CFM Corporation DVT44IN, DVT38IN Chateau, Termination Clearances, 20011956

Page 16
Termination Clearances

Chateau™

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

Inside Corner

Outside Corner

Alcove Applications*

 

 

 

F =

 

 

G =

 

Combustible

G

Combustible

 

6"

(152 mm)

 

6" (152 mm)

V

Noncombustible

 

 

2"

(51 mm)

 

Noncombustible

 

V

 

F

 

2" (51 mm)

 

 

Balcony -

Balcony -

with no side wall

with perpendicular side wall

M

M

 

V

V

 

P

M =

Combustible &

Noncombustible

Combustible &

M = 24" (610 mm)

Noncombustible

P = 20” (508 mm)

12" (305 mm)

Manual backgroundManual background D Manual backgroundManual background

C C

V

Manual backgroundManual background E Manual background

O

E = Min. 6” (152 mm) for non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls

O = 8’ (2.4 m) Min.

No.

 

 

of Caps

DMin.

CMax.

1

3’ (914 mm)

2 x DActual

2

6’ (1.8 m)

1 x DActual

3

9’ (2.7 m)

2/3 x DActual

4

12’ (3.7 m)

1/2 x DActual

DMin. = # of Termination caps x 3

CMax. = (2 / # termination caps) x DActual

584-15

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.

Fig. 13 Termination clearances.

Quick Reference for Fresh Air Restrictor Plate / Flue Baffle

Application

Item

DVT38N

DVT38P

DVT44N

DVT44P

SK8DVSK

Flue Restrictor Plate

3”

None

None

4¹⁄

 

Fresh Air Restrictor Plate

None

None

None

#1

Vertical Less than 12’

Flue Restrictor Plate

None

None

None

None

 

Fresh Air Restrictor Plate

None

None

None

None

Vertical 12’ to 20’

Flue Restrictor Plate

4¹⁄

4¹⁄

4¹⁄

4¹⁄

 

Fresh Air Restrictor Plate

#3

#3

#3

#3

Vertical 20’ to 30’

Flue Restrictor Plate

4¹⁄

4¹⁄

4¹⁄

4¹⁄

 

Fresh Air Restrictor Plate

#2

#2

#2

#2

Vertical 30’ to 40’

Flue Restrictor Plate

4¹⁄

4¹⁄

4¹⁄” or 6³⁄

4¹⁄” or 6³⁄

 

Fresh Air Restrictor Plate

#1

#1

#1

#1

NOTE: Refer to Page 22, Figure 35 for instructions to fabricate 3” and 4¹⁄” flue restrictor plates.

16

20011956

Image 16
Contents Installation Instructions and Homeowner’s Manual Model: DVT38IN, DVT44ININSTALLER/CONSUMER SAFETY INFORMATION ChateauChateau Table of Contents20011956 Installation & Operating Instructions ChateauDVT38IN / DVT44IN Certified To 20011956Fireplace Dimensions - DVT38IN Fireplace Dimensions - DVT44INChateau 20011956Chateau Locating Your FireplaceClearance to Combustibles MantelsHearth Framing and FinishingFinal Finishing ChateauGas Line Installation Gas SpecificationsGas Inlet and Manifold Pressures High ElevationsControl System Installation Electrical Junction BoxControl System ChateauChateau Special Feature for Cold Climates20011956 Remote Control Transmitter Operating Instructions ON H/LMODE ChateauSetting F / C Scale Setting Desired Room TemperatureChateau Manual FunctionCONTINUOUS PILOT FEATURE CP CHILDPROOF FEATURESETTING “LOCK-OUT”- CP ChateauThermostatic Updating Feature ChateauOperational Notes 20011956General Venting ChateauLocation of Vent Termination 20011956Canadian Installations1 US Installations2Chateau 18” 458 mm for non-vinylsoffitsTermination Clearances Chateau20011956 General Information Assembling Vent Pipes SK8 Venting PipesHorizontal Termination Vertical TerminationSidewall Applications Use of the Restrictor Plates inHorizontal Venting Applications ChateauSidewall Installation ChateauSTEP STEPSTEP Chateau20011956 Vertical Through-the-Roof Applications Use of Restrictor Platefor Vertical Venting Applications ChateauChateau Vertical Through-the-RoofInstallation20011956 Attic Installation Ceiling InstallationChateau Min 2 610mmChimney Components ChateauComponent DescriptionGlass Frame Assembly Removal Glass CleaningRestrictor Plate Installation Operating InstructionsCeramic Refractory Installation ChateauAppliance Kit ModelLog, Lava Rock and Ember Placement ChateauDVT38IN Logs 20011956DVT44IN Logs Chateau20011956 9.Position the Log Rear Left Chateau20011956 12. Position the Log Front Middle Right Chateau20011956 Chateau 20011956Fig. 48 DVT38IN logset complete Fig. 49 DVT44IN logset completeFlame Characteristics ChateauDVT38 DVT44Trim Installation Chateau20011956 Fig. 53 Trim frame in placeFor Your Safety, Read the Following Warnings Lighting & Operating Instructionsbefore Lighting the Appliance Lighting InstructionsTroubleshooting ChateauAmerican Flame Gas Control System 20011956Main flame will not light Chateau20011956 American Flame Gas Control System Error Codes ChateauWhat to Check What to CheckConversion Precautions Conversion ProcedureFuel Conversion Instructions ChateauConverting the Gas Control Valve Chateau20011956 Table 2 Air Shutter Settings Pilot Flame AdjustmentTable Injector Orifice Size MatrixMaintenance Cleaning the Control SystemChateau 20011956DVT38IN, DVT44IN For Units GFYN5Q0, GFYN500Chateau 20011956DVT38IN, DVT44IN continued ChateauDescription DVT38INDVT38IN, DVT44IN continued ChateauDescription DVT38INAccessories Back-upBattery KitCeramic Refractory Kits ChateauChateau 20011956LIMITED LIFETIME WARRANTY IF WARRANTY SERVICE IS NEEDEDLIMITED LIFETIME WARRANTY BASIC ONE-YEARWARRANTYEfficiency Ratings CFM Corporation