BMC and
TROUBLESHOOTING
SENSOR INPUTS
Display shows Sensor OPEN or SHORT
When OPEN, Check the sensor is connected and the wires are continuous to the BMC. Finally follow the procedure for Incorrect Temperature or Pressure Display. When SHORT Remove the wires from the sensor terminals. The display should change to read OPEN. If it does not, the BMC may be damaged.
Display shows an Incorrect Temperature
Remove the wires from the sensor terminals. The display should change to read OPEN. If it does not, the BMC may be damaged. Take an ohm reading across the detached sensor wires. The ohm reading should correspond to the Temperature sensor Table. If it does not, the sensor may be damaged.
CONTROL OPERATION
No Heat
•Season - Make sure that the Season is set to Winter. Check Message Display Line on page 24.
•Prove - Even though, the system relay may be energized, the BMC will not energize and stage relays unless the Prove is shorted. Check Message Display Line on page 24.
•Shutdown - The BMC will activate stage outputs when the Shutdown terminals are short. Check Message Display Line on page 24.
•Tstat - The BMC will activate stage outputs when the Tstat terminals are open. Check Message Display Line on page 24.
•Sensor Fault - When the Sensor Fault is set to All Off in the startup menu (see page 16), the System sensor fault (in all Sensor Type modes) or the Outdoor sensor fault (in Reset mode) will
•System or Outdoor Sensor - If the System or Outdoor sensor reading was higher that the actual temperature, the BMC might not bring any stage on. Check "Display shows an Incorrect Temperature" section.
Too Much Heat
Check if the control has any of the following:
•Domestic Hot Water call - The BMC will raise the temperature of the system to either 200˚F or Maximum Water Temperature on a DHW call, connected to terminals 29 and 30. Check to see if there is a call for DHW and the length of time it lasts.
•Reset Ratio and Offset - If excessive heat occurs only in certain weather conditions, adjust the Reset Ratio and Offset (See Understanding Operating Concept on page 5). If excessive heat occurs year round, reduce the Offset.
•Boiler Mode Settings - The BMC will only modulate boilers their mode is set to Auto or Standby. Check to if any boiler stage is set to Manual or On. See Mode on page 25.
•Control Settings - The Last Stage Hold will allow only the Lead boiler to stay on for an additional number of degrees. If the setting is too high, and only the Lead boiler is on, the system can over heat. Reduce the Last Stage Hold setting. See page 21.
Too Little Heat
Check if the control has any of the following:
•Reset Ratio and Offset - If reduced heat occurs only in certain weather conditions, adjust the Reset Ratio and Offset (See Understanding Operating Concept on page 5). If reduced heat occurs year round, increase the Offset.
•Setback and Day/Night Schedule - If reduced heat occurs only during specific hours, check the Day/Night Schedule and the Setback values. Either reduce the Setback setting (See page 20).
Temperature Sensor Chart
TEMPERATURE | Value | |
°F | °C | (in Ohms) |
117720 | ||
|
|
|
82823 | ||
|
|
|
59076 | ||
|
|
|
0 | 42683 | |
|
|
|
10 | 31215 | |
20 | 23089 | |
|
|
|
25 | 19939 | |
30 | 17264 | |
|
|
|
35 | 2 | 14985 |
|
|
|
40 | 4 | 13040 |
|
|
|
45 | 7 | 11374 |
|
|
|
50 | 10 | 9944 |
55 | 13 | 8714 |
|
|
|
60 | 16 | 7653 |
70 | 21 | 5941 |
|
|
|
80 | 27 | 4649 |
|
|
|
90 | 32 | 3667 |
|
|
|
100 | 38 | 2914 |
|
|
|
110 | 43 | 2332 |
120 | 49 | 1879 |
|
|
|
130 | 54 | 1524 |
140 | 60 | 1243 |
|
|
|
150 | 66 | 1021 |
160 | 71 | 842 |
|
|
|
170 | 77 | 699 |
180 | 82 | 583 |
190 | 88 | 489 |
|
|
|
200 | 93 | 412 |
210 | 99 | 349 |
|
|
|
220 | 104 | 297 |
230 | 110 | 253 |
|
|
|
240 | 116 | 217 |
250 | 121 | 187 |
27