Regency F39-NG DURA-FLUE Vertical Termination, Hole previously drilled in the ceiling, and mark

Page 14
Diagram 8

INSTALLATION

Diagram 6

8)Slide the decorative wall thimble up to the wall surface being careful not to scratch the paint and attach with screws provided. Apply decorative brass or chrome trim if desired. See diagram 7.

Diagram 7

Diagram 9

3)To install the Round Support Box/WallThim- ble in a fl at ceiling, cut a 10 inch square hole in the ceiling centred on the hole drilled in Step 2. Frame the hole as shown in diagram 10.

6)Continue to assemble pipe lengths.

Note: If an offset is necessary in the attic to avoid obstructions, it is important to support the flue pipe every 3 feet, to avoidexcessivestressontheelbows, and possible separation. Wall straps are available for this purpose. See diagram 7.

Galvanized pipe and elbows may be utilized in the attic as well as above the roofl ine. The galvanized fi nish is desirable above the roofl ine due to its higher corrosion resist- ance.

Continue to add pipe sections through the flashing until the height of the flue cap meets the minimum height requirements specifi ed in diagram 12 or local codes. Note that for steep roof pitches, the vertical height must be increased. Apoor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the fl ue height may solve the problem.

DURA-FLUE VERTICAL

TERMINATION

1)Maintain the 1-1/4" clearances (air spaces) to combustibles

when passing through ceil- ings, walls, roofs, enclo- sures, attic rafter, or other nearby combustible surfaces. Do not pack air spaces with insulation. Check page 9 for the maximum vertical rise of the fl uing system and the maximum horizontal offset limitations.

2)Set the gas appliance in its desired location. Drop a

plumb bob down from the ceiling to the position of the appliance fl ue exit, and mark the location where

the fl ue will penetrate the ceiling. Drill a small hole

at his point. Next, drop a plumb bob from the roof to

the hole previously drilled in the ceiling, and mark the

spot where the fl ue will penetrate the roof. Determine if ceiling joists, roof rafters or other framing will obstruct the fluing system. You may wish to relocate the appliance or to offset, as shown in diagram 9 to avoid cutting load bearing members.

Diagram 10

4)Assemble the desired lengths of black pipe and elbows necessary to reach from the appliance adaptor up though the Round Support Box. Insure that all pipes and elbow connections are in the fully twist-locked position and sealed.

5)Cut a hole in the roof centred on the small drilled hole placed in the roof in Step 2. The hole should be of suffi cient size to meet the minimum requirements for clearance to combustibles of 1-1/4". Slip the fl ashing under the shingles (shingles should overlap half the fl ashing) as per diagram 11.

Diagram 11: The upper half of the fl ashing is installed under the roofi ng material and not nailed down until the chimney is installed. This allows for small adjustments.

Diagram 12

Roof Pitch

Minimum Flue Height

 

Feet

 

Meters

 

 

 

fl at to 7/12

2

 

 

 

0.61

 

 

 

 

over 7/12 to 8/12

2

 

0.61

 

over 8/12 to 9/12

2

 

0.61

 

over 9/12 to 10/12

2.5

 

0.76

 

over 10/12 to 11/12

3.25

 

0.99

 

over 11/12 to 12/12

4

 

1.22

 

over 12/12 to 14/12

5

 

1.52

 

over 14/12 to 16/12

6

 

1.83

 

over 16/12 to 18/12

7

 

2.13

 

over 18/12 to 20/12

7.5

 

2.29

 

 

 

 

 

 

7)Ensure fl ue is vertical and secure the base of the fl ashing to the roof with roofi ng rails, slide storm collar over the pipe section and seal with a mastic.

8)Install the vertical termination cap by twist locking it.

Notes:

a)For multistorey vertical installations, a Ceiling Fire stop (Part # 963) is required at the second floor, and any subsequent fl oor. Diagram 13. The opening should be framed to 10 " x 10" inside dimen-

14

Regency® F39 Room Sealed Freestanding Gas Stove

Image 14
Contents Please Keep These Instructions For Future Reference 05/18/06Unit Specifications Regency F39 Room Sealed Freestanding Gas StoveTable of Contents Safety Label General Safety Information InstallationSpecifications Before YOU StartLocating Your Regency GAS Stove Installation ChecklistClearances to Combustibles Safety Precautions For the Installer Louver InstallationInstallation Precautions Flueing IntroductionSpace Heaters Exterior Flue Termination LocationsClearance k in mm Flue Restrictor Position Fluing ArrangementsHorizontal Terminations for All Fluing Systems Qty. Description DV Stove Horizontal Flue KIT # 946-112 InstallationDV Stove Horizontal Flue KIT OptionalInstallation DURA-FLUE Termination KIT Planning Your Dura-Flue InstallationMinimum components for a Dura-Flue Horizontal Installation DURA-FLUE Fluing ComponentsPipe and elbows to the ap- pliance adaptor with DURA-FLUE Horizontal Installations988 Wall Strap 942 Wall Thimble View as possible.DURA-FLUE Vertical Termination Hole previously drilled in the ceiling, and markGAS Connection GAS Pipe Pressure TestingOffset Chart Cathedral CeilingsSystem Data F39 with 40mj Aeration AdjustmentValve Description System DataConversion KIT #731-968 from NG to LPG Conversion Kit Contains Qty DescriptionLOG SET Installation Conversion to Lower BTU RatingPlace Front Left Log C02-44 onto Place the Middle Left Log B02-56 on the two pins as shownPlace Front Right Log E02-45 on the two pins as shown Optional Wall Thermostat Front Door InstallationOptional Remote Control Final CheckWiring Operating Instructions Copy of the Lighting Plate Instructions Normal Operating Sounds of GAS AppliancesGeneral Flue Maintenance MaintenanceMaintenance Instructions GOLD-PLATED DoorsGlass Replacement LOG ReplacementLatch Adjustment Door GasketTo remove F39 fan FAN MaintenanceAlternate Fan Access Replacing F39 FanRemoving Valve Description Parts ListF39 Main Assembly Part# DescriptionF39 Burner & LOG Assembly 940-323/P Side Glass 650-920 Door Gasket KitCeramic Paper 936-243 Glass GasketWarranty Warranty Lifetime

F39-LPG, F39-NG specifications

The Regency F39-LPG and F39-NG are contemporary gas fireplaces that have garnered attention for their stylish design and advanced technology. These models cater to homeowners seeking an efficient and visually appealing heating solution. Designed with both function and aesthetics in mind, the F39 series stands out for its elegant linear design, making it suitable for a variety of interior styles.

One of the distinguishing features of the F39 series is its commitment to energy efficiency. Both the F39-LPG, which operates on liquid propane, and the F39-NG, which utilizes natural gas, have been engineered to deliver optimal heat output while consuming minimal fuel. This efficiency not only reduces energy costs but also minimizes environmental impact, aligning with modern sustainable living practices.

The F39 series boasts advanced venting technology, allowing for versatile installation options. This feature enables homeowners to select the perfect location for their fireplace without compromising aesthetic appeal or functionality. The unit can be vented either vertically or horizontally, providing flexibility in design while ensuring safe and effective operation.

In terms of control, the Regency F39 models come equipped with a user-friendly remote control option. This allows for convenient operation from across the room, making it easy to adjust flame height and heat settings to create the perfect ambiance. Moreover, the models can also be connected to smart home systems, enabling homeowners to integrate their fireplace into a broader heating management system.

Aesthetically, the F39 series offers customizable options, including various media and decorative elements. Homeowners can choose from traditional logs, contemporary glass, or pebbles, allowing each unit to reflect their personal style and complement their home’s decor. The large glass viewing area enhances the visual experience, showcasing the beautiful flame patterns that add warmth and character to any room.

Durability is also a significant aspect of the design, with high-quality materials that ensure longevity and performance. The F39-LPG and F39-NG are constructed to withstand the rigors of everyday use while maintaining their sleek appearance.

In summary, the Regency F39-LPG and F39-NG fireplaces represent a blend of efficiency, technology, and elegance. With their advanced features, customizable aesthetics, and environmentally friendly operation, these models are ideal for those looking to enhance their living spaces with both warmth and style. Whether for a modern home or a more traditional setting, the F39 series is designed to meet diverse heating needs while providing a stunning focal point in any room.