PIPING
Standard Munchkin boiler
Retrofit piping (zoning with valves) Domestic water heating mode
Drawing 1B
zone valves |
|
|
|
OFF | OFF | OFF | OFF |
|
|
| |
P1 |
|
|
|
|
|
| flow |
purging |
|
| bypass |
valves |
|
| valve |
V1 |
|
|
|
|
|
| |
|
| mixing valve | |
|
|
| cold |
|
|
| water |
T/P |
|
|
|
Munchkin boiler |
| Super Stor | |
| indirect DHW tank | ||
|
| ||
NOTES: |
|
|
|
1.This drawing is meant to show system piping concept only.
Installer is responsible for all equipment & detailing required by local codes.
2.Adjust flow bypass valve for the following minimum boiler flow rates in any operating mode: Munchkin model 399M: 16 gpm
3.The minimum pipe size for connecting a Super Stor water heater is 1 inch.
4.The minimum pipe size for connecting a Munchkin boiler is 1.25 inches.
5.All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.
6.The
7.Install a minimum of 12 diameters of straight pipe upstream of all circulators.
8.A purging valve may be used .in lieu of the ball valve / hose bib combination shown
Fig.
22