Weil-McLain BMC-6X Maintenance, System & Outdoor Sensor Trim, SOFT-OFF Delay, Output Trim

Page 23

BMC and BMC-6X Installation and Operation Manual

MAINTENANCE

Button: MENU/<Maintenance>

The Maintenance menu gives access to sensor and outputs trimming and Soft-Off. In addition, you'll have access to view the Startup configuration settings.

ALERT

To be able to change the BMC settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a lock.

SYSTEM & OUTDOOR SENSOR TRIM

Adjustable from -5F°/-3C°to +5F°/+3C°

Default: 0°F

Button: MENU/<Maintenance>/System Trim

 

Button: MENU/<Maintenance>/Outdoor Trim

 

The Weil McLain thermistor type sensors are very accurate, and normally require no calibration. Sometimes it may be desirable to make small adjustments to the displayed value for either the Outdoor temperature (OD) or the System temperature (SYS). The Trim setting can adjust the displayed value by ± 5°F.

Do not use the Trim setting to make the Outdoor temperature sensor match that reported on the radio or TV. Outdoor temperature can vary widely over a broadcast range. Only trim the outdoor sensor based on an accurate thermometer reading taken where the sensor is located.

SOFT-OFF DELAY

Adjustable from 0sec to 60sec

Default: 45sec

Button: MENU/<Maintenance>/Soft-Off Delay

 

When a stage is no longer needed, the Soft-Off keeps that stage burner in Low Fire prior to turning it off.

The display will show a percent that is equal to the Ignition % for the stage in Soft-Off delay. That number will blink for the Soft-Off delay period.

If during the Soft-Off delay period the BMC needed that stage to turn back on, the stage will be released from the Soft-Off delay and resume normal operation.

On a Shutdown initiation or Tstat termination any stage that was on will go into Soft-Off delay before fully turning off.

----------

MAINTENANCE

---------

System

Trim

+0

F

Outdoor

Trim

+0

F

Soft-Off Delay

45sec

<Output

Trim>

 

 

<Configuration>

 

 

BACK

 

SELECT

PROGRAM

RUN

---SYSTEMSENSORTRIM----

 

+0 F

[]

 

BACK

SAVE

-- OUTDOOR SENSOR TRIM ----

 

+0 F

[]

 

BACK

SAVE

------- SOFT-OFF DELAY --------

 

45sec

[]

 

BACK

SAVE

ALERT

When using Soft-Off and Last Stage Hold, the last boiler stage will not turn off until both parameters have elapsed. In this case, Soft-Off will start after the Last Stage Hold has been reached or exceeded.

OUTPUT TRIM

Adjustable from -5 to +5

Default: 0

Button: MENU/<Maintenance>/Output Trim

 

Each of the stages controlled by the BMC has a separate Output Trim setting.

Output Trim acts as an adjustment to a stage output percent to match the burner motor.

After adjusting the Output Trim, test the operation to make sure the results match your expectation.

--------

STAGE A

TRIM --------

Output

Trim

+0.0

<Prev

Stage>

 

<Next

Stage>

 

BACK

 

SELECT

ALERT

DO NOT use the Output Trim for a Stage unless it is absolutely necessary. Test burner operation and modulation output matching after adjusting the Output Trim.

23

Image 23
Contents BMC Installation and Operation Instructions ManualContents Associated relay status BMC LayoutBMC Overview Understanding Operation Concept Reset RATIO/OUTDOOR ResetMake Sure YOU have the Right Control Initial SetupSelecting the System Features Mounting the Enclosure InstallationOutdoor Sensor Installation Install the SensorsHeating System Sensor HSS Installation Wiring the SHUTDOWN, TSTAT, or Setback Terminals 31 WiringWiring the Power Terminals 1 Wiring the SensorsWiring the Boilers Wiring the Prove Terminals 29Wiring the Domestic HOT Water Call DHW Terminals 29 Wiring the System Output Terminals 3Connecting to the BMC-6X Panels Wiring to Modulating Motors65 F Menu SequenceSystem SETTINGS2 System SETTINGS1Maintenance Startup Settings PROVE/DOMESTIC HOT Water DHW Boost Mode not Available with SetbackNormal, Parallel Default Normal Button MENU/System Startup/..../Boost ModeReset Mode Setting the Control to Factory DefaultsSensor Fault Button MENU/System Startup/..../Sensor FaultSeason Operating SettingsSET Point not Adjustable in EMS Mode Reset RatioMaximum Water Temp Outdoor Cutoff TemperatureOffset Minimum Water TempLead Boiler Rotation System SettingsPurge Delay GainSetback Standby DelaySystem RUN-ON Avoiding Conflicting Boiler Limits Button MENU/System Settings/More Settings/Last Stg HoldLast Stage Hold DAY/NIGHT SchedulesButton MENU/Histories HistorySET Time Output Trim MaintenanceSOFT-OFF Delay System & Outdoor Sensor TrimDisplay Boiler Modulation Status ConfigurationButton MENU/Maintenance/Configuration DisplayButton Stage Boiler Stage SettingsMode Display MessagesButton STAGE/Ignition % Copy Settings Boiler a onlyIgnition % Modulation Start %Control Operation TroubleshootingSensor Inputs Boilers are Short-Cycling Multiple Modulating Boilers Direct Heating Piping DiagramDirect Heating Wiring Diagram External 4-20MA SET Point Using 4-20MA EMS Interface BMC-6X Specifications SpecificationsBMC Specifications