Weil-McLain BMC-6X Boiler Stage Settings, Display Messages, Button Stage, Button STAGE/Mode

Page 25

BMC and BMC-6X Installation and Operation Manual

DISPLAY MESSAGES

The BMC normal display layout reserved the second line for message indications. The following is a list of the most common Message Display Line information:

Summer

The control is set to Summer. No heat is active. See Season on page 17.

Shutdown Active

The Shutdown Terminals are Shorted. No boilers will be active. See Shutdown on pages 15 and 9.

Shutdown by EMS

The EMS is below 2mA or above 22mA. See EMS input and External Set Point pages 14 and 31.

Tstat Call

The Tstat Terminals are Shorted. Boilers will be active.

DHW Call (171˚F)

There is a DHW (Domestic Hot Water) call. The BMC will Raise system Set Point to the indicated

 

 

temperature. DHW increases calculated temperature to 200˚F or Max Water Temperature, whichever

 

 

is lower. See DHW setting on page 15.

Purge Delay: 23

The current boiler is in purge cycle and the remaining purge time in seconds is 23. See Purge Delay

 

 

on page 19.

Lag Delay: 123

The lead boiler is at 100% and the remaining purge time to start the lag boiler in seconds is 123. See

 

 

Lag Delay on page 20.

Holding Until 150˚F The Lead boiler is in Last Stage Hold. This example shows that the lead stage will turn off when system temperature reaches 150˚F. See Last Stage Hold on page 21.

System Run-On: 46 The System relay is ON for the System Run-On Delay. This example shows that it will remain in

 

 

System Run-On for an additional 46 seconds before turning off. See System Run-On on page 20.

Waiting for Prove

The System relay is ON and the prove terminals are open before the lead boiler relay can energize.

 

 

See Prove setting on page 15.

Prove Failure

After boilers have run for a while, Prove signal was opened. The boiler relays will de-energize.

 

 

However, the System relay will remain energized. See Prove setting on page 15.

BOILER STAGE SETTINGS

Button: STAGE/

The Maintenance menu gives access to sensor and outputs trimming and Soft-Off. In addition, you'll have access to view the Startup configuration settings.

In most installations, all active boiler adjustments are the same, but each can be configured differently if desired.

If the boilers are not set up properly, the BMC operation may appear to be erratic.

When the STAGE button is depressed, the Boiler A Settings menu will be shown.

Make all the appropriate settings for Boiler A (See below).

After completing all the settings for Boiler A (See below), you have the option of copying these settings to all other boilers. Everything but the Mode -- Auto/Standby/ Manual/Off/On -- will be copied.

Then select the Next Stage option from the menu to bring up the Boiler B Settings menu and make all the settings. Continue until all boilers have been set.

If a BMC-6X is connected to the BMC, scrolling through stages using the Next and Prev Stage menu options will scroll through the BMC-6X stages as well.

ALERT

To be able to change the BMC settings, the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a lock.

MODE

Auto, Standby, Manual, Off, On

Default: Auto

Button: STAGE/Mode

 

The BMC only controls the modulation of boilers set to Auto or (after a delay) those set to Standby. None of the other settings is recommended for output boilers connected to active units.

Any boiler without an active unit connected must be set to Off.

The following list describes the MODE options:

-----STAGEASETTINGS----

Mode

 

Off

Ignition %

1%

Mode

Start %

75%

<Prev

Stage>

 

<Next

Stage>

 

Copy

Settings

 

BACK

 

SELECT

CAUTION

Remember to set the Mode for each stage. For Stages that do not have a boiler, contractor must change their Mode to OFF. Otherwise the BMC will include them in the modulation calculation and rotation. That might have dire effects on system response.

PROGRAM RUN

-------STAGEAMODE--------

Auto

Standby

Manual

Off

On

BACKSAVE

25

Image 25
Contents BMC Installation and Operation Instructions ManualContents Associated relay status BMC LayoutBMC Overview Understanding Operation Concept Reset RATIO/OUTDOOR ResetSelecting the System Features Initial SetupMake Sure YOU have the Right Control Mounting the Enclosure InstallationHeating System Sensor HSS Installation Install the SensorsOutdoor Sensor Installation Wiring the Power Terminals 1 WiringWiring the Sensors Wiring the SHUTDOWN, TSTAT, or Setback Terminals 31Wiring the Domestic HOT Water Call DHW Terminals 29 Wiring the Prove Terminals 29Wiring the System Output Terminals 3 Wiring the BoilersConnecting to the BMC-6X Panels Wiring to Modulating Motors65 F Menu SequenceMaintenance System SETTINGS1System SETTINGS2 Startup Settings Normal, Parallel Default Normal Boost Mode not Available with SetbackButton MENU/System Startup/..../Boost Mode PROVE/DOMESTIC HOT Water DHWSensor Fault Setting the Control to Factory DefaultsButton MENU/System Startup/..../Sensor Fault Reset ModeSET Point not Adjustable in EMS Mode Operating SettingsReset Ratio SeasonOffset Outdoor Cutoff TemperatureMinimum Water Temp Maximum Water TempPurge Delay System SettingsGain Lead Boiler RotationSystem RUN-ON Standby DelaySetback Last Stage Hold Button MENU/System Settings/More Settings/Last Stg HoldDAY/NIGHT Schedules Avoiding Conflicting Boiler LimitsSET Time HistoryButton MENU/Histories SOFT-OFF Delay MaintenanceSystem & Outdoor Sensor Trim Output TrimButton MENU/Maintenance/Configuration ConfigurationDisplay Display Boiler Modulation StatusMode Boiler Stage SettingsDisplay Messages Button StageIgnition % Copy Settings Boiler a onlyModulation Start % Button STAGE/Ignition %Sensor Inputs TroubleshootingControl Operation Boilers are Short-Cycling Multiple Modulating Boilers Direct Heating Piping DiagramDirect Heating Wiring Diagram External 4-20MA SET Point Using 4-20MA EMS Interface BMC Specifications SpecificationsBMC-6X Specifications