INSTALLATION INSTRUCTIONS

GAS OPERATED BOILERS

MODELS:

M24G100A - 4SP

M24G200A - 4SP

M36G100A - 4SP

M36G200A - 4SP

M36G300A - 4SP

CAUTION: BE SURE TO READ:

Keep this appliance area free and clear from combustibles.

Do not obstruct the flow of combustion and ventilation air.

Keep this manual for future reference.

This installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas code, ANSI Z223.1-Latest Edition. For installation in Canada, this appliance is to be in accordance with the current CAN/CGA-B149(.1 or .2) Installation Code for Gas Burning Appliances and Equipment and/or Local Codes.

This applicance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electric Code, ANSI/NFPA70-Latest Edition. For installation in Canada, All electrical connections are to be made in accordance with CSA C22.1 Canadian Electrical Code Part 1 and/or Local Codes.

The boiler and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressure in excess of 1/2 psig (3.45 k/PA).

The boiler must be isolated from the gas supply system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.45 k/PA).

The wiring diagram label is located on the inside of the Lift-Off Front Panel.

This product must be installed in a room with adequate air supply.

Do not place any objects on or directly against the unit as to block air openings into the combustion chamber.

Clearances from both combustible and non-combustible construction are 3” (76mm) from side walls, 6” (152mm) from rear wall. With lower deflector plate, shown on page 4, installed this unit is suitable for Installation on Com- bustible Floors.

This unit is serviceable from the front, do not install in such a manner where a service person cannot remove front panels.

INSTALLING LEGS:

Some models are shipped without legs. A separate carton will contain the legs. If your model is received this way, be sure to follow the installation instruction sheet packed with the legs.

LEVELING:

In order for the boiler to drain correctly, it is important to use a level on cabinet top both left and right and front-to- back. If not level, adjust feet. On compartment cookers, check the interior shelves for level condition.

LOWER DEFLECTOR PLATE:

The lower deflector plate must be installed on the boiler. Be sure to follow the installation instructions located on page 4.

1

Image 4
Contents GAS Operated Boiler Table of Contents Introduction HOW to USE this Manual IntroductionTo the Kitchen Manager Theory of Operation for GAS BoilerInstallation Instructions Installing LegsGAS Operated Boilers Models LevelingGAS Service Connections Electric Service ConnectionService Connections Gas Operated BoilersLower Deflector Assembly Operating Instructions First Check to be Sure ThatIf GAS Pressure is LOW AdjustmentsIf GAS Pressure is TOO High Setting the Boiler Control Pressure Switches Pressure Control Switch AdjustmentGeneral TROUBL-SHOOTING Trouble Possible Cause RemedyGeneral TROUBL-SHOOTING Testing Procedure Water Control Board Testing ProcedureIllustrated Parts List Item no Part DescriptionPressure Switch Box Control Box Assembly, with and without Cover Plumbing, Left Side Gas Boiler Front View Gas Boiler, 24, 200K Gas Train, 200K BTU Boiler Shown Gas Train, 200K Boiler Shown Electrical Information Electrical Information Cleaning the Boiler MaintenanceCleaning Instructions Maintenance Application Instructions General NotesDo not Reuse Container