Market Forge Industries M36G200A-4SP manual General TROUBL-SHOOTING, Trouble Possible Cause Remedy

Page 11

GENERAL TROUBL-SHOOTING

TROUBLE

 

POSSIBLE CAUSE

 

REMEDY

Pilot will not ignite or does not hold.

1.

Gas not reaching unit.

1.

Check to make sure gas is on

 

2.

Main “gas cock knob” not in

 

and gas line is purged of air.

 

 

 

 

 

ON position.

2.

Depress and turn “main gas

 

3.

Air pocket or clog in gas line.

 

cock” to pilot position - (refer to

 

 

lighting instructions).

 

4.

Defective wiring or poor con-

 

 

3. Purge or blow out gas line.

 

 

nection at pilotstat power unit.

 

 

4. Check - replace or tighten.

 

5.

Defective switching across

 

 

 

 

 

either the water level control or

5.

Make continuity check - replace

 

 

pressure switches.

 

units that are defective.

 

6.

Defective gas valve.

6.

Replace gas valve.

Water enters boiler very slowly.

1.

Clogged strainer screen on

1.

Clean or replace strainer

 

 

water fill solenoid valve

 

screen. (P/N 08-4871).

 

2.

Debris or lime accumulation on

2.

Clean valve seat

 

 

seat of water fill valve.

 

 

Boiler overfills with water

1.

Probes scaled.

1.

Clean.

 

2.

Water supply valve fails to

2.

Clean valve seat or replace

 

 

close.

 

valve.

 

3.

Defective water level control.

3.

Follow the test procedure on

 

 

 

 

page 11. Replace if defective.

 

 

 

 

 

Main Burners will not ignite or will

1.

No water in boiler.

1.

Check to be sure water switch

not remain lighted.

2.

Main gas cock or supply line

 

is on. Check to be sure main

 

 

water supply is on and the elec-

 

 

not open.

 

 

 

 

trical supply to unit is on.

 

3.

Pressure switch set too low.

 

 

2.

Open.

 

4.

No voltage to gas valve.

 

3. Reset - if continuity check

 

5.

Gas valve defective.

 

 

shows to be defective - replace.

 

 

 

4.

Check main fuse.

 

 

 

5.

Replace.

Boiler fails to build up any pressure

1.

Check to see that main gas is

1.

Turn on.

when the water is at the correct

 

turned on.

2. Turn to burners “on”.

level and the fuel switch is turned

2.

Check to see that gas valve is

3. Check for voltage thru right

on.

 

in burners “on” position.

 

 

 

side of control board, replace if

 

 

 

 

 

3.

Current flow is broken at water

 

defective.

 

 

level control (ascertain with

4. Re-adjust to proper setting -

 

 

continuity check).

 

 

 

refer to instruction for re-adjust-

 

 

 

 

 

4.

Current flow is broken at pres-

 

ment, replace if defective.

 

 

sure control or high limit control

 

 

 

 

switches (ascertain with conti-

 

 

 

 

nuity check).

 

 

Water level in gauge glass

1.

Top shutoff valve on water

1.

Open.

fluctuates up and down.

 

gauge glass is closed.

 

 

 

 

 

 

 

8

Image 11
Contents GAS Operated Boiler Table of Contents Theory of Operation for GAS Boiler Introduction HOW to USE this ManualIntroduction To the Kitchen ManagerLeveling Installation InstructionsInstalling Legs GAS Operated Boilers ModelsElectric Service Connection GAS Service ConnectionsGas Operated Boilers Service ConnectionsLower Deflector Assembly First Check to be Sure That Operating InstructionsIf GAS Pressure is TOO High AdjustmentsIf GAS Pressure is LOW Pressure Control Switch Adjustment Setting the Boiler Control Pressure SwitchesTrouble Possible Cause Remedy General TROUBL-SHOOTINGGeneral TROUBL-SHOOTING Water Control Board Testing Procedure Testing ProcedureItem no Part Description Illustrated Parts ListPressure Switch Box Control Box Assembly, with and without Cover Plumbing, Left Side Gas Boiler Front View Gas Boiler, 24, 200K Gas Train, 200K BTU Boiler Shown Gas Train, 200K Boiler Shown Electrical Information Electrical Information Cleaning Instructions MaintenanceCleaning the Boiler Maintenance General Notes Application InstructionsDo not Reuse Container