Nortec Industries GS Series manual Servicing the Unit, Service Checks Combustion Blower, Burner

Page 35

The switch board must be replaced into the same position as before cleaning and the tie -wrap must be used to hold the float chamber in position.

SERVICING THE UNIT

Caution: Disconnect power before servicing this appliance.

Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

The combustion chamber, heat exchanger and flue baffles are all fabricated from stainless steel and do not require internal cleaning.

Should the main burner fail to light, or flame is not detected during the first trial for ignition period, the gas valve is de-energized and the control goes through an interpurge delay before another ignition attempt. The control will attempt two additional ignition trials before going into lockout. The valve relay will be de-energized immediately, and the combustion blower will be turned off.

SERVICE CHECKS

COMBUSTION BLOWER

The combustion air blower motors are permanently lubricated and do not require lubrication. Clean out any dust that has accumulated in the blower housing using an air gun.

BURNER

The burners are made of ceramic fabric material and operate in the infrared mode. Depending on the environment, the burner(s) may require removal of lint or grease-laden dust periodically. This may be achieved by removing the burner and applying pressurized air to the external surface of the material. Refer to the Servicing Section related to burner removal.

Flame Sensor

Flame current is the current which passes through the flame from the sensor to ground. The ignition module must detect a minimum flame current of 0.7 microamps or a flame proving lockout will occur. To measure flame current, connect an DC micrometer to the FC- FC+ terminals on the module. Meter should read 0.7 uA or higher. If meter reads below “0” on scale, meter leads are reversed. Disconnect power and reconnect meter leads for proper polarity.

NOTE: Proper polarity of supply voltage to the unit is necessary for flame sensing to occur. Oxidation on flame sensing rod can reduce measured current. The oxidation can be cleaned from the sensing rod using steel wool or an emery cloth.

Igniter Check

If the igniter is suspected of being defective then the following test may be carried out;

1.Ensure that the power and gas is switched off before servicing.

2.To test the igniter, disconnect the igniter leads from their terminal connections.

3.Using a multimeter set the Ohm’s scale and place one of the meter leads on one of the igniter wire ends and the other meter lead on the end of the other igniter wire.

Gas Valve Setting

The gas valves used in the GS series humidifier are negative-pressure-regulated valves. The valve setting listed on the product rating plate is shown relative to atmosphere – this setting will always remain constant.

The valves come preset from the factory for the correct gas type. If an adjustment is required, use the following steps:

1.Remove the screw from the pressure port marked “out” on the back side of the gas valve.

2.Connect a hose from a digital manometer (or an inclined manometer capable of reading below 0.1”w.c.) to the “out” pressure port.

3.Activate the humidifier and measure the gas valve pressure once the valve is energized and a flame is established in the combustion chamber. Verify this pressure to the pressure listed on the unit specification label.

4.If the pressure needs adjusting, remove the locking cap on the top of the gas valve.

5.Below the locking cap is an adjustment screw. Increase the pressure by turning the adjustment screw clockwise, decrease by turning counter-clockwise.

NOTE: The pressure will fluctuate slightly as the unit operates, especially with very sensitive measuring devices. Use the mean pressure value as the set pressure.

- 31 -

Image 35
Contents Installation User & Maintenance Guide For Your Safety Table Of Contents Principle of Operation Model Designation General SpecificationsDelivery Receiving & Unpacking EquipmentModel Specification Figure #1 Typical Installation Indoor Side Clearance Locating and MountingGAS GAS PipingDirect Vent Guidelines Combustion AIR RequirementsGeneral Requirements Exhaust VentingFigure #7 Vertical Venting Application Using B or BH Venting Figure # Co-venting Application Using B Vent Only Recommended B-Venting Manufacturers Installation as a Category I ApplianceBH Vent Manufacturers Installation as a Category III ApplianceAdditional Requirements When Venting Through a Sidewall Electrical Primary WiringLOW Voltage Control Wiring 600V/3ph 5 6 7 8 9 10 11 12 13 14 15 16 17 Drain Line Control InstallationPlumbing Fill Water Supply LineMounting GS Outdoor InstallationAUX Drain Port Steam Lines and Condensate LineFigure # Gstc Outdoor Typical Installation Rooftop TOP Figure #17 Gas Piping GAS PipingExhaust Venting Outdoor Units Electrical InstallationAuxiliary Drain Figure #21 Fill Water ConnectionSteam Lines CombustionWater Management Filling the System Start UP ProcedureSTART-UP Checklist Testing the Ignition Safety SHUT-OFFTaking OUT of Operation Starting the HumidifierGS Inspection Check List Factory for more information Supply Water LineWater Quality Scale ManagementGstc Models Safety InstructionsFault Conditions Draining the TankMandatory Maintenance Schedule Figure #26 Cleaning Tank Access Cleaning the Steel TankBurner Service Checks Combustion BlowerServicing the Unit Burner Removal and Installation Consult Factory Prior to the Replacement of ANY ComponentHot Surface Igniter and Flame Sensor Replacement Gas Valve Replacement Removal and Installation of the Combustion BlowerFloat Chamber Replacement Air Switch ReplacementFill Valve Replacement Ignition Module ReplacementTransformer Replacement Fill Box Replacement Drain Pump ReplacementRemoval of Heat Exchanger Figure #38 Heat Exchange AssemblyPage Analog Channel Maintenance GSPDAY Drain Keep WarmBlowdown GSP Maintenance ShutdownInput Channel Time ProportioningNortec TC Controller System Status 1 Main Menu System Status User Settings Status LockoutSystem Status 2 System Status Service IntervalMain Menu System Status Service Level User Settings Service Level 1Service Level 2 User Settings 1 Main Menu System Status Service Level User Settings User Settings 2Type User Settings 3Product name Service Level password protectedUser Settings password protected Diagnostics safety loop protectedScreen Start Date Service intervalSafety sensors RemainingService history Service LevelService interval Tank Drain Fault historyBurners Tank Pre-CleanShort Cycle Delay Date User SettingsDate / Time Units Time of dayFtbd Hours Language ControlsWater Management Float Check Ftbd HourBlowdown Rate Control Input Fill Corrctn correctionDrain Corrctn correction Drain CoolCalibrate Transducer InputCapacity Limit Fault List Fault GIF-X See Fault List Page GS Series Internal Components Spare Parts Igniter / flame sensor gasket Page GS Series Indoor Cabinetry Spare Parts GS Series Outdoor Cabinetry Exploded View GS Outdoor Spare Parts List Page InstructionsAssembly GS Quick Reference Limited Warranty Walter Meier Climate USA Inc

GS Series specifications

Nortec Industries has established itself as a leader in the field of industrial automation, particularly with the introduction of its GS Series. This series is designed to cater to the needs of a diverse range of industries, providing advanced solutions for modern manufacturing challenges. The GS Series embodies a perfect blend of technology, precision, and versatility, designed to enhance productivity and efficiency.

One of the standout features of the GS Series is its modular design. This allows for easy customization and scalability, making it a suitable choice for businesses of any size. Users can configure their systems to meet specific operational requirements, ensuring that they get the most out of their investment. The modularity of the GS Series enables companies to start small and expand their operations as needed without extensive overhauls.

Another key characteristic of the GS Series is its incorporation of cutting-edge technologies. This series leverages artificial intelligence and machine learning algorithms to optimize production processes. These technologies enable the system to learn from real-time data, making adjustments that can significantly boost efficiency and reduce waste. Furthermore, the GS Series features advanced sensors and automation tools that allow for precise monitoring and control of manufacturing processes, ensuring that quality standards are consistently met.

The GS Series is also built with robust connectivity options, allowing for seamless integration with existing enterprise systems. This interoperability is crucial in today’s fast-paced business environment, where data-driven decision-making is key to maintaining a competitive edge. The ability to connect with Internet of Things (IoT) devices enhances the flexibility of the GS Series, enabling manufacturers to gather and analyze data from multiple sources for more informed operations.

Safety features are paramount in the design of the GS Series. Nortec Industries prioritizes the well-being of its operators by incorporating numerous safety protocols and fail-safes within the system. These features not only comply with industry standards but also ensure that operations can continue without interruptions caused by safety concerns.

In summary, Nortec Industries' GS Series represents a significant advancement in industrial automation. With its modular design, integration of AI and machine learning, robust connectivity, and inherent safety features, the GS Series is poised to drive efficiency and productivity across various sectors. Companies looking to enhance their manufacturing capabilities would find the GS Series an invaluable asset in navigating the complexities of modern production environments.