Radiance Direct Vent/Natural Vent Gas Heater
Parallel Installation: Minimum Clearance
and Flue Centerline, Direct Vent and Natu-
ral Vent
42" (1070mm)
Min. Alcove Width
4" (102mm)
48"
(1220mm) Max. Alcove Depth
|
|
| 6" |
|
|
| 6" |
|
|
|
|
|
|
| |||||
ST130 |
| (150mm) |
|
|
| (150mm) |
Fig. 3 Parallel installation, minimum back and side clear- ances, and flue centerlines.
Corner Installation: Minimum Clearance and Flue Centerline, Direct Vent & Natural Vent
18"
(457mm)
6"
�(150mm)
�
18"
(457mm)
�
�
6"
(150mm)
ST129
Fig. 4 Corner installation, minimum corner clearances and flue centerline.
Wall Centerline from Floor
Direct Vent Only
A
ST131b
A
Effective Minimum
Centerline 57” (1448 mm) (CFM Corporation Pipe) 55” (1399 mm) (Simpson DuraVent Pipe)
Fig. 5 Minimum wall centerline.
Wall and Ceiling Clearances
Direct Vent Only |
|
|
|
| D |
|
|
|
| ||
|
|
|
|
|
|
B
C
A
A: Rear Wall | 4” (102 mm) | |
B: Min. Clearance | 44” (1118 mm)* | |
C: Min. Alcove Height | 72” | (1830 mm)* |
D: Max. Alcove Depth | 48” | (1220 mm) |
Sidewall Clearance | 6” (150 mm) |
*needed for installing DuraVent Minimum Vent Kit #2792 or
CFM Corporation Minimum Vent Kit #7TFSMSK. | ST101b |
|
Fig. 6 Dimensions and clearances to ceiling or alcove.
Hearth Requirements
The Radiance Heaters must be installed on rigid floor- ing. When the heater is installed directly on any com- bustible surface other than wood flooring, a metal or wood panel extending the full width and depth of the unit must be used as the hearth. There are no other hearth requirements.
66 | 20004188 |