Vermont Casting 3360, 3399 Gas Specifications, Gas Inlet and Manifold Pressures, High Elevations

Page 7

Gas Specifications

 

 

 

 

 

 

Max.

Min.

 

 

 

 

 

 

Input

Input

 

Model

Fuel

Gas Control

BTU/h

BTU/h

 

RDVODRN

Nat

 

Millivolt

35,000

25,000

 

RDVODRP

Prop

 

Millivolt

35,000

27,500

 

RDVODRFN

Nat

Comfort Control

35,000

25,000

 

RDVODRFP

Prop

Comfort Control

35,000

27,500

Weight: Fully assembled; 350 lbs.

 

 

 

 

 

 

 

Gas Inlet and Manifold Pressures

 

 

 

 

 

 

 

 

 

 

 

Natural

 

LP (Propane)

 

Inlet Minimum

 

5.5” w.c.

 

11.0” w.c.

 

Inlet Maximum

 

14.0” w.c.

 

14.0” w.c.

 

Manifold Pressure

 

3.5” w.c.

 

10” w.c.

 

 

 

 

 

 

 

 

Radiance Direct Vent/Natural Vent

Certified to:

ANSI Z21.88-2005 / CSA 2.33-2005

Vented Gas Fireplace Heaters

The installation of your Vermont Castings stove must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54 - latest edition, or CSA B149.1 Installation code. (EXCEPTION: Do not derate this appliance for altitude up to 4,500 feet (1,370m). Maintain the manifold pressure at 3.5” w.c. for Natural Gas and 10.0” w.c. for LP Gas.

High Elevations

Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level.

For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.

In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).

WARNING: Improper installation, adjust- ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.

Radiance Direct Vent /Natural Vent Gas Heater

Horizontal Termination -

Direct Vent ONLY

The vent must rise vertically a minimum of 24” (610mm) off the top of the unit, before the first elbow. The hori- zontal run may extend up to 20’ (6m) and include a vertical rise of up to 40’ (12m). (Fig. 7) Horizontal termi- nation must also meet the criteria shown in Figures 10 through 12.

Approved vent systems must terminate above and including the heavy line in Figure 7.

Two 45˚ elbows may be substituted for each single 90˚ elbow.

With a rise between 2’ - 5’, one 90˚ or two 45˚ elbows may be used.

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pipe.)

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

top

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

feet)(inRunVertical collarflueappliancetheto the

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

May

use

up

to

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

three 90°

Elbows

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

���

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

���

 

 

 

 

 

One

90°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Elbow

 

 

 

 

 

 

 

Unacceptable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Venting

Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

� � � � � � � � �� �� �� �� �� �� �� �� �� �� ��

Horizontal Run (in feet)

ST134a

Fig. 7 Horizontal vent termination window.

20004188

7

Image 7
Contents Radiance Direct Vent/Natural Vent Gas Heater Table Of Contents Installation & Operating Instructions Radiance dimensions Radiance Direct Vent/Natural Vent Stove DimensionsLocating The Stove Installation RequirementsClearance Requirements Wall and Ceiling Clearances Wall Centerline from FloorHearth Requirements Horizontal Termination Direct Vent only Gas SpecificationsGas Inlet and Manifold Pressures High ElevationsVertical Termination Direct Vent only Restictor Plate is used on Direct Vent installations onlyVent Termination Clearances Location of Vent Termination General Venting Information Termination Location Canadian Installations1 US Installations2Plate supplied with the stove is not used Venting Requirements Natural Vent OnlyApproved Vent System Components Venting Requirements and Options Direct Vent onlyUnpack and Assemble Legs Assembly ProceduresParts Bag Contents Tools RequiredRemove rear shroud Install the Optional FanAttach the Inner Vent Assembly to the stove Venting System Assembly Direct Vent General InformationInstall the Vent Adapter Pipe For Canadian installations The venting system mustInstall the Outer Adapter Pipe. Orient the verti Side Wall Termination AssemblyDiscard the inner starter pipe shipped with the log Measure the horizontal length Vent Termination Below Grade Vertical Through the Roof Vent AssemblyInstall firestops and attic insulation shield Venting System Assembly Natural Vent General InformationInstall Log Set Install the Vent PipeConnect the Gas Supply Line Install the left and right rear logs and the right logThermostat Connection optional Install ON/OFF SwitchInstall the Mesh and Grille Burner InformationYour First Fire Flame & Temperature AdjustmentFlame Characteristics OperationTo Turn Off Gas To Heater Lighting and Operating InstructionsSymptom Possible Causes Corrective Action Troubleshooting / Honeywell #8420 Gas Control SystemDelay Timer Mode Shut Off ProcedureTransmitter Operation Off Mode On Manual ModeDisable Thermostat Function Auto ModeFan Override During Auto Mode Change Between F/C Temperature UnitsLocal Path On Path Auto Path Burner Orifice Conversion Conversion PrecautionsConversion Procedure Fuel Conversion InstructionsPilot type 2 Honeywell Pilot SIT 820 ValvePilot Orifice Conversion Pilot Type 1 SIT PilotAll Models Models 3352, 3354, 3390 thru 3399 RF Models OnlyConversion to LP Input BTU/h Air Shutter AdjustmentInjector Orifice Size Matrix Conversion to Natural Gas Input BTU/hMaintenance Inspect the Vent System Annually Gasket ReplacementCheck the Gas Flame Regularly BLK Wiring DiagramsDescription Radiance Direct Vent/Natural Vent Gas Heater RdvodRadiance Direct Vent/Natural Vent Gas Heater Rdvod Shell Enamel Parts Radiance Direct Vent / Natural Vent Fuel Conversion KitsOptional Accessories Radiance Direct Vent /Natural Vent Gas Heater 4242 Limited Lifetime Warranty Model EnerGuide Ratings Fireplace Efficiency % Efficiency Ratings