GENERAL TROUBL-SHOOTING
TROUBLE |
| POSSIBLE CAUSE |
| REMEDY | |
Pilot will not ignite or does not hold. | 1. | Gas not reaching unit. | 1. | Check to make sure gas is on | |
| 2. | Main “gas cock knob” not in |
| and gas line is purged of air. | |
|
|
| |||
|
| ON position. | 2. | Depress and turn “main gas | |
| 3. | Air pocket or clog in gas line. |
| cock” to pilot position - (refer to | |
|
| lighting instructions). | |||
| 4. | Defective wiring or poor con- |
| ||
| 3. Purge or blow out gas line. | ||||
|
| nection at pilotstat power unit. | |||
|
| 4. Check - replace or tighten. | |||
| 5. | Defective switching across | |||
|
|
| |||
|
| either the water level control or | 5. | Make continuity check - replace | |
|
| pressure switches. |
| units that are defective. | |
| 6. | Defective gas valve. | 6. | Replace gas valve. | |
Water enters boiler very slowly. | 1. | Clogged strainer screen on | 1. | Clean or replace strainer | |
|
| water fill solenoid valve |
| screen. (P/N | |
| 2. | Debris or lime accumulation on | 2. | Clean valve seat | |
|
| seat of water fill valve. |
|
| |
Boiler overfills with water | 1. | Probes scaled. | 1. | Clean. | |
| 2. | Water supply valve fails to | 2. | Clean valve seat or replace | |
|
| close. |
| valve. | |
| 3. | Defective water level control. | 3. | Follow the test procedure on | |
|
|
|
| page 11. Replace if defective. | |
|
|
|
|
| |
Main Burners will not ignite or will | 1. | No water in boiler. | 1. | Check to be sure water switch | |
not remain lighted. | 2. | Main gas cock or supply line |
| is on. Check to be sure main | |
|
| water supply is on and the elec- | |||
|
| not open. |
| ||
|
|
| trical supply to unit is on. | ||
| 3. | Pressure switch set too low. |
| ||
| 2. | Open. | |||
| 4. | No voltage to gas valve. | |||
| 3. Reset - if continuity check | ||||
| 5. | Gas valve defective. | |||
|
| shows to be defective - replace. | |||
|
|
| 4. | Check main fuse. | |
|
|
| 5. | Replace. | |
Boiler fails to build up any pressure | 1. | Check to see that main gas is | 1. | Turn on. | |
when the water is at the correct |
| turned on. | 2. Turn to burners “on”. | ||
level and the fuel switch is turned | 2. | Check to see that gas valve is | |||
3. Check for voltage thru right | |||||
on. | |||||
| in burners “on” position. | ||||
|
|
| side of control board, replace if | ||
|
|
|
| ||
| 3. | Current flow is broken at water |
| defective. | |
|
| level control (ascertain with | 4. | ||
|
| continuity check). | |||
|
|
| refer to instruction for | ||
|
|
|
| ||
| 4. | Current flow is broken at pres- |
| ment, replace if defective. | |
|
| sure control or high limit control |
|
| |
|
| switches (ascertain with conti- |
|
| |
|
| nuity check). |
|
| |
Water level in gauge glass | 1. | Top shutoff valve on water | 1. | Open. | |
fluctuates up and down. |
| gauge glass is closed. |
|
| |
|
|
|
|
|
8