Weil-McLain BMC Outdoor Cutoff Temperature, Offset, Minimum Water Temp, Maximum Water Temp

Page 18

BMC and BMC-6X Installation and Operation Manual

OUTDOOR CUTOFF TEMPERATURE

 

------- OUTDOOR CUTOFF -------

Adjustable Off, from 20ºF/ to70ºC - 100ºF, On

Default: 60ºF/ 16ºC

 

Button: MENU/Set Point/Outdoor Cutoff

in Set Point

65 F

Button: MENU/Set Point/Offset/Outdoor Cutoff

in Reset

[]

If the outdoor sensor is installed, the Outdoor Cutoff screen will automatically appear

after the temperature Set Point has been selected.

BACK

SAVE

When the outdoor temperature falls to the adjustable Outdoor Cutoff temperature, the BMC will control and modulate boilers to hold the calculated temperature.

When the outdoor temperature rises to the Outdoor Cutoff plus a 2°F differential, the BMC will turn all boilers off. The System relay will remain energized for the Run-On delay then de-energize.

The Outdoor Cutoff can be set from 20°F to 100°F. In addition, the Setting can be set to ON or OFF. In the ON position, the System Relay will run regardless of the Outdoor temperature (OD) and the burner stages will be active to hold the calculated water temperature. (Note: The lowest water temperature the BMC will circulate is 70°F. If the Outdoor Cutoff is turned ON and the Season is set to Winter, the BMC will circulate at least 70°F water even in the hottest of weather.) In the OFF position, the system pump will always be off and all burner stages will be off.

OFFSET

Default: 0Fº/0Cº

--------------

OFFSET -------------

Adjustable from 50Fº/28Cº to (-50Fº/-28Cº)

 

 

Button: MENU/Set Point/Offset

in Reset only

 

+0 F

• The Offset setting lets you adjust the starting points of the Reset Ratio curves. This

[]

 

means that, regardless of the Outdoor temperature (OD), or the Reset Ratio that has

 

 

been selected, when the Offset setting is changed, that change is directly added to or

BACK

SAVE

subtracted from the calculated temperature. For example, if the Set Point temperature

 

 

was 130°F and the Offset was changed from 0° to 10° (an increase of 10°), then the Set

 

 

Point temperature would increase to 140°F

 

 

 

The Offset setting does not change the ratio selection. For instance, with 1.00 (OD):1.00 (SYS) Reset Ratio, the System water temperature (SYS) will always increase one degree for each degree change in the Outdoor temperature (OD). What the Offset does is add or subtract a constant temperature value. (See Understanding Operation Concept on page 5)

If required: Adjust the Water Offset in mild weather. If the ambient building temperatures are too warm in the mild weather, decrease the Water Offset. If the ambient building temperatures are too cold in the mild weather, increase the Water Offset. The rule of thumb for baseboard radiation is to change the Offset 4°F for every 1°F you wish to change the building temperatures.

In radiant heat applications, change the Offset 1°F or 2°F for every 1°F you wish to change the building temperature.

---MINIMUMWATERTEMP----

MINIMUM WATER TEMP

Adjustable from 70ºF/21ºC to 180ºF/82ºC

Default: 140ºF/ 60ºC

70 F

Button: MENU/Set Point/Offset/Outdoor Cutoff/Minimum Water Temp

in Reset only

[]

 

The Minimum Water Temperature must be set to the boiler manufacturer’s specification.

The BMC will calculate the Set Point based on the Outdoor temperature (OD), the Reset

BACK

SAVE

 

 

Ratio, and the Offset value. The BMC will control all boilers modulation to

 

 

hold either the Set Point temperature, or the Minimum Water Temperature, whichever is higher.

 

 

The Minimum Water Temperature must be at least 20°F lower than the Maximum Temperature (See next setting).

MAXIMUM WATER TEMP

Adjustable 90ºF/21ºC - 240ºF/116ºC

Default: 200ºF/93ºC

Button: MENU/Set Point/Offset/..../Maximum Water Temperature

in Reset only

This is the highest temperature heating water the BMC will circulate through the heating system. It is available in Reset mode only.

When using a radiation system, it should be set according to the tubing or floor manufacturer’s specification.

The Maximum Temperature must be at least 20°F higher than the Minimum Temperature (See previous setting).

---MAXIMUMWATERTEMP----

 

240 F

[]

 

BACK

SAVE

18

Image 18
Contents Installation and Operation Instructions Manual BMCContents BMC Layout Associated relay statusBMC Overview Reset RATIO/OUTDOOR Reset Understanding Operation ConceptInitial Setup Selecting the System FeaturesMake Sure YOU have the Right Control Installation Mounting the EnclosureInstall the Sensors Heating System Sensor HSS InstallationOutdoor Sensor Installation Wiring the Sensors WiringWiring the Power Terminals 1 Wiring the SHUTDOWN, TSTAT, or Setback Terminals 31Wiring the System Output Terminals 3 Wiring the Prove Terminals 29Wiring the Domestic HOT Water Call DHW Terminals 29 Wiring the BoilersWiring to Modulating Motors Connecting to the BMC-6X PanelsMenu Sequence 65 FSystem SETTINGS1 MaintenanceSystem SETTINGS2 Startup Settings Button MENU/System Startup/..../Boost Mode Boost Mode not Available with SetbackNormal, Parallel Default Normal PROVE/DOMESTIC HOT Water DHWButton MENU/System Startup/..../Sensor Fault Setting the Control to Factory DefaultsSensor Fault Reset ModeReset Ratio Operating SettingsSET Point not Adjustable in EMS Mode SeasonMinimum Water Temp Outdoor Cutoff TemperatureOffset Maximum Water TempGain System SettingsPurge Delay Lead Boiler RotationStandby Delay System RUN-ONSetback DAY/NIGHT Schedules Button MENU/System Settings/More Settings/Last Stg HoldLast Stage Hold Avoiding Conflicting Boiler LimitsHistory SET TimeButton MENU/Histories System & Outdoor Sensor Trim MaintenanceSOFT-OFF Delay Output TrimDisplay ConfigurationButton MENU/Maintenance/Configuration Display Boiler Modulation StatusDisplay Messages Boiler Stage SettingsMode Button StageModulation Start % Copy Settings Boiler a onlyIgnition % Button STAGE/Ignition %Troubleshooting Sensor InputsControl Operation Boilers are Short-Cycling Direct Heating Piping Diagram Multiple Modulating BoilersDirect Heating Wiring Diagram External 4-20MA SET Point Using 4-20MA EMS Interface Specifications BMC SpecificationsBMC-6X Specifications