with the combustion fan housing. See Fig. 11.

Step 7 — Trap Condensate Drain — See Fig. 12 for drain location. One 3/4-in. half coupling is provided outside unit evaporator section for condensate drain connection. A trap at least 4-in. deep must be used. See Fig. 13.

All units must have an external trap for condensate drain- age. Install a trap at least 4 in. deep and protect against freeze- up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection.

Step 8 — Install Gas Piping — Unit is equipped for use with natural gas. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-latest year and addendum Z223.1A-latest year entitled NFGC. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.

Support gas piping. For example, a 3/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 3 support beams.

Install field-supplied manual gas shutoff valve with a 1/8-in. NPT pressure tap for test gage connection at unit. The pressure tap is located on the gas manifold, adjacent to the gas valve. Field gas piping must include sediment trap and union. See Fig. 14.

FLUE HOOD

INLET HOOD

Fig. 10 — Flue and Inlet Hood Locations

COMBUSTION

FAN HOUSING

HEAT

EXCHANGER

SECTION INDUCED-DRAFT MOTOR

MAIN BURNER

SECTION

Fig. 11 — Combustion Fan Housing Location

10

Image 10
Contents Installation, Start-Up and Service Instructions Installation Provide Unit SupportRoof Curb Details Shipping Rail Removal Base Unit Dimensions Physical Data CompressorFan Motor and Drive Data Vertical Supply/Return Fan Motor and Drive Data Horizontal Supply/Return Make Unit Duct Connections Alignment Hole DetailsInstall Flue Hood and Inlet Hood Concentric Duct DetailsMake Electrical Connections Condensate Drain DetailsField Power Wiring Connections Supply Optional Hacr Size Supply Optional Hacr Size Voltage Breaker Outdoor-Air Hood Details Outdoor-Air Hood Assembled Power Exhaust or Barometric Relief Damper Mounting Details PRE-START-UP Fan Performance 48PGD20 Vertical Supply/Return Units Fan Performance 48PGE20 Vertical Supply/Return Units Fan Performance 48PGF20 Vertical Supply/Return Units 8500 940Fan Performance 48PGD24 Vertical Supply/Return Units Fan Performance 48PGE24 Vertical Supply/Return Units Fan Performance 48PGF24 Vertical Supply/Return Units 500 94011,000 Fan Performance 48PGD28 Vertical Supply/Return Units10,500 1310 11.76 1342 12.33 11,5001304 000 Fan Performance 48PGE28 Vertical Supply/Return Units1327 11.47 11,000 1309 1341 10.09 500Fan Performance 48PGF28 Vertical Supply/Return Units Fan Performance 48PGD20 Horizontal Supply and Return Units Fan Performance 48PGE20 Horizontal Supply and Return Units Fan Performance 48PGF20 Horizontal Supply and Return Units Fan Performance 48PGD24 Horizontal Supply and Return Units Fan Performance 48PGE24 Horizontal Supply and Return Units Fan Performance 48PGF24 Horizontal Supply and Return Units 1354 1391 000 1381 500 10,000Fan Performance 48PGD28 Horizontal Supply and Return Units 1328 10.37 1358 10.87 10,000Fan Performance 48PGE28 Horizontal Supply and Return Units 1308 1340 10.08 500Fan Performance 48PGF28 Horizontal Supply and Return Units General Notes for FAN Performance Data TablesEvaporator Fan Motor Specifications Power Exhaust Fan Performance 48PG20-28Operation Air Quantity Limits Evaporator Fan Motor Specifications Accessory/FIOP Static Pressure in. wg* 48PG20-28 Fan Rpm at Motor Pulley SettingsEconoMi$er IV Sensor Usage EconoMi$er IV Wiring Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings Operating SequenceSubcooler Operation Service Lubrication Removing Heat Exchanger CeramicEvaporator-Fan Motor Adjustment Sensor Temperature/Resistance Values Condenser-Fan Adjustment FigBelt Tension Adjustment Unit Model Number PositionGas Valve Adjustment Charging Chart 48PG20Gas Valve Protective Devices Altitude CompensationTypical Low Voltage Control Schematic Typical Power Schematic Typical Component Arrangement 48PG20,24 Typical Component Arrangement 48PG28 Troubleshooting Cooling Service AnalysisGas Heating Service Analysis Burners Will Not IgniteIGC Control Heating and Cooling Flash EconoMi$er IV TroubleshootingIGC Board LED Alarm Codes FlashesLED Status Function Copyright 2005 Carrier Corporation Page Unit START-UP Checklist