Page 15

INSTALLATION

VENTING ARRANGEMENTS

HORIZONTAL TERMINATION (FLEX)

Regency® Direct Vent System

These venting systems, in combination with the L900, have been tested and listed as a direct vent system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.

FPI Direct Vent (Flex) System Termination Kits include all the parts needed to install the L900 using a flexible vent.

INSTALLATION

FPI Kit #

Length

Contains:

#946-618

6 Feet

1)

8” fl exible liner (Kit length)

 

 

2)

5” fl exible liner (Kit length)

 

 

3)

spring spacers (3)

 

 

4)

thimble (2)

 

 

5)

AstroCap termination cap (1)

#946-616

10 Feet

6)

screws (12)

 

 

7)

tube of Mill Pac (1)

 

 

8)

plated screws (8)

 

 

9)

S.S. screws #8 x 1-1/2” drill point, (4)

 

 

10)

vinyl siding standoff

 

 

 

 

Vinyl Siding

Standoff

Wall Thimble

(Mandatory in all

Horizontal Terminations)

5” dia. flue pipe

 

8” dia.

spring spacer

Flue pipe

 

Vent Guard - if required*

(Part #946-506/P)

AstroCap XLTM

Termination Cap

(Part #946-623/P)

*A Vent Guard is required when the AstroCap is installed above grade at 7 feet or lower.

Notes:

1)Liner sections should be continuous without any joints or seams.

2)Only Flex pipe purchased from FPI may be used for Flex installations.

3)Horizontal vent must be supported every 3 feet.

4)Awallthimbleismandatoryforallhorizontalterminations due to high temperatures.

Regency® L900 Direct Vent Gas Fireplace

15

Image 15
Contents Libertytm L900 Gas Fireplace Information for MOBILE/MANUFACTURED Homes After First Sale Manufactured Mobile Home RequirementsTable of Contents Certified for / Certifiée pour Canada and U.S.A Safety LabelCopy of Safety Decal Listed Vented GAS Fireplace HeaterMA Code CO Detector RequirementsUnit Dimensions Important Message Save These Instructions InstallationGeneral Safety Information Installation ChecklistLocating Your GAS Fireplace Heat Release KITHearth Requirements Manufactured Mobile Home Additional RequirementsClearances Mantel LEG Clearances Mantel ClearancesDiagram Framing & FinishingMaterial Prior to Installation Unit AssemblyVent Restrictor Plate Venting IntroductionVent Restrictor Position Latch Location= Clearance to permanently closed window *min /30cm Exterior Vent Termination RequirementsVenting Arrangements Horizontal Termination FlexFPI Kit # Length Contains Basic Horizontal & Vertical Terminations Rigid Pipe Venting Systems58DVA-16AB 8 Rigid Pipe Cross Reference ChartL676 & L900 Direct Vent Fireplace Allowable Horizontal Terminations Vent Restrictor SettingHorizontal Venting with Two 2 90o Elbows Vertical Venting with Three 3 90o Elbows Allowable Vertical Terminations Unit Installation with Horizontal Termination Minimum Vent Unit Installation With Vertical TerminationThis allows for small adjustments DiagramAstrocap XL Unit InstallationSIT 825 Valve Description GAS LineL900-NG System Data L900-LP System DataHeat Shield Latch Location BACK-UP Battery InstallationHinge Door Heat Shield Power Module Power ModuleLP Conversion Kit Contains Qty Description Conversion KIT #546-969 from NG to LPUsing a flat head screw driver Pilot Shield HeatClip Heat Shield J9 Jumper Location Bracket Heat Shield Unplug the power sourceHinge Door Heat ShieldValve Tray Slightly Removed Modulating Coil WiresBottom Brick Panel Valve TrayJ9 Jumper Pilot ShieldClip Cable TieHandle with care. do not Force Into Position Brick Panel InstallationRight Side Brick Panel F t Side Brick Panel Back Brick PanelTop Brick Panel Outerbox of FireboxLOG SET Installation 03-4203-42 03-41 03-45 03-41 03-43 03-43Burner Tube 03-44Wiring Diagram Aeration AdjustmentOperating Instructions Lighting ProcedureOperating Instructions Matching Remote Handset & Control BOX ID CodeShutdown Procedure Operation During Power OutageNormal Operating Sounds GAS Appliances Copy of Lighting Plate Instructions STOP! Read the safety information above on this labelMaintenance BACK-UP Battery Replacement Heat ShieldBracket Hinge Heat Door Bracket Heat Shield Power Module ReplacementControl Module Replacement Bracket Hinge HeatControl Module DC Sparker Replacement Battery CoverHeat Shield Replace the DC sparker Unplug the power source Valve Tray ReplacementValve Tray WiresBottom Brick Panel Modulating Coil Valve Tray Slightly RemovedParts List Main AssemblyDescription Parts List Burner & LOG Assembly Regency L900 Direct Vent Gas Fireplace Regency L900 Direct Vent Gas Fireplace Regency L900 Direct Vent Gas Fireplace Warranty Limited Lifetime WarrantyInstaller Please complete the following information