Vermont Casting 3350 Burner Information, Install ON/OFF Switch, Thermostat Connection optional

Page 22

Radiance Direct Vent/Natural Vent Gas Heater

CAUTION

This appliance should only be connected by a qualified gas technician. Test to confirm manifold pressures as specified below.

The Radiance Heater and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

The Radiance Heater must be isolated from the gas supply piping system by closing its indi- vidual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig.

There must be a gas shutoff between the stove and the supply.

In order to connect Natural Gas, use a fitting with 1/2” NPT on the valve side and 1/2” natural gas supply line with an input of 35,000 BTUs at a manifold pressure of 3.5” between minimum inlet supply of 5.5” w.c. and maximum of 14.0” w.c.

In order to connect Propane, use a fitting with 1/2” NPT on the valve side and 1/2” propane gas sup- ply line with an input of 35,000 BTUs at a manifold pressure of 10.0” between a minimum inlet supply of 11.0” w.c. and maximum of 14.0” w.c.

Burner Information

The appliance must only use the gas specified on the rating plate, unless converted using a Vermont Castings Fuel Conversion Kit. To convert from LP to Natural Gas use Kit #000-5009. To convert from Natural Gas to LP use Kit #000-5010.

Conversion instructions are provided with each kit and beginning on Page 29 in this manual.

THIS APPLIANCE SHOULD BE CON- NECTED TO THE GAS SUPPLY ONLY BY A QUALIFIED GAS SERVICE TECHNICIAN. FOLLOW ALL LOCAL CODES.

THERE MUST BE A GAS SHUT-OFF BE- TWEEN THE STOVE AND THE SUPPLY.

In order to connect Natural Gas, use a fitting with 1/2” NPT on the valve side and 1/2” natural gas supply line with an input of 35,000 BTUs at a manifold pressure of 3.5” between minimum inlet supply of 5.5” w.c. and maximum of 14.0” w.c.

In order to connect Propane, use a fitting with 1/2” NPT on the valve side and 1/2” propane gas supply line with an input of 35,000 BTUs at a manifold pressure of 10.0” between a minimum inlet supply of 11.0” w.c. and maximum of 14.0” w.c.

Install ON/OFF Switch

The switch assembly parts are found in the parts bag.

1.Attach switch assembly to left rear side of stove shroud (when facing shroud) using two screws and existing holes in shroud. (Fig. 42)

2.Run wires down back of stove, under bottom of rear shroud to valve.

3.Attach wires to valve terminals. (Fig. 43)

Switch As-

semblyExisting Holes

Screws

ST315

 

Fig. 42 Attach switch assembly to rear shroud.

TPTH TP TH

PILOT

ADJ

ST228

Fig. 43 Attach switch wires to valve.

Thermostat Connection (optional)

Use only a thermostat rated for 500 - 750 millivolts.

Check the table below for the appropriate gauge ther- mostat wire to use for the length of lead required in your installation.

Thermostat

 

Wire / Gauge

Maximum Run

18

20 feet

16

20 - 40 feet

14

up to 60 feet

1.Install the wall thermostat in the desired location and run the wires to the stove location. Terminate these leads with 1/4” female connectors.

2.Connect the thermostat wires to the valve. (Fig. 43)

Install the Mesh and Grille

Place the mesh and grille on the top of the Radiance stove to complete assembly.

2222

20004188

Image 22
Contents Radiance Direct Vent/Natural Vent Gas Heater Table Of Contents Installation & Operating Instructions Radiance Direct Vent/Natural Vent Stove Dimensions Radiance dimensionsLocating The Stove Installation RequirementsClearance Requirements Wall and Ceiling Clearances Wall Centerline from FloorHearth Requirements High Elevations Gas SpecificationsGas Inlet and Manifold Pressures Horizontal Termination Direct Vent onlyVertical Termination Direct Vent only Restictor Plate is used on Direct Vent installations onlyVent Termination Clearances Location of Vent Termination Canadian Installations1 US Installations2 General Venting Information Termination LocationVenting Requirements Natural Vent Only Plate supplied with the stove is not usedVenting Requirements and Options Direct Vent only Approved Vent System ComponentsTools Required Assembly ProceduresParts Bag Contents Unpack and Assemble LegsInstall the Optional Fan Remove rear shroudFor Canadian installations The venting system must Venting System Assembly Direct Vent General InformationInstall the Vent Adapter Pipe Attach the Inner Vent Assembly to the stoveInstall the Outer Adapter Pipe. Orient the verti Side Wall Termination AssemblyDiscard the inner starter pipe shipped with the log Measure the horizontal length Vertical Through the Roof Vent Assembly Vent Termination Below GradeVenting System Assembly Natural Vent General Information Install firestops and attic insulation shieldInstall the Vent Pipe Install Log SetInstall the left and right rear logs and the right log Connect the Gas Supply LineBurner Information Install ON/OFF SwitchInstall the Mesh and Grille Thermostat Connection optionalOperation Flame & Temperature AdjustmentFlame Characteristics Your First FireLighting and Operating Instructions To Turn Off Gas To HeaterTroubleshooting / Honeywell #8420 Gas Control System Symptom Possible Causes Corrective ActionOn Manual Mode Shut Off ProcedureTransmitter Operation Off Mode Delay Timer ModeChange Between F/C Temperature Units Auto ModeFan Override During Auto Mode Disable Thermostat FunctionLocal Path On Path Auto Path Fuel Conversion Instructions Conversion PrecautionsConversion Procedure Burner Orifice ConversionPilot Type 1 SIT Pilot SIT 820 ValvePilot Orifice Conversion Pilot type 2 Honeywell PilotModels 3352, 3354, 3390 thru 3399 RF Models Only All ModelsConversion to Natural Gas Input BTU/h Air Shutter AdjustmentInjector Orifice Size Matrix Conversion to LP Input BTU/hMaintenance Inspect the Vent System Annually Gasket ReplacementCheck the Gas Flame Regularly Wiring Diagrams BLKRadiance Direct Vent/Natural Vent Gas Heater Rdvod DescriptionRadiance Direct Vent/Natural Vent Gas Heater Rdvod Fuel Conversion Kits Shell Enamel Parts Radiance Direct Vent / Natural VentOptional Accessories Radiance Direct Vent /Natural Vent Gas Heater 4242 Limited Lifetime Warranty Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency %