Vermont Casting 33XDV Below Grade Installations, Vertical Through-the-RoofApplication, 10009383

Page 20
Below Grade Installations

XDV Direct Vent Gas Fireplace

Below Grade Installations

When it is not possible to meet the required vent ter- minal clearances of 12” (305 mm) above grade level a snorkel kit is recommended. This allows installation depth of down to 7” (178 mm) below grade level. The 7” is measured from the center of the horizontal vent pipe as it penetrates through the wall.

Ensure the sidewall venting clearances are observed. If venting system is installed below ground, we recom- mend a window well with adequate and proper drainage to be installed around the termination.

If installing a snorkel, a minimum 24” (610 mm) vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is 36” (914 mm). This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24” (610 mm).

1.Establish vent hole through the wall. (Fig. 33)

2.Remove soil to a depth of approximately 16”

(406 mm) below base of snorkel. Install window well (not supplied). Refill hole with 12” (305 mm) of coarse gravel leaving a clearance of approximately 4” (102 mm) below snorkel. (Fig. 39)

3.Install vent system. See Page 18, Steps 2 through 5.

4.Ensure a watertight seal is made around the vent pipe coming through the wall.

5.Apply high temperature sealant caulking (supplied) around the 4” and 7” snorkel collars.

6.Slide the snorkel into the vent pipe and secure to the wall.

7.Level the soil to maintain a 4” (102 mm) clearance below snorkel. (Fig. 39)

Zero Clearance Sleeve

Screws

(if required)

 

 

7TDVSNORK

 

(Snorkel)

Firestop

 

Do not backfill around snorkel.

A clearance of at lest 4” must be main- tained between the snorkel and the soil.

If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fas- ten brackets to wall first, then secure to snorkel with self drilling #8 x 1/2 sheet metal screws. It will be necessary to extend vent pipes out as far as the protruding wall face. (Fig. 40)

 

Snorkel

Foundation

 

Recess

 

 

Wall Screws

Watertight Seal

Sheet Metal

Around Pipe

Screws

BG401

Fig. 40 Snorkel installation, recessed foundation.

Vertical Through-the-Roof Application

This gas fireplace has been approved for:

Vertical installations up to 40’ (12 m) in height. Up to a 10’ (3 m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. (Fig. 41)

Up to two 45° elbows may be used within the hori- zontal run. For each 45° elbow used on the horizon- tal plane, the maximum horizontal length must be reduced by 18” (450 mm).

Example: Maximum horizontal length:

No elbows

=

10’ (3 m)

1 x 45° elbow

=

8.5’ (2.6 m)

7” Pipe

24” (610 mm )

Minimum *

4” Clear- ance Min.

Window

Well

Do not backfill around snorkel. Gravel

Vertical Through-the-Roof Application Drain

Manual background Foundation Wall

*A minimum of 24” (610 mm) vertical pipe must be installed when using the 7TDVSNORK.

2 x 45° elbows = 7’ (2.1 m)

A minimum of an 8’ (2.5m) vertical rise is required.

Two sets of 45° elbow offsets may be used within the

vertical sections. From 0 to a maximum of 8’ (2.5 m)

of vent pipe can be used between elbows. (Fig. 42)

7DVCS supports offsets. (Fig. 44) This application

will require that you first determine the roof pitch

and use the appropriate starter kit. (Refer to Venting

Components List)

The maximum angular variation allowed in the sys-

tem is 270°. (Fig. 42)

The minimum height of the vent above the highest

BG402a

Fig. 39 Below grade installation.

point of penetration through the roof is 2’ (610 mm).

(Fig. 45) Refer to note 2, Page 15.

20

10009383

Image 20
Contents Direct Vent Models: 33XDV, 36XDV, 39XDV Installation Instructions and Homeowner’s ManualINSTALLER/CONSUMER SAFETY INFORMATION Table of Contents XDV Direct Vent Gas FireplaceInstallation & Operating Instructions MaintenanceInstallation & Operating Instructions Locating Your FireplaceXDV Direct Vent Gas Fireplace 10009383XDV Fireplace Dimensions - Installed as Rear Vent Framing DimensionsXDV Direct Vent Gas Fireplace 33XDVXDV Fireplace Dimensions - Installed as Top Vent Framing DimensionsXDV Direct Vent Gas Fireplace 33XDVClearance to Combustibles MantelsHearth Cold climate installation recommendationGas Line Installation Framing and FinishingFinal Finishing Gas SpecificationsRemote ON/OFF Switch Alternate Switch LocationEB-1Electrical Box XDV Direct Vent Gas Fireplace10009383 Electronic Gas Control ValveXDV Direct Vent Gas Fireplace 10009383 Optional Top Vent ApplicationXDV Direct Vent Gas Fireplace General Venting Top Vent Application Restrictor Plate33XDV Restrictor Plate Installation 36XDV Restrictor Plate InstallationCanadian Installations1 US Installations2XDV Direct Vent Gas Fireplace 10009383General Information Assembling Vent Pipes Flex Vent PipesCanadian Installations USA InstallationsHow to Use the Vent Graph Twist Lock PipesRear Wall Venting Applications XDV Direct Vent Gas FireplaceRear Wall Installation Twist Lock Pipe XDV Direct Vent Gas FireplaceSTEP STEPRear Wall Vent Installations Flex Vent Pipe Vertical Sidewall ApplicationsXDV Direct Vent Gas Fireplace Step10009383 XDV Direct Vent Gas FireplaceTotal angular variation = Vertical Sidewall Installation Twist Lock Pipe XDV Direct Vent Gas FireplaceSTEP STEPVertical Sidewall Installation Flex Vent Pipe XDV Direct Vent Gas FireplaceSTEP STEPBelow Grade Installations Vertical Through-the-RoofApplicationXDV Direct Vent Gas Fireplace Do not backfill around snorkel10009383 Vertical Through-the-RoofInstallationXDV Direct Vent Gas Fireplace XDV Direct Vent Gas Fireplace 10009383Typical Roof SupportTypical Ceiling ApplicationSupport ApplicationVenting Components XDV Direct Vent Gas FireplaceWindow Frame Assembly Removal Glass CleaningReplacement Of Ceramic Hearth Panels Operating InstructionsInstallation of Logs Log Identification Chart33XDV XDV Direct Vent Gas Fireplace10009383 36XDVXDV Direct Vent Gas Fireplace Log Center Right B153 XDV Direct Vent Gas Fireplace10009383 10009383 39XDVXDV Direct Vent Gas Fireplace XDV Direct Vent Gas Fireplace 10009383Burner Lava Rock Placement Flame & Temperature AdjustmentFlame Characteristics Large Lava RockXDV Direct Vent Gas Fireplace 33XDV36XDV 39XDVFOR YOUR SAFETY READ BEFORE LIGHTING Lighting and Operating InstructionsLighting Instructions To Turn Off Gas To HeaterFor Your Safety, Read the Following Warnings Lighting & Operating Instructionsbefore Lighting the Appliance Lighting InstructionsShut Off Procedure Instructions for RF Comfort Control ValveOperation Transmitter Operation Off ModeDelay Timer Mode Disable Thermostat FunctionTroubleshooting Auto ModeService Action XDV Direct Vent Gas FireplaceLED Count Replace valveXDV Direct Vent Gas Fireplace On PathLocal Path 10009383Troubleshooting the Gas Control System SYMPTOMXDV Direct Vent Gas Fireplace POSSIBLE CAUSESTroubleshooting the Gas Control System XDV Direct Vent Gas FireplaceNormal Operation Abnormal OperationXDV Direct Vent Gas Fireplace Honeywell ValveBurner Orifice Conversion 33/36XDV NOVA SIT820 ValveBurner Orifice Conversion 39XDV XDV Direct Vent Gas FireplacePilot Orifice Conversion 10009383Fuel Conversion Instructions Honeywell Comfort Control Valve ONLYInstallation Precautions Conversion Procedure39XDV XDV Direct Vent Gas FireplacePilot Orifice Conversion 10009383Table 1 Injector Orifice Size Matrix XDV Direct Vent Gas FireplaceConversion to Natural Gas Burner OrificeMaintenance Cleaning the Standing Pilot Control Systemfireplace has been in use. FK24/FK12 Fan Assembly XDV Direct Vent Gas Fireplace10009383 33XDV/36XDV/39XDVXDV Direct Vent Gas Fireplace 33XDV/36XDV/39XDV continued XDV Direct Vent Gas FireplaceDescription 33XDV33XDV/36XDV/39XDV continued XDV Direct Vent Gas FireplaceDescription 33XDVOptional Accessories Available Hard Direct Wire Hook UpFan Kits Turn off all power before hook upRemote Controls Ceramic Refractory PanelsInstallation Instructions XDV Direct Vent Gas FireplaceOptional Trim Kits Screen Door KitFiligree Louvre Kit Arch/Square Face KitXDV Direct Vent Gas Fireplace 10009383XDV Direct Vent Gas Fireplace 10009383XDV Direct Vent Gas Fireplace 10009383LIMITED LIFETIME WARRANTY PRODUCT COVERED BY THIS WARRANTYIF WARRANTY SERVICE IS NEEDED… 2DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELFEfficiency Ratings CFM CorporationModel EnerGuide Ratings