Weil-McLain BMC Setting the Control to Factory Defaults, Sensor Fault, Reset Mode, SET Point Mode

Page 16

BMC and BMC-6X Installation and Operation Manual

SENSOR FAULT

All Off, All On

Default: All On

Button: MENU/<System Startup>/..../Sensor Fault

 

The Sensor Fault will determine the operating status of all output stages that are set to Auto when a sensor reads Short or Open.

---------

SENSOR

FAULT --------

All

Off

 

All

On

 

BACK

SAVE

RESET MODE

When All-On is selected, the BMC will turn all boilers On to a 100% when System reads Short or Open and Outdoor is below Outdoor Cutoff. When Outdoor reads Short or Open, the BMC will turn all boilers On to a 100%.

When All-Off is selected, the BMC will turn all boilers Off when either System or Outdoor sensor reads Short or Open.

SET POINT MODE

When All-On is selected, the BMC will turn all boilers On to a 100% when the System sensor reads Short or Open.

When All-Off is selected, the BMC will turn all boilers Off when the System sensor reads Short or Open.

The Outdoor Sensor Short or Open status will not affect the control operation in Set Point mode.

SETTING THE CONTROL TO FACTORY DEFAULTS

To Reset the BMC control to its original factory defaults, power down the control. Hold down the two right most buttons while powering the control back up until the Total Clear Started screen appears. The Display will direct you to the Startup menu to program the control after the defaults are loaded.

TOTAL CLEAR STARTED

Release buttons

and

Please Wait

NOTE: When resetting the control to original factory defaults all control settings will be overwritten and will no longer exist.

ALERT

Do not turn off power to control until all Startup settings have been made. Otherwise, the next power-up will be set to many Startup factory settings that might not fit your application.

16

Image 16
Contents Installation and Operation Instructions Manual BMCContents BMC Layout Associated relay statusBMC Overview Reset RATIO/OUTDOOR Reset Understanding Operation ConceptSelecting the System Features Initial SetupMake Sure YOU have the Right Control Installation Mounting the EnclosureHeating System Sensor HSS Installation Install the SensorsOutdoor Sensor Installation Wiring Wiring the Power Terminals 1Wiring the Sensors Wiring the SHUTDOWN, TSTAT, or Setback Terminals 31Wiring the Prove Terminals 29 Wiring the Domestic HOT Water Call DHW Terminals 29Wiring the System Output Terminals 3 Wiring the BoilersWiring to Modulating Motors Connecting to the BMC-6X PanelsMenu Sequence 65 FMaintenance System SETTINGS1System SETTINGS2 Startup Settings Boost Mode not Available with Setback Normal, Parallel Default NormalButton MENU/System Startup/..../Boost Mode PROVE/DOMESTIC HOT Water DHWSetting the Control to Factory Defaults Sensor FaultButton MENU/System Startup/..../Sensor Fault Reset ModeOperating Settings SET Point not Adjustable in EMS ModeReset Ratio SeasonOutdoor Cutoff Temperature OffsetMinimum Water Temp Maximum Water TempSystem Settings Purge DelayGain Lead Boiler RotationSystem RUN-ON Standby DelaySetback Button MENU/System Settings/More Settings/Last Stg Hold Last Stage HoldDAY/NIGHT Schedules Avoiding Conflicting Boiler LimitsSET Time HistoryButton MENU/Histories Maintenance SOFT-OFF DelaySystem & Outdoor Sensor Trim Output TrimConfiguration Button MENU/Maintenance/ConfigurationDisplay Display Boiler Modulation StatusBoiler Stage Settings ModeDisplay Messages Button StageCopy Settings Boiler a only Ignition %Modulation Start % Button STAGE/Ignition %Sensor Inputs TroubleshootingControl Operation Boilers are Short-Cycling Direct Heating Piping Diagram Multiple Modulating BoilersDirect Heating Wiring Diagram External 4-20MA SET Point Using 4-20MA EMS Interface BMC Specifications SpecificationsBMC-6X Specifications