Nortec Industries GS Series manual Exhaust Venting Outdoor Units, Electrical Installation

Page 24

Figure #18

GasPiping

system can be damaged is by the failure of both devices.

EXHAUST VENTING - OUTDOOR UNITS

￿All required exhaust venting is provided with each GS Outdoor model, by Nortec, including rain cap and storm collar. All venting components external to the unit are shipped with the unit and must be installed on site. Refer to Figure #19 for venting components.

Figure #19

Exhaust - Outdoor Units

Rain Cap

All Venting provided by Nortec

Extension Pipe

Storm Collar

￿Each vent length and the rain cap have a built-in mechanical locking band and gasket. Simply push together each component to the stop bead, which provides an air & water-tight seal. Then tighten the integrated locking band on each component to complete the installation of the exhaust venting.

￿The rain cap must extend at least 2 feet above any ridge within 10 feet of the unit. The exhaust venting can be extended using additional vent lengths purchased from Nortec.

ELECTRICAL INSTALLATION

￿Power and control wiring is to be routed into the humidifier through the pipe chase in the base pan of the outdoor models located in the burner area.

￿Installation details for primary and low voltage control wiring are the same as for indoor units.

￿A field supplied NEMA rated weatherproof disconnect switch must be mounted external to the GS Outdoor unit to allow for power interruption during servicing and/or maintenance. A mounting plate, located on the front of each outdoor model above the electrical access door, is available for mounting of the disconnect switch. Two electrical conduits are provided for routing the primary wiring to the disconnect switch and then back inside the enclosure to the main power terminal strip. See Figure #20 for details.

Figure #20

Electrical Box

Disconnect box

(By others)

Primary wiring

(By others)

- 20 -

Image 24
Contents Installation User & Maintenance Guide For Your Safety Table Of Contents Principle of Operation General Specifications DeliveryReceiving & Unpacking Equipment Model DesignationModel Specification Figure #1 Typical Installation Indoor Locating and Mounting Side ClearanceGAS Piping GASCombustion AIR Requirements Direct Vent GuidelinesExhaust Venting General RequirementsFigure #7 Vertical Venting Application Using B or BH Venting Figure # Co-venting Application Using B Vent Only Installation as a Category I Appliance Recommended B-Venting ManufacturersInstallation as a Category III Appliance Additional Requirements When Venting Through a SidewallBH Vent Manufacturers Primary Wiring LOW Voltage Control WiringElectrical 600V/3ph 5 6 7 8 9 10 11 12 13 14 15 16 17 Control Installation PlumbingFill Water Supply Line Drain LineGS Outdoor Installation AUX Drain PortSteam Lines and Condensate Line MountingFigure # Gstc Outdoor Typical Installation Rooftop TOP GAS Piping Figure #17 Gas PipingElectrical Installation Exhaust Venting Outdoor UnitsFigure #21 Fill Water Connection Auxiliary DrainCombustion Water ManagementSteam Lines Start UP Procedure START-UP ChecklistTesting the Ignition Safety SHUT-OFF Filling the SystemStarting the Humidifier Taking OUT of OperationGS Inspection Check List Supply Water Line Factory for more informationScale Management Water QualitySafety Instructions Fault ConditionsDraining the Tank Gstc ModelsMandatory Maintenance Schedule Cleaning the Steel Tank Figure #26 Cleaning Tank AccessService Checks Combustion Blower Servicing the UnitBurner Consult Factory Prior to the Replacement of ANY Component Hot Surface Igniter and Flame Sensor ReplacementBurner Removal and Installation Removal and Installation of the Combustion Blower Gas Valve ReplacementAir Switch Replacement Float Chamber ReplacementIgnition Module Replacement Transformer ReplacementFill Valve Replacement Drain Pump Replacement Fill Box ReplacementFigure #38 Heat Exchange Assembly Removal of Heat ExchangerPage Maintenance GSP DAY DrainKeep Warm Analog ChannelMaintenance Shutdown Input ChannelTime Proportioning Blowdown GSPNortec TC Controller Main Menu System Status User Settings Status Lockout System Status 1System Status Service Interval System Status 2Service Level 1 Main Menu System Status Service Level User SettingsService Level 2 User Settings 1 User Settings 2 Main Menu System Status Service Level User SettingsUser Settings 3 TypeService Level password protected User Settings password protectedDiagnostics safety loop protected Product nameScreen Service interval Safety sensorsRemaining Start DateService Level Service intervalService history Fault history Tank DrainTank Pre-Clean Short Cycle DelayBurners User Settings Date / Time UnitsTime of day DateLanguage Controls Water ManagementFtbd Hours Ftbd Hour Blowdown RateFloat Check Fill Corrctn correction Drain Corrctn correctionDrain Cool Control InputTransducer Input Capacity LimitCalibrate Fault List Fault GIF-X See Fault List Page GS Series Internal Components Spare Parts Igniter / flame sensor gasket Page GS Series Indoor Cabinetry Spare Parts GS Series Outdoor Cabinetry Exploded View GS Outdoor Spare Parts List Page InstructionsAssembly GS Quick Reference Limited Warranty Walter Meier Climate USA Inc

GS Series specifications

Nortec Industries has established itself as a leader in the field of industrial automation, particularly with the introduction of its GS Series. This series is designed to cater to the needs of a diverse range of industries, providing advanced solutions for modern manufacturing challenges. The GS Series embodies a perfect blend of technology, precision, and versatility, designed to enhance productivity and efficiency.

One of the standout features of the GS Series is its modular design. This allows for easy customization and scalability, making it a suitable choice for businesses of any size. Users can configure their systems to meet specific operational requirements, ensuring that they get the most out of their investment. The modularity of the GS Series enables companies to start small and expand their operations as needed without extensive overhauls.

Another key characteristic of the GS Series is its incorporation of cutting-edge technologies. This series leverages artificial intelligence and machine learning algorithms to optimize production processes. These technologies enable the system to learn from real-time data, making adjustments that can significantly boost efficiency and reduce waste. Furthermore, the GS Series features advanced sensors and automation tools that allow for precise monitoring and control of manufacturing processes, ensuring that quality standards are consistently met.

The GS Series is also built with robust connectivity options, allowing for seamless integration with existing enterprise systems. This interoperability is crucial in today’s fast-paced business environment, where data-driven decision-making is key to maintaining a competitive edge. The ability to connect with Internet of Things (IoT) devices enhances the flexibility of the GS Series, enabling manufacturers to gather and analyze data from multiple sources for more informed operations.

Safety features are paramount in the design of the GS Series. Nortec Industries prioritizes the well-being of its operators by incorporating numerous safety protocols and fail-safes within the system. These features not only comply with industry standards but also ensure that operations can continue without interruptions caused by safety concerns.

In summary, Nortec Industries' GS Series represents a significant advancement in industrial automation. With its modular design, integration of AI and machine learning, robust connectivity, and inherent safety features, the GS Series is poised to drive efficiency and productivity across various sectors. Companies looking to enhance their manufacturing capabilities would find the GS Series an invaluable asset in navigating the complexities of modern production environments.