Vermont Casting 3232, 3399, 3369, 3354, 3225, 3390, 3350, 3360 Venting Requirements Natural Vent Only

Page 11

Radiance Direct Vent /Natural Vent Gas Heater

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

Inside Corner

Outside Corner

Alcove Applications*

 

 

 

F =

 

 

G =

 

Combustible

G

Combustible

 

6"

(152 mm)

 

6" (152 mm)

V

Noncombustible

 

 

2"

(51 mm)

 

Noncombustible

 

V

 

F

 

2" (51 mm)

 

 

Balcony -

Balcony -

with no side wall

with perpendicular side wall

M

M

 

V

V

 

P

M =

Combustible &

Noncombustible

Combustible &

M = 24" (610 mm)

Noncombustible

P = 20” (508 mm)

12" (305 mm)

D

C C

V

E

O

E = Min. 6” (152 mm) for non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls

O = 8’ (2.4 m) Min.

No.

 

 

of Caps

DMin.

CMax.

1

3’ (.9 mm)

2 x DActual

2

6’ (1.8 m)

1 x DActual

3

9’ (2.7 m)

2/3 x DActual

4

12’ (3.7 m)

1/2 x DActual

DMin. = # of Termination caps x 3

CMax. = (2 / # termination caps) x DActual

584-15

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.

Fig. 10 Termination clearances.

Venting Requirements - Natural Vent Only

Vertical Run (in feet) (Measured from top of the unit before any elbow)

��

��

�� A

�� B

��

��

��

��

��

��

��

��

��

��

������������������������������������������������������

Venting Runs

NOTE: When venting staight vertical, without any elbow, a minimum of 8 ft. vertical is required off the top of the stove.

= Acceptable venting configuration = Unacceptable venting configuration

A:Vertical installations up to 36 feet (12m) in height. Up to an 18 ft. horizontal vent run can be installed within the vent system using a maximum of two 90-degree elbows or four 45-degree elbows.

B:Vertical installations up to 36 feet (12m) in height. Up to a 24 ft. horizontal vent run can be installed within the vent system using a maximum of two 45-degree elbows.

(Ratio = 2/3, Hor./Vert.)

Horizontal Run (in feet)

Fig. 11 Vent termination window - Natural Vent ONLY.

NOTE: When using the FSDHAG, the restrictor

 

plate supplied with the stove is not used.

20004188

11

Image 11
Contents Radiance Direct Vent/Natural Vent Gas Heater Table Of Contents Installation & Operating Instructions Radiance dimensions Radiance Direct Vent/Natural Vent Stove DimensionsClearance Requirements Installation RequirementsLocating The Stove Hearth Requirements Wall Centerline from FloorWall and Ceiling Clearances Horizontal Termination Direct Vent only Gas SpecificationsGas Inlet and Manifold Pressures High ElevationsVent Termination Clearances Restictor Plate is used on Direct Vent installations onlyVertical Termination Direct Vent only Location of Vent Termination General Venting Information Termination Location Canadian Installations1 US Installations2Plate supplied with the stove is not used Venting Requirements Natural Vent OnlyApproved Vent System Components Venting Requirements and Options Direct Vent onlyUnpack and Assemble Legs Assembly ProceduresParts Bag Contents Tools RequiredRemove rear shroud Install the Optional FanAttach the Inner Vent Assembly to the stove Venting System Assembly Direct Vent General InformationInstall the Vent Adapter Pipe For Canadian installations The venting system mustDiscard the inner starter pipe shipped with the log Side Wall Termination AssemblyInstall the Outer Adapter Pipe. Orient the verti Measure the horizontal length Vent Termination Below Grade Vertical Through the Roof Vent AssemblyInstall firestops and attic insulation shield Venting System Assembly Natural Vent General InformationInstall Log Set Install the Vent PipeConnect the Gas Supply Line Install the left and right rear logs and the right logThermostat Connection optional Install ON/OFF SwitchInstall the Mesh and Grille Burner InformationYour First Fire Flame & Temperature AdjustmentFlame Characteristics OperationTo Turn Off Gas To Heater Lighting and Operating InstructionsSymptom Possible Causes Corrective Action Troubleshooting / Honeywell #8420 Gas Control SystemDelay Timer Mode Shut Off ProcedureTransmitter Operation Off Mode On Manual ModeDisable Thermostat Function Auto ModeFan Override During Auto Mode Change Between F/C Temperature UnitsLocal Path On Path Auto Path Burner Orifice Conversion Conversion PrecautionsConversion Procedure Fuel Conversion InstructionsPilot type 2 Honeywell Pilot SIT 820 ValvePilot Orifice Conversion Pilot Type 1 SIT PilotAll Models Models 3352, 3354, 3390 thru 3399 RF Models OnlyConversion to LP Input BTU/h Air Shutter AdjustmentInjector Orifice Size Matrix Conversion to Natural Gas Input BTU/hMaintenance Check the Gas Flame Regularly Gasket ReplacementInspect the Vent System Annually BLK Wiring DiagramsDescription Radiance Direct Vent/Natural Vent Gas Heater RdvodRadiance Direct Vent/Natural Vent Gas Heater Rdvod Shell Enamel Parts Radiance Direct Vent / Natural Vent Fuel Conversion KitsOptional Accessories Radiance Direct Vent /Natural Vent Gas Heater 4242 Limited Lifetime Warranty Model EnerGuide Ratings Fireplace Efficiency % Efficiency Ratings