CFM Corporation DVT44IN Sidewall Applications, Use of the Restrictor Plates in, Chateau, 20011956

Page 18
Sidewall Applications

Chateau™

Vertical Run (in feet) (Measured from the appliance flue collar to the top of the vent pipe.)

May use one (1) elbow only

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

May use up to

��

three (3) 90°

elbows, but must

 

��not have two (2)

��consecutive 90°

��elbows in horizon-

��tal plane

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

��

 

 

 

 

 

 

���

 

���

Unacceptable vent-

 

ing configuration

 

 

� �

� � � � � � � �� �� �� �� �� �� �� �� �� �� ��

Minimum clearance between vent pipes and combustible materials is 3¹⁄” (89 mm) on top, 2¹⁄” (64 mm) on both sides and 1¹⁄” (38 mm) on the bottom.

When the vent termination exits through foundations less than 20” (508 mm) below siding outcrop, the vent pipe must be flush with the siding.

It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length of vent pipe from the flue collar of the fire- place to the face of the outer wall.

Horizontal plane means no vertical rise exists on this portion of the vent assembly.

 

20’ (6 m)

 

 

Unitized Elbow

 

 

 

(SK890)

 

 

 

 

 

Pipe

 

 

 

Straps

(4.3m)

 

 

Every 3’

Pipe Straps

(914 mm)

 

Every 3’ (914

 

14’

 

mm)

Firestop/Zero

 

 

Clearance Sleeve

 

Minimum 2’ (610

 

 

mm) Section

 

 

NOTE: Apply high temperature sealant or UL approved high temperature metal adhesive tape as directed on Page

12.

FP1012a

Fig. 16 Support straps for horizontal runs.

The maximum number of 90° elbows per side wall

installation is three (3), but must not have two (2)

consecutive elbows in the horizontal plane.

Horizontal Run (in feet)

FP1359

Fig. 15 Horizontal vent termination window.

Sidewall Applications

Since it is very important that the vent- ing system maintain its balance between

the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

NOTE: The penetration to the outside of the build- ing or structure shall be sealed air and weather tight.

Use of the Restrictor Plates in

Horizontal Venting Applications

The primary purpose for the vent restrictor plate is to regain flame height under certain venting conditions as outlined below.

The DVT38IN is shipped with the fresh air plate set- tings at #4 (this applies to both natural gas and propane) when using the horizontal starter vent kit SK8DVSK.

A minimum of 2’ (610 mm) vertical section off the top

of the unit is required, an elbow and a 1’ (305 mm)

maximum horizontal run to get through a wall. (Fig.

17)

2'

(610mm)

C Wall Opening

L

2'

(610mm)

X

(DVT44) X = 7’3¹⁄” (2216 mm)

(DVT38) X = 6’9⁷⁄” (2080 mm)

FP1237a

Fig. 17 Minimum vertical run / maximum horizontal run.

18

20011956

Image 18
Contents INSTALLER/CONSUMER SAFETY INFORMATION Installation Instructions and Homeowner’s ManualModel: DVT38IN, DVT44IN ChateauTable of Contents Chateau20011956 DVT38IN / DVT44IN Certified To Installation & Operating InstructionsChateau 20011956Chateau Fireplace Dimensions - DVT38INFireplace Dimensions - DVT44IN 20011956Clearance to Combustibles ChateauLocating Your Fireplace MantelsFinal Finishing HearthFraming and Finishing ChateauGas Inlet and Manifold Pressures Gas Line InstallationGas Specifications High ElevationsControl System Control System InstallationElectrical Junction Box ChateauSpecial Feature for Cold Climates Chateau20011956 MODE Remote Control Transmitter Operating InstructionsON H/L ChateauChateau Setting F / C ScaleSetting Desired Room Temperature Manual FunctionSETTING “LOCK-OUT”- CP CONTINUOUS PILOT FEATURECP CHILDPROOF FEATURE ChateauOperational Notes Thermostatic Updating FeatureChateau 20011956Location of Vent Termination General VentingChateau 20011956Chateau Canadian Installations1US Installations2 18” 458 mm for non-vinylsoffitsChateau Termination Clearances20011956 Horizontal Termination General Information Assembling Vent PipesSK8 Venting Pipes Vertical TerminationHorizontal Venting Applications Sidewall ApplicationsUse of the Restrictor Plates in ChateauSTEP Sidewall InstallationChateau STEPChateau STEP20011956 for Vertical Venting Applications Vertical Through-the-Roof ApplicationsUse of Restrictor Plate ChateauVertical Through-the-RoofInstallation Chateau20011956 Chateau Attic InstallationCeiling Installation Min 2 610mmComponent Chimney ComponentsChateau DescriptionRestrictor Plate Installation Glass Frame Assembly RemovalGlass Cleaning Operating InstructionsAppliance Ceramic Refractory InstallationChateau Kit ModelDVT38IN Logs Log, Lava Rock and Ember PlacementChateau 20011956Chateau DVT44IN Logs20011956 Chateau 9.Position the Log Rear Left20011956 Chateau 12. Position the Log Front Middle Right20011956 Fig. 48 DVT38IN logset complete Chateau20011956 Fig. 49 DVT44IN logset completeDVT38 Flame CharacteristicsChateau DVT4420011956 Trim InstallationChateau Fig. 53 Trim frame in placebefore Lighting the Appliance For Your Safety, Read the Following WarningsLighting & Operating Instructions Lighting InstructionsAmerican Flame Gas Control System TroubleshootingChateau 20011956Chateau Main flame will not light20011956 What to Check American Flame Gas Control System Error CodesChateau What to CheckFuel Conversion Instructions Conversion PrecautionsConversion Procedure ChateauChateau Converting the Gas Control Valve20011956 Table Table 2 Air Shutter SettingsPilot Flame Adjustment Injector Orifice Size MatrixChateau MaintenanceCleaning the Control System 20011956Chateau DVT38IN, DVT44INFor Units GFYN5Q0, GFYN500 20011956Description DVT38IN, DVT44IN continuedChateau DVT38INDescription DVT38IN, DVT44IN continuedChateau DVT38INCeramic Refractory Kits AccessoriesBack-upBattery Kit ChateauChateau 20011956LIMITED LIFETIME WARRANTY LIMITED LIFETIME WARRANTYIF WARRANTY SERVICE IS NEEDED BASIC ONE-YEARWARRANTYEfficiency Ratings CFM Corporation